10. TROUBLESHOOTING

10-1 No AC output

*Checking the exciting coil for resistance. (RGV12100) (Refer to 8-6.) If insulation is NG, replace exciting coil with new one.

* Checking the brush and slip ring of rotor for resistance. (Refer to 8-5 and 8-7.)

If insulation is NG, replace brush and slip ring with new one.

* Check stator for winding resistance between terminals. (Refer to 8-4.)

If stator is faulty, replace with new one.

 

* Checking stator for insulation resistance.

(Refer to 7-3.)

If insulation is NG, replace stator with new one.

 

* Checking the A.V.R . (RGV12100)

(Refer to 8-8.)

If insulation is NG, replace A.V.R with new one.

 

* Checking the diode unit and C.T . (RGV13100T)

(Refer to 8-9 and 8-12.)

If insulation is NG, replace diode unit and C.T with new one.

10-2 AC Voltage is too high or too low

*Check engine speed.

Nominal engine speed at no load ; 3,700 to 3,750 rpm

If engine speed is too high or too low, adjust to the rated rpm.

* Check stator for winding resistance and insulation.

(Refer to 8-4 and 7-3.)

* Check rotor for resistance and insulation.

(Refer to 8-5 and 7-3.)

* Checking the idle control unit. (RGV12100)

(Refer to 8-11.)

If insulation is NG, replace idle control unit with new one.

10-3 AC voltage is nominal at no-load, but load cannot be applied.

*Check engine speed.

If engine speed is low, adjust to the rated rpm.

*Check total wattage of appliances connected to generator.

If the generator is overloaded, reduce the load to the rated output of generator.

*Check appliance for trouble.

If the appliance is faulty, replace it.

*Check if engine is overheated.

If generator cooling air inlet and/or outlet is clogged with dirt, grass, chaff or other debris,

remove it.

 

* Check insulation of generator.

(Refer to 7-3.)

44

Image 47
Contents Generators Contents - 04- - 1- Specifications- 2- Performance Curves- 3- General Description of Generator- 4- Control Panel- 5- Serial Number- 6- Construction and FunctionStator Diode Unit RGV13100T only RotorBrush / Brush Holder Current Transformer- 8- 5 A.V.R Automatic Voltage Regulator RGV12100 onlyECU Electronic Control Unit - 9- Idle Control Unit RGV12100 only- 10- OIL Pressure SwitchAC Switch NO-FUSE Breaker Relief Valve- 11- AC ReceptacleRGV13100T AC plug Description - 12-- 13- Connecting to Domestic Circuit House WiringGfci Receptacle - 14- - 15- - 16- AC Three Phase Receptacle RGV13100T only- 17- Description of Generator OperationPrimary Exciting Action RGV12100 Voltage Regulating Mechanism RGV12100- 18- Current Transformer Control RGV13100TAdvantages of Current Transformer Control RGV13100T Do not operate with wet hands or in the rain Safety PrecautionsDo not place inflammable materials near the generator Operate the generator on a level surface- 20- Incandescent lamp, heater, etc. with a power factorRange of Applications Motor driven tools and light electrical appliances- 21- Appliances without any indication as to power consumption- 22- - 23- Measuring ProceduresMeasuring Instruments - 24- AC Output Measuring- 25- Measuring Insulation ResistanceStator - 26- RotorControl Panel Current Transformer RGV13100T- 27- Checking Functional MembersPilot Lamp and Voltmeter AC Receptacles- 28- RGV12100- 29- Rotor AssemblyExciting Coil RGV12100 only - 30- BrushA.V.R Automatic Voltage Regulator- 31- Current Transformer RGV13100T only- 32- Idle Control UnitRGV12100 only - 33- Alternator Disassembly and AssemblyPreparation and Precautions Disassembly Procedures Control Panel- 35- Component PartsGenerator assembly Control Box RGV12100 Control Box RGV13100T Fuel Tank - 40- Generator Assembling Procedures Front Cover- 41- - 42- Rear Cover- 43- Check if engine is overheated TroubleshootingNo AC output AC Voltage is too high or too low Check engine speed- 45- Engine dose not run- 46- Wiring Diagram- 47- Lively Blvd. Wood Dale, IL 60191 Phone 630-350-8200 Fax