STATIONARY EMERGENCY GENERATOR INSTALLATION

~

k..Connecting this generator to an electrical illsystem normally supplied by an electric util- ity shall be by means of a transfer switch

(such as the "GTS" type transfer switch), so as to isolate the electric system from the utility distribution system when the genera- tor is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.

ACAUTIONI

t If an open bottom is used, the engine-gener- Lmator is to be installed over non-combustible

materials and should be located such that combustible materials are not capable of accumulating under the generator set.

Only qualified, competent installation contractors or electricians thoroughly familiar with applicable codes, standards and regula- tions should install this stationary emergency electric power sys- tem. The installation must comply strictly with all codes, standards and regulations pertaining to the installation.

This genset must be installed on a level surface. The base frame must be level within two (2) inches all around.

ACAUTIONI

AAfter the system has been installed, do noth-

..... ing that might render the installation in non· compliance with such codes, standards and regulations.

NOTE:

For more information about the installation of a stationary emergency system, order Engine-Generator Stationary emer- gency Electric Power Systems Installer's Guide and Reference Manual (part #046622) from an Authorized Service Dealer.

NFPA STANDARDS

The following published standards booklets pertaining to station- ary emergency electric systems are available from the National Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA 02269 or www.nfpa.org.

oNFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES.

o NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR HEALTH CARE FACILITIES.

oNFPA No. 220, STANDARD TYPES OF BUILDING CONSTRUCTION o NFPA No. 68, GUIDE FOR EXPLOSION VENTING

o NFPA No. 70, NATIONAL ELECTRICAL CODE.

Installation

NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.

NFPA No. 10, INSTALLATION, MAINTENANCE AND USE OF PORTABLE FIRE EXTINGUISHERS.

OTHER PUBLISHED STANDARDS

In addition to NFPA standards, the following information pertain- ing to the installation and use of stationary emergency electric systems is available:

Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, NY 10038,

oAGRICULTURAL WIRING HANDBOOK, obtainable from the Food and Energy Council, 909 University Avenue, Columbia, MO, 65201.

ASAE EP-364.2, INSTALLATION AND MAINTENANCE OF FARM STANDBY ELECTRIC POWER, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, M149085.

A52.1, AMERICAN NATIONAL STANDARD FOR CHIMNEYS, FIREPLACES AND VENTING SYSTEMS, available from the American National Standard Institute, 1430 Broadway, New York, N.Y 10018.

BASIC STATIONARY EMERGENCY ELECTRIC SYSTEM

Figure 2.1 shows a schematic diagram of a basic stationary emergency electric system. Both the UTILITY power supply and the STANDBY (GENERATOR) output are connected to an approved transfer switch. The transfer switch is required by electrical code and serves the following functions:

oPermits the LOAD circuits to be connected to only one power supply at atime.

oPrevents electrical backfeed between the generator and the UTILITY power circuits.

Notice that both the STANDBY and the UTILITY power supplies to the transfer switch are protected against overload by a main line circuit breaker.

Figure 2.1 - Basic Stationary Emergency Electric

System

MAIN UNE

CIRCUIT BREAKER

UTIUTY

POWER -- t - /

SUPPLY '- - - --

TRANSFER r---+-~

SWITCH

 

I -

 

 

,

 

 

I

 

. _ J

,

TO LOAD

 

c--f---CIRCUITS

 

,

 

 

'- -

 

STANDBY

---

--

 

GENERATOR --~'

,..;.-'

--1

OUTPUT

,

~

 

MAIN UNE

CIRCUIT BREAKER

13

Image 15
Contents @us Table of Contents Introduction Authorized Service Dealer LocationOperation and Maintenance HOW to Obtain ServiceGeneral Hazards Electrical Hazards Identification Record Data LabelGenerator SET XPL Label Equipment Description Engine Protective DevicesDC Fuses Fuel System SpecificationsFuel System Reduirements and Recommendations Battery InstallationBattery Generator AC LeadConnections Field Wiring Requirements Table SIX-LEAD VAG, THREE-PHASE StatorField Wiring Connections to Buss Bars Generator and Load CompatibilityStarting Aids Engine Coolant Heaters ~KE~Battery Chargers Battery Warmers OptionalOther Published Standards Nfpa StandardsGrounding the Generator Transfer Switch Start Signal ConnectionsEmergency Circuit Isolation Method Total Circuit Isolation MethodPreparation Before START-UP Vented BatteriesPrior to Initial START-UP Operating Unit with Manual Transfer Switch Generator Control and OperationEngine STA8T-UP and TRANSFE8 Transfer Switch Service ScheduleRetransfer and Shutdown Annually or Every 600 Hours whichever comes first Periodic MaintenanceInspect Exhaust System Repair PartsHOW to Order Parts Check FluidsService Maintenance Interval Information Maintenance Tasks Maint Maintenance Maintenance Tasks Task Completed Maint Maintenance Maintenance Tasks Task Completed Maint Maintenance Maintenance Tasks Task Completed Level Maintenance Tasks Task Completed TechniciansSignature Warranty California and Federal Emission Control Warranty Statement Warranty Groupb Groupb 34h ~tJ· ~tJ Grouph Grouph Exploded View EV, CB Mounting KIT MDl Drawing # OJl027 Group a Group a ~ //rY Exploded View EV Altcomprt 80KW DD PME G17 Drawing # OJ1481 Applicable to PART# This page Left Intentionally Blank Group a MAIN, ALT Tower 390 Long 10 390 Alternator Single CIS 390/520 Alternator Dual CIS Load CENTER,125A,SIEMENS 8 BAY\ Group B Blank 171\\ PART# QTY Description QTY Date 7/27//11 Exploded View Drawing # OH5043D Group H Drawing # OH5043D Part Date 2/25/10 FAN Guard R/H Side GROUpe GROUpe 111 GROUpe 180 Basetank CD0095U1N Type GROUpe GROUpe Groupd Groupd ~14 Reducer Hump 18\\ Groupf Groupf Groupf 3 of4 This page left blank intentionally ~-+-+ + + This page is Left Intentionally Blank Groupg Groupg ~ o ===~ ~ o DO-~~ ~ o Nl ---+ + + + 1 Groupg Groupg ~~r= ~~~~WHtjITEt=~= ~S NC RB3 ~~~~~~ 5005~ ~fi Ir~ Drawing # OH9863 ~~BR2DB Drawing # OH9863 Group H This page is Left Intentionally Blank 2ASSEMBY View for Shroud OH78890ST03 only QTY Description RevisionH-6657-C 1of Clamp Hose 7/8 00 Double Wire Date 2/12/10 Washer Date 3/21/10 Drawing No. OH8028 Junction BOX Alternate Dual Battery Configuration Battery Heater Connection Rl.·1 Drawing # OJI047 Page JNI ISWEU.SAS tl3MOd ,,Jdtl3N3EJ