8-3 AC SWITCH (NO-FUSE BREAKER)
Check continuity between each of 2 terminals at the back side of AC switch
Normally, there is continuity between each of the 2 terminals when the breaker is ON, while no continuity when the breaker is OFF.
RGV12100
8-4 STATOR
RGV13100T
Disengage connectors on the wires from stator and check the resistance between wires with a circuit tester, referring to the following specification table.
NOTE : If the circuit tester is not sufficiently accu- rate, it may not show the values given and may give erroneous readings.
Erroneous readings will also occur when there is a wide variation of resistance among coil windings or when measure- ment is performed at ambient tempera- tures different from 20℃
(68 °F).
|
|
|
| Stator coil |
|
| |
Model | Hz/Voltage |
|
|
|
|
| |
White- | |||||||
|
| ||||||
|
| Light green | |||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
RGV12100 | 60/120/240 | 0.11Ω | 0.11Ω | 0.37Ω | |||
|
|
|
|
|
|
| |
RGV13100T | 60/120/208 | 0.23Ω | 0.23Ω | 0.23Ω | |||
|
|
|
|
|
|
|