Heater Will Not Fire - B

Start

Is red “SERVICE HEATER” LED “on”

YES

NO

Is red “SERVICE SYSTEM” LED on?

YES

Verify that pump is on, filter is not blocked, and the water flow is above the minimum requirement.

YES

NO

NO

Increase POOL/SPA tempera- ture setting on Membrane Pad above actual water tem- perature. Heater should fire on demand for heat. If not, and no other red LED’s light, replace Control Board.

Service pump/filter and elimi-

CONTINUE

With pump running, adjust Water Pressure Switch to lower pressure until ‘SER- VICE SYSTEM” LED goes out. Then verify that “SER- VICE SYSTEM” LED goes on with pump off.

NO

Check that water pressure is within the adjustment range of the Pressure Switch (0-5 psig)

YES

Verify that switch wiring is OK and sensing tube is not blocked, and replace water Pressure Switch.

YES

NO

nate other flow obstructions.

Heater should fire on call for heat. Re-verify that water flow is above minimum requirement.

Minimum Flow Requirements

ModelFlow

20020 GPM

33330 GPM

40040 GPM

If water pressure is outside of adjustment range that will open switch with pump off and close switch with pump on, replace with flow switch set above minimum flow requirement.

Minimum Flow Requirements

ModelFlow

20020 GPM

33330 GPM

40040 GPM

Check whether any of the red diagnostic LED’s on back of board (AGS, AFS, SFS, HLS or PS) are “on”

NO

GO TO

“HEATER WILL NOT FIRE - C”

Page 26

YES

Go to “Diagnostic LED’s”, (Pages 28 and 29)

25

Image 25
Contents Sta-Rite Pool/Spa Group Special Instructions to OwnerTo Consumer To InstallerSafety Instructions OWNER’S Operating Instructions Description of the HeaterSequence of Operation START-UP and OperationWhat to do if YOU Smell GAS SPA Temperature CautionOperating Instructions Operating Control To Turn OFF GAS to the ApplianceAfter START-UP Maintenance Instructions Care and MaintenancePutting the Heater Into Service Installation InstructionsOutdoor Installation Instructions Heater Clearances OutdoorInstallation in a Garage Or Utility Room Indoor Installation InstructionsControl Panel Indexing Heater Clearances IndoorCombustion and Ventilation AIR Supply Indoor Vent InstallationOutside Vent Cover Removal Metal Flue Collar Sta-Rite Part No Vertical Venting Negative PressureMin. Height Minimum Height Connecting Special GAS Vent to the HeaterRoof Pitch Above Roof Brand Manufacturer Material Type Sealant MinSpecial Gas Vent Vertical or Horizontal No. of 90 Elbows Water ConnectionsCool Water Water PipingWater Chemistry Water Flow RateModel Minimum Flow Maximum Flow 200 120 333 400 Chemical ValuesPressure Relief Valve Water Pressure SwitchConnect Gas Valve to End Cap Air Orifice Supplying Power to the Heater Pressure TestingElectrical Wiring GAS ConnectionsFuse FIREMAN’S Switch ConnectionMax Temperature Set Point Controls Maximum Temperature SET PointDoes red Service Initial TroubleshootingHeater LED come Start Heater Will Not Fire aContinue Heater Will Not Fire BHeater Will Not Fire C Heater Will Not Fire D Do not jumper a safety switch to remedy a failed switch Diagnostic LED’s AGS, AFS, HLS, PS, ThermistorSFS on Diagnostic LED’s SFSHeat Exchanger Troubleshooting Burner TroubleshootingRepair Parts are available from your Sta-Rite dealer 2692 Repair Parts Burner System Repair Parts Water System Repair Parts Electrical System Pool Heater Wiring Connection Diagram Pool Heater Electrical Schematic Ladder Diagram Page Page Warranty Registration Card