Chromalox 1604-7 P7 = analog retransmission initial scale value, P10 = Alarm 1 operating mode

Page 15

P7 = analog retransmission - initial scale value.

Available only when P5 = Pv.rt or SP.rt. It is programmable from -1999 to 4000.

The decimal point will be positioned as selected with P2 parameter.

P8 = analog retransmission - full scale value.

Available only when P5 = Pv.rt or SP.rt. It is programmable from -1999 to 4000.

The decimal point will be positioned as selected with P2 parameter.

P9 = Output 2 function. nonE = output not used.

rEv

= Out 2 is used as control output with

 

reverse action.

dir

= Out 2 is used as control output with direct

action.

AL1.P =it is used as Alarm 1 output and the alarm 1 is programmed as process alarm.

AL1.b = it is used as Alarm 1 output and the alarm 1 is programmed as band alarm.

AL1.d = it is used as Alarm 1 output and the alarm1 is programmed as deviation alarm.

NOTE: If P9 has been changed to "rEv", the cycle time (Cy2) will be forced to 15 seconds.

If P9 has been changed to "dir", the cycle time (Cy2) will be forced to:

10 s when P22 is equal to "AIr"

4 s when P22 is equal to "OIL"

2 s when P22 is equal to "H2O".

P10 = Alarm 1 operating mode

Available only when P9 is equal to "AL1.P", "AL1.b" or "AL1.d".

H.A. = High alarm (outside for band alarm) with automatic reset (latched).

L.A. = Low alarm (inside for band alarm) with automatic reset (latched).

H.L. = High alarm (outside band) with manual re- set (latched).

L.L.= Low alarm (inside band) with manual reset (latched).

P11 = Output 3 function nonE = output not used.

rEv

= Out 3 is used as control output with

 

reverse action.

dir

= Out 3 is used as control output with direct

 

action.

AL2.P =it is used as Alarm 2 output and the alarm 2 is programmed as process alarm.

AL2.b = it is used as Alarm 2 output and the alarm 2 is programmed as band alarm.

AL2.d = it is used as Alarm 2 output and the alarm 2 is programmed as deviation alarm.

NOTES: 1) If P11 has been changed to "rEv", the cycle time (Cy3) will be forced to 15 seconds.

If P11 has been changed to "dir", the cycle time (Cy3) will be forced to:

10 s when P22 is equal to "AIr"

4 s when P22 is equal to "OIL"

2 s when P22 is equal to "H2O".

2)The relations among P5, P9 and P11 are shown by the following notes:

-one Out only can be configured as "rEv" output.

-one Out only can be configured as "dir" output.

-if no Output is configured as control output the instrument will operate as an indicator.

12

1604-7-1-AB.p65

12

5/16/00, 10:50 AM

Image 15
Contents Chromalox Contents III Model identificationScrew Mounting RequirementsOutline and CUT-OUT Dimensions Outline and CUT OUT DimensionsMeasuring Inputs TC Input Connection DiagramsLinear Input RTD InputLogic Input Safety note Relay OutputsOUT Inductive Loads Linear OutputLoad Operating Voltage Serial Interface Power Line WiringWhen the Neutral line is present, connect it to terminal Open Input Circuit Preliminary Hardware SettingsInput Type TC-RTDSEr4 = Byte format for serial link SEr1 = Serial interface protocolOFF SEr3 = Baude rate for serial linkP5 = Output 1 function P2 = Decimal point positionP3 = Initial scale value P4 = Full scale valueP9 = Output 2 function. nonE = output not used P10 = Alarm 1 operating modeP7 = analog retransmission initial scale value P8 = analog retransmission full scale valueP12 = Alarm 2 operating mode P14 = Alarm 2 threshold valueP15 = Alarm 2 hysteresis value P22 = Cooling media P19 = Displayed value of the main power outputP18 = Main control output action P20 = Secondary control output actionP29 = Displayable protected parameters P24 = Alarm 1 actionP26 = Alarm 2 action P28 = Offset adjustment added to the measured valueP36 = Timeout selection P38 = Output safety valueP34 = Manual function P41 = Control action type P43 = Set point indicationP44 = Operative set point alignment at instrument start up Indicators Display FunctionREM SP2 MAN SP SP2 Selection MAN =Direct Access to SET Point Manual FunctionLamp Test Serial Link Smart functionAL2 Alarm 2 threshold RSt Manual reset of the alarmsAL1 Alarm 1 threshold HSA1 Alarm 1 hysteresisIntegral time Output 3 cycle timeHysteresis for ON/OFF control action Relative Cooling gainGrd1 Ramp applied to an increasing set point change TOL Time duration of the output power limiter soft startUnderrange Error MessagesError Messages OverrangeError List General Specifications General InformationsInputs Thermocouple Logic Input Linear InputsSET Points Control ActionsOutputs Output AlarmsMaintenance Serial Communication InterfaceStop bit one Address HSA1, HSA2 Appendix a Default ParametersParameter Default Value = OFFER0 ParaP44 Appendix A.3 Appendix A.4 Emerson Electric CO Chromalox