DIRECT ACCESS TO SET POINT

When the device is in AUTO mode and in “Normal Display Mode”, it is possible to access directly to set point modification (SP or SP2).

Pushing s or t for more than 2 s, the set point will begin changing.

The new set point value becomes operative since no pushbutton has been depressed at the end of 2 s timeout.

MANUAL FUNCTION

The MANUAL function can be accessed (only if enabled by P34=On) by depressing the MAN pushbutton for more than 1 sec.

The command is accepted and executed only if the display is in "Normal Display Mode".

When in MANUAL mode the LED's MAN annunciator will light up while the lower display shows the power output values.

The value of "rEV" is shown in the two most signifi- cant digit field while the value of "dir" (if present) is shown in the two less significant digit field.

The decimal point between the two values will be flashing to indicate instrument in manual mode. NOTE :

- A graphic symbol "

" is used for "rEV"= 100

- A graphic symbol "

" is used for "dir"= 100

The power output can be modified by using s and t pushbuttons.

In manual mode the output resolution is equal to 1%.

By depressing, for more than 1 second, MAN pushbutton the device returns in AUTO mode.

The transfer from AUTO to MANUAL and viceversa is bumpless (this function is not provided if integral action is excluded).

If transfer from AUTO to MANUAL is performed during the first part of SMART algorithm (TUNE) when returning in AUTO the device will be forced automatically in the second part of the SMART algorithm (ADAPTIVE).

At power up the device will be in the AUTO mode or as it was left prior to power shut down depending on P35 configuration selection. NOTE:When start up occurs in Manual mode with power output set to 0, the control outputs will be in accordance with the following formula: "rEV" output - "dir" output = 0

LAMP TEST

When it is desired to verify the display efficiency, push FUNC pushbutton for more than 10 s. The instrument will turn ON, with a 50 % duty cycle, all the LEDs of the display (we define this function "LAMP TEST").

No time out is applied to the LAMP TEST. When it is desired to come back to the normal display mode, push FUNC pushbutton again. During the LAMP TEST the instrument continues to control the process but no keyboard functions are available (exception made for the FUNC pushbutton).

20

1604-7-1-AB.p65

20

5/16/00, 10:50 AM

Image 23
Contents Chromalox Contents III Model identificationScrew Mounting RequirementsOutline and CUT-OUT Dimensions Outline and CUT OUT DimensionsMeasuring Inputs TC Input Connection DiagramsLinear Input RTD InputOUT Logic Input Safety noteRelay Outputs Load Operating Voltage Inductive LoadsLinear Output Serial Interface Power Line WiringWhen the Neutral line is present, connect it to terminal Open Input Circuit Preliminary Hardware SettingsInput Type TC-RTDSEr4 = Byte format for serial link SEr1 = Serial interface protocolOFF SEr3 = Baude rate for serial linkP5 = Output 1 function P2 = Decimal point positionP3 = Initial scale value P4 = Full scale valueP9 = Output 2 function. nonE = output not used P10 = Alarm 1 operating modeP7 = analog retransmission initial scale value P8 = analog retransmission full scale valueP15 = Alarm 2 hysteresis value P12 = Alarm 2 operating modeP14 = Alarm 2 threshold value P22 = Cooling media P19 = Displayed value of the main power outputP18 = Main control output action P20 = Secondary control output actionP29 = Displayable protected parameters P24 = Alarm 1 actionP26 = Alarm 2 action P28 = Offset adjustment added to the measured valueP34 = Manual function P36 = Timeout selectionP38 = Output safety value P44 = Operative set point alignment at instrument start up P41 = Control action typeP43 = Set point indication REM SP2 MAN IndicatorsDisplay Function SP SP2 Selection MAN =Lamp Test Direct Access to SET PointManual Function Serial Link Smart functionAL2 Alarm 2 threshold RSt Manual reset of the alarmsAL1 Alarm 1 threshold HSA1 Alarm 1 hysteresisIntegral time Output 3 cycle timeHysteresis for ON/OFF control action Relative Cooling gainGrd1 Ramp applied to an increasing set point change TOL Time duration of the output power limiter soft startUnderrange Error MessagesError Messages OverrangeError List Inputs Thermocouple General SpecificationsGeneral Informations Logic Input Linear InputsOutputs SET PointsControl Actions Output AlarmsStop bit one Address MaintenanceSerial Communication Interface HSA1, HSA2 Appendix a Default ParametersParameter Default Value = OFFER0 ParaP44 Appendix A.3 Appendix A.4 Emerson Electric CO Chromalox