General Information
Figure 1.9 - Single-/Three-phase
Delta Stator Connection
E2
240V | 240V | ||
|
| S6 | I |
|
| ||
|
| SII | S3~ |
|
|
|
|
--240V
SIX-LEAD. 600 VAG, THREE-PHASE STATOR
This type of stator has three coils and six leads (Figure 1.10). Units may be assigned any of the following voltage codes:
•"1.:' units are rated 346/600 VAG,
•"5" units are rated 277/480 VAG,
Figure 1.10 - Six-lead Stator Connection
51
1 1
277V 50HZ 480V 50 HZ 346V60HZ 600V 60 HZ
!
S2
FIELD WIRING CONNECTIONS REQUIREMENTS
The table should be used as areference for: wire type, temperature rating, and size range of output wires to be connected to the circuit breakers. Wire sizes should be in accordance with table 310.16 of the National Electric Gode (NEG).
FIELD WIRING REQUIREMENTS TABLE
|
|
|
| Circuit Breaker |
|
| |
Breaker Frame | Gircuit Breaker Range | Wire Type | Wire Temperature | Lug AWG Wire | Torque to Wire | ||
(A) | Rating | Range / (Number of | |||||
|
|
|
| ||||
|
|
|
| Gonductors) |
|
| |
Series G- JG Frame | 20 - 250 | Cu | 75c C | 180 | |||
Series G- LG Frame | 160 - 600 | Cu/AI | 75C C | ||||
|
|
|
|
|
| ||
|
|
|
|
| |||
| 15 - 100 | Cu/AI | 75c C | (#8) 40 | |||
| |||||||
Series C- FFrame |
|
|
|
| |||
|
|
|
|
|
| ||
|
|
|
|
| |||
| 60 - 200 | CulAl | 75c C | 120 | |||
| 100 - 225 | Cu/AI | 75°C | 120 | |||
Series C- J Frame | 250 | Cu | 75°C | 275 | |||
| 225 | CulAl | 75°C | 275 | |||
Series C- K Frame | 300 | CulAl | 75DC | 375 | |||
| 350 - 400 | Cu/AI | 75D C | ||||
Series C- L Frame | 450 - 500 | Cu/AI | 75°C | 275 | |||
600 | Cu/AI | 75°C | 275 | ||||
| |||||||
Series C- M Frame | 700 - 800 | Cu/AI | WC | ||||
Series C- NFrame | 900 - 1000 | Cu/AI | 75°C | 375 | |||
1200 | Cu/AI | WC | 450 | ||||
| |||||||
Series C- RFrame | 1400 - 1600 | Cu/AI | 75°C | 550 |
NOTE: All field installations must meet the National Electric Code for wire size and bending space requirements.
10