at least 4 feet below or horizontally from, or 1 foot above, any doors or windows or gravity air inlet to a building

At least 3 feet above any forced air inlet located within 10 feet

At least 4 feet horizontally from electric meters, gas meters, regulators and relief equipment

At least 7 feet above grade adjacent to walkways or sim- ilar traffic areas.

Allow at least 3 feet vertical clearance over vent termina- tion when terminating under an overhang or deck.

Avoid corners or alcoves where snow or wind could have an effect. Exhaust may affect shrubbery and some building materials. Keep shrubbery away from termination. To pre- vent staining or deterioration, sealing or shielding exposed surfaces may be required.

Metal Special

Support

 

Gas Vent

 

 

 

weight

 

requires

 

 

 

of pipe

 

 

Appliance

 

 

Listed

 

 

 

 

 

Adapter

 

 

 

Condensate

Terminal

 

 

 

 

Tee

 

 

 

Metal

Vent

Body

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slope at least

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4" per foot

 

 

 

 

 

 

Condensate

 

 

 

 

 

 

down towards

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3" Minimum,

drain w/Trap

condensate dr

ain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12" Maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clearance

2787 0297

FIGURE 14: Typical Special Gas Vent Pipe Installation (Horizontal-Positive Pressure)

8. Fire Hazard. Do not run the heater vent into a common vent with any other appliance. Do not run the Special Gas Vent into, through, or within any active vent such as a factory built or masonry chimney.

Table 6: Maximum Vent Length

4” Special Gas Vent (Vertical or Horizontal)*

No. of 90° Elbows

Maximum Length

0

50 Ft.

2

40 Ft.

4

30 Ft.

6

20 Ft.

*Minimum vent length is one (1) foot, or in accordance with vent manufacturer’s instructions, and local and national codes.

Horizontal vents 3’ or less in length do not require a condensate tee, but must slope down toward the outlet at 1/4” to the foot to allow condensate to drain.

Final Installation Check:

Check that horizontal vent pipe runs slope uniformly at least 1/4” per foot to condensate drain(s). No sags, no dips, no high or low spots.

Check that vent is supported at elbows, tees, and horizon- tal and vertical runs according to manufacturer’s instruc- tions and code requirements.

Check that vent supports and wall and ceiling penetrations allow free movements up, down, and sideways without putting any strains on the heater or vent body.

Check for at least six (6) inch free air clearance between the heater vent pipe and combustible materials.

Check that all joints are completely together and sealed.

WATER CONNECTIONS

The heater requires proper water flow and pressure for its operation. See Figures 15 and 16 for the recommended installation. The filter pump discharges to the filter, the fil- ter discharges to the heater, and the heater discharges directly to the pool or spa.

Table 7: Listed Thimbles and Vent Terminals (for Special Gas Vents)

Vent Brand

Wall Thimble

Horizontal Terminal

Vertical Terminal

 

 

 

 

Saf-T Vent®

(Part of Vent term.)

5490CI Horizontal Term.

5400 Cap

Saf-T CI Vent®

(Part of Vent term.)

5490CI Horizontal Term.

5400 Cap

Z-Vent

2SVSWTF04

2SVSTTF04 Tee

2SVSRCF04 Cap

 

 

 

 

15

Image 15
Contents Sta-Rite Pool/Spa Group Special Instructions to OwnerTo Consumer To InstallerSafety Instructions START-UP and Operation Description of the HeaterOWNER’S Operating Instructions Sequence of OperationSPA Temperature Caution What to do if YOU Smell GASOperating Instructions Operating Control To Turn OFF GAS to the ApplianceAfter START-UP Maintenance Instructions Care and MaintenanceHeater Clearances Outdoor Installation InstructionsPutting the Heater Into Service Outdoor Installation InstructionsHeater Clearances Indoor Indoor Installation InstructionsInstallation in a Garage Or Utility Room Control Panel IndexingIndoor Vent Installation Combustion and Ventilation AIR SupplyOutside Vent Cover Removal Vertical Venting Negative Pressure Metal Flue Collar Sta-Rite Part NoMin. Height Connecting Special GAS Vent to the Heater Minimum HeightRoof Pitch Above Roof Brand Manufacturer Material Type Sealant MinSpecial Gas Vent Vertical or Horizontal No. of 90 Elbows Water ConnectionsCool Water Water PipingChemical Values Water Flow RateWater Chemistry Model Minimum Flow Maximum Flow 200 120 333 400Pressure Relief Valve Water Pressure SwitchConnect Gas Valve to End Cap Air Orifice GAS Connections Pressure TestingSupplying Power to the Heater Electrical WiringFuse FIREMAN’S Switch ConnectionMax Temperature Set Point Controls Maximum Temperature SET PointInitial Troubleshooting Does red ServiceHeater LED come Start Heater Will Not Fire aContinue Heater Will Not Fire BHeater Will Not Fire C Heater Will Not Fire D Do not jumper a safety switch to remedy a failed switch Diagnostic LED’s AGS, AFS, HLS, PS, ThermistorSFS on Diagnostic LED’s SFSHeat Exchanger Troubleshooting Burner TroubleshootingRepair Parts are available from your Sta-Rite dealer 2692 Repair Parts Burner System Repair Parts Water System Repair Parts Electrical System Pool Heater Wiring Connection Diagram Pool Heater Electrical Schematic Ladder Diagram Page Page Warranty Registration Card