Five Star Comprehensive Manual for Swimming Pool Heaters - Installation and Parts Information

Page 10

CONTROL PANEL INDEXING

The exhaust discharges vertically from outside the vent cover. The heater control panel assembly on top of the jacket can be turned to any of six positions for convenient access to the panel as follows:

1.Unbolt and separate the jacket halves.

2.Pull hair pin clips.

3.Depress plastic clips on the control panel assembly.

4.Lift panel off of support plate.

5.Turn the assembly to the desired position and snap in place.

6.Make sure that the operating controls can be adjusted without having to lean over the exhaust vent.

7.Replace hair pin clips.

8.Replace jacket halves and bolts and tighten.

5

4

3

2

1

2732 1296

FIGURE 9: Indexing Control Panel

INDOOR INSTALLATION

INSTRUCTIONS

NOTICE: Local codes may restrict indoor installations. Consult local code officials.

Risk of asphyxiation if exhaust is not correct- ly vented. Follow venting instructions exactly when installing heater. Do not use a draft hood with this heater,

as the exhaust is under pressure from the burner blower and a draft hood will allow exhaust fumes to blow into the room housing the heater. Exhaust venting to the outdoors is required for all indoor installations.

Risk of explosion if an LP (propane) gas unit is installed in a pit or other low spot. LP gas is heavier than air. Do not install the heater using LP gas in pits or other locations where gas might collect. Consult your local building code officials to determine installation require- ments of heater relative to LP gas storage tanks and filling equipment. Installation must meet the requirements for the Standard for the Storage and Handling of Liquified Petroleum Gases, ANSI/NFPA 58 (latest edition). Consult local codes and fire protection authorities about specific installation restrictions.

The heater is design certified by CSA International for installation on combustible flooring; in alcoves; in base- ments; in closets or utility rooms.

INSTALLATION IN A GARAGE

OR UTILITY ROOM

Risk of fire and explosion if installed at floor level in an automotive garage or near gasoline or flamma- ble liquid storage. Gasoline fumes are heavier than air and will settle to floor level in closed spaces. Gasoline fumes and spilled gasoline or other volatile liquids (such as some paints and varnishes) will travel across the floor and can be ignited by a gas appliance. In a utility room or residential garage installation, install the heater with the base at least 18 inches above the floor. In a garage, install a rail or wall to protect the heater from physical damage by a moving vehicle.

Provide an adequate ventilation air supply (see Instruc- tions, at right). Choose a location that will avoid contami- nation by chemical fumes.

NOTICE: LPG fired heaters must not be installed in garages in Massachusetts, by order of the State Fire Marshall. For more information, call the Massachusetts State Fire Marshall’s office.

NOTICE: Combustion air contaminated by corrosive chemical fumes can damage the heater and will void the warranty (See Table 1, Page 11).

6 in. clear space above

Raise at least 18" above floor to avoid 18" flammable vapors

leave 6 in.

of clear space between

unit and

6"

 

combustible surfaces

TOP VIEW

FIGURE 10: Minimum indoor clearances - garage or utility room installation

HEATER CLEARANCES – INDOOR

The following clearances must be maintained from com- bustible surfaces:

TOP

6 INCHES

ALL SIDES

6 INCHES

VENT

6 INCHES

10

Image 10
Contents Special Instructions to Owner Sta-Rite Pool/Spa GroupTo Installer To ConsumerSafety Instructions Sequence of Operation Description of the HeaterOWNER’S Operating Instructions START-UP and OperationWhat to do if YOU Smell GAS SPA Temperature CautionOperating Instructions To Turn OFF GAS to the Appliance Operating ControlAfter START-UP Care and Maintenance Maintenance InstructionsOutdoor Installation Instructions Installation InstructionsPutting the Heater Into Service Heater Clearances OutdoorControl Panel Indexing Indoor Installation InstructionsInstallation in a Garage Or Utility Room Heater Clearances IndoorCombustion and Ventilation AIR Supply Indoor Vent InstallationOutside Vent Cover Removal Metal Flue Collar Sta-Rite Part No Vertical Venting Negative PressureMin. Height Minimum Height Connecting Special GAS Vent to the HeaterRoof Pitch Above Roof Min Brand Manufacturer Material Type SealantWater Connections Special Gas Vent Vertical or Horizontal No. of 90 ElbowsWater Piping Cool WaterModel Minimum Flow Maximum Flow 200 120 333 400 Water Flow RateWater Chemistry Chemical ValuesWater Pressure Switch Pressure Relief ValveConnect Gas Valve to End Cap Air Orifice Electrical Wiring Pressure TestingSupplying Power to the Heater GAS ConnectionsFIREMAN’S Switch Connection FuseMaximum Temperature SET Point Max Temperature Set Point ControlsDoes red Service Initial TroubleshootingHeater LED come Heater Will Not Fire a StartHeater Will Not Fire B ContinueHeater Will Not Fire C Heater Will Not Fire D Diagnostic LED’s AGS, AFS, HLS, PS, Thermistor Do not jumper a safety switch to remedy a failed switchDiagnostic LED’s SFS SFS onBurner Troubleshooting Heat Exchanger TroubleshootingRepair Parts are available from your Sta-Rite dealer 2692 Repair Parts Burner System Repair Parts Water System Repair Parts Electrical System Pool Heater Wiring Connection Diagram Pool Heater Electrical Schematic Ladder Diagram Page Page Warranty Registration Card