VERTICAL VENTING - NEGATIVE PRESSURE

(See Figures 11 and 12)

Vent the heater vertically in a negative pressure (positive draft) system in accordance with the National Fuel Gas Code, ANSI Z223.1, and local codes. Type “B” Double- wall vent connector is recommended; however single-wall pipe is allowed by the National Fuel Gas Code in some circumstances. Consult your local code official for detailed information. Do not use a draft hood with this heater.

To connect a negative pressure metal gas vent to the heater, order the appropriate Metal Flue Collar from the chart below:

Metal Flue Collar

Sta-Rite Part No.

4x6”77707-0076

4x8”77707-0077

1.See Table 3, below, to determine allowable vent sizes for your heater.

NOTICE: Table 3 is for installations in which the total later- al vent length (that is, the horizontal distance from the flue collar to the main vertical portion of the vent) is less than 1/2 the total vent height (the vertical distance from the flue collar to the vent termination) and which have three or less elbows in the system. For venting systems which do not meet these conditions, consult the National Fuel Gas Code, ANSI Z223.1

2.Install the metal Flue Collar in the Vent Body of the heater (located under the outside vent cover). Fasten the metal Flue Collar to the Vent Body with two #10 sheet metal screws. Use UltraCopper® silicone RTV to seal the metal Flue Collar to the Vent Body. Follow instructions supplied with the metal Flue Collar. Before connecting the metal Flue Collar to the Vent Body, wet a clean cloth or paper towel with isopropyl alcohol (rubbing alcohol) and vigorously wipe the socket of the Vent Body. Immediately wipe the cleaned surfaces dry with a clean cloth or paper towel. Repeat for the exte-

rior of the 4” end of the metal Flue Collar. Attach the metal Flue Collar to the Vent Body using the RTV sup- plied with the kit, following the instructions included with kit. Do not use a draft hood with this heater.

3.Attach the vent pipe to the metal Flue Collar with sheet-metal screws.

Risk of fire or asphyxiation if vent is not assembled according to manufacturer’s instructions or if vent parts from different manufacturers are mixed. Vent parts from different manufacturers ARE NOT interchange- able. Mixing parts from more than one manufacturer may cause leaks or damage to vent. When assembling a vent, pick one manufacturer and be sure that all vent parts come from that manufacturer and are specified by the manufac- turer for your system. Follow manufacturer’s instructions and local and National Fuel Gas Code requirements care- fully during assembly and installation.

4.Install vent pipe so that it can expand and contract freely as the temperature changes. Support the vent pipe according to applicable codes and the vent manu- facturer’s instructions. Pipe support must allow the vent pipe free movement out and back, from side to side, or up and down as necessary, without putting a strain on the heater or vent body. Slope horizontal pipe runs up from the heater at least 1/4” per foot. Install Listed condensate drains at low points where conden- sate might collect. Plumb condensate drains to a drain through hard piping or high-temperature tubing such as silicone rubber or EPDM rubber – do not use vinyl or other low temperature tubing. Follow drain manu- facturer’s installation instructions.

5.Use Listed firestops for floor and ceiling penetrations. Use Listed thimble for wall penetrations. Use a Listed roof flashing, roof jack, or roof thimble for all roof pen- etrations. Do not fill the space around the vent (that is, the clear air space in the thimble or firestop) with insulation. The roof opening must be located so that the vent is vertical.

Table 3: Permitted Minimum and Maximum Vent Heights By Size and Heater Model

Read “VERTICAL VENTING – NEGATIVE PRESSURE” (above) before using this table.

 

Type B Double Wall Vent With Type B Double Wall Connector

 

 

Model 200

Model 333

Model 400

Vent Size

Min. Height

Max. Height

Min. Height

Max. Height

Min. Height

Max. Height

 

 

 

 

 

 

 

6 in.

6 Ft.

100 Ft.

30 Ft.

100 Ft.

Not Rec.

Not Rec.

7 in.

6 Ft.

100 Ft.

10 Ft.

100 Ft.

15 Ft.

100 Ft.

8 in.

6 Ft.

100 Ft.

6 Ft.

100 Ft.

8 Ft.

100 Ft.

9 and 10 in.

6 Ft.

50 Ft.

6 Ft.

100 Ft.

6 Ft.

100 Ft.

 

Type B Double Wall Vent With Single Wall Connector

 

 

 

Model 200

Model 333

Model 400

Vent Size

Min. Height

Max. Height

Min. Height

Max. Height

Min. Height

Max. Height

 

 

 

 

 

 

 

6 in.

6 Ft.

15 Ft.

Not Rec.

Not Rec.

Not Rec.

Not Rec.

7 in.

6 Ft.

8 Ft.

10 Ft.

20 Ft.

15 Ft.

50 Ft.

8 in.

Not Rec.

Not Rec.

6 Ft.

20 Ft.

8 Ft.

20 Ft.

9 in.

Not Rec.

Not Rec.

Not Rec.

Not Rec.

6 Ft.

6 Ft.

10 in.

Not Rec.

Not Rec.

Not Rec.

Not Rec.

Not Rec.

Not Rec.

12

Image 12
Contents Special Instructions to Owner Sta-Rite Pool/Spa GroupTo Installer To ConsumerSafety Instructions Description of the Heater OWNER’S Operating InstructionsSequence of Operation START-UP and OperationSPA Temperature Caution What to do if YOU Smell GASOperating Instructions To Turn OFF GAS to the Appliance Operating ControlAfter START-UP Care and Maintenance Maintenance Instructions Installation Instructions Putting the Heater Into Service Outdoor Installation Instructions Heater Clearances OutdoorIndoor Installation Instructions Installation in a Garage Or Utility RoomControl Panel Indexing Heater Clearances IndoorIndoor Vent Installation Combustion and Ventilation AIR SupplyOutside Vent Cover Removal Vertical Venting Negative Pressure Metal Flue Collar Sta-Rite Part NoMin. Height Connecting Special GAS Vent to the Heater Minimum HeightRoof Pitch Above Roof Min Brand Manufacturer Material Type SealantWater Connections Special Gas Vent Vertical or Horizontal No. of 90 ElbowsWater Piping Cool WaterWater Flow Rate Water ChemistryModel Minimum Flow Maximum Flow 200 120 333 400 Chemical ValuesWater Pressure Switch Pressure Relief ValveConnect Gas Valve to End Cap Air Orifice Pressure Testing Supplying Power to the HeaterElectrical Wiring GAS ConnectionsFIREMAN’S Switch Connection FuseMaximum Temperature SET Point Max Temperature Set Point ControlsInitial Troubleshooting Does red ServiceHeater LED come Heater Will Not Fire a StartHeater Will Not Fire B ContinueHeater Will Not Fire C Heater Will Not Fire D Diagnostic LED’s AGS, AFS, HLS, PS, Thermistor Do not jumper a safety switch to remedy a failed switchDiagnostic LED’s SFS SFS onBurner Troubleshooting Heat Exchanger TroubleshootingRepair Parts are available from your Sta-Rite dealer 2692 Repair Parts Burner System Repair Parts Water System Repair Parts Electrical System Pool Heater Wiring Connection Diagram Pool Heater Electrical Schematic Ladder Diagram Page Page Warranty Registration Card