Subaru Robin Power Products 13100T, RGV12100 service manual AC Output Measuring, - 24-

Page 27

(4)CIRCUIT TESTER

Used for measuring resistance, etc.

(5)MEAGER TESTER

Used for measuring generator insulation resistance.

Select one with testing voltage range of 500V.

7-2 AC OUTPUT MEASURING

SWITCH

A

~

TO AC RECEPTACLE

F

V

 

 

~

LOAD

Use a circuit above for measuring AC output. A hot plate or lamp with a power factor of 1.0 may be used as a load. Adjust the load and rpm. and check that the voltage range is as speci- fied in the following table at the rated amperage and rated rpm.

24

Image 27
Contents Generators Contents - 04- - 1- Specifications- 2- Performance Curves- 3- General Description of Generator- 4- Control Panel- 5- Serial NumberConstruction and Function Stator- 6- Diode Unit RGV13100T only RotorBrush / Brush Holder Current Transformer5 A.V.R Automatic Voltage Regulator RGV12100 only ECU Electronic Control Unit- 8- - 9- Idle Control Unit RGV12100 only- 10- OIL Pressure SwitchAC Switch NO-FUSE Breaker Relief ValveAC Receptacle RGV13100T- 11- AC plug Description - 12-Connecting to Domestic Circuit House Wiring Gfci Receptacle- 13- - 14- - 15- - 16- AC Three Phase Receptacle RGV13100T only- 17- Description of Generator OperationPrimary Exciting Action RGV12100 Voltage Regulating Mechanism RGV12100Current Transformer Control RGV13100T Advantages of Current Transformer Control RGV13100T- 18- Do not operate with wet hands or in the rain Safety PrecautionsDo not place inflammable materials near the generator Operate the generator on a level surface- 20- Incandescent lamp, heater, etc. with a power factorRange of Applications Motor driven tools and light electrical appliances- 21- Appliances without any indication as to power consumption- 22- Measuring Procedures Measuring Instruments- 23- - 24- AC Output MeasuringMeasuring Insulation Resistance Stator- 25- - 26- RotorControl Panel Current Transformer RGV13100T- 27- Checking Functional MembersPilot Lamp and Voltmeter AC Receptacles- 28- RGV12100Rotor Assembly Exciting Coil RGV12100 only- 29- - 30- BrushA.V.R Automatic Voltage Regulator- 31- Current Transformer RGV13100T onlyIdle Control Unit RGV12100 only- 32- - 33- Alternator Disassembly and AssemblyPreparation and Precautions Disassembly Procedures Control Panel- 35- Component PartsGenerator assembly Control Box RGV12100 Control Box RGV13100T Fuel Tank - 40- Generator Assembling Procedures Front Cover- 41- - 42- Rear Cover- 43- Check if engine is overheated TroubleshootingNo AC output AC Voltage is too high or too low Check engine speed- 45- Engine dose not run- 46- Wiring Diagram- 47- Lively Blvd. Wood Dale, IL 60191 Phone 630-350-8200 Fax