Subaru Robin Power Products RGV12100, 13100T Measuring Insulation Resistance, Stator, - 25-

Page 28

Model

 

Rated voltage

 

 

 

 

 

 

 

 

120 V

208 V

240 V

 

 

 

 

 

 

 

 

 

 

 

RGV12100

112V-128V

--------------

224V-256V

range

 

 

 

 

 

 

 

 

 

 

Voltage

 

RGV13100T

--------------

218V-249V

--------------

 

 

 

 

 

 

 

 

 

 

 

 

7-3 MEASURING INSULATION RESISTANCE

Use a megger tester to check the insulation resistance. Connect a megger tester to one of receptacle output terminals and the ground terminal, then measure the insulation resis- tance.

An insulation resistance of 1MΩ or more is normal.

If it is less than 1MΩ, disassemble the gen- erator and measure the insulation resistance of the stator, rotor and control panel individu- ally.

STATOR

(1)Measure the insulation resistance between BLUE (RGV12100),

GREEN (RGV13100T) lead and the core.

(2)Measure the insulation resistance between WHITE lead and the core.

(3)Measure the insulation resistance between BLACK lead and the core.

(4)Measure the insulation resistance between RED lead and the core.

25

Image 28
Contents Generators Contents - 04- Specifications - 1-Performance Curves - 2-General Description of Generator - 3-Control Panel - 4-Serial Number - 5-Stator Construction and Function- 6- Rotor Brush / Brush HolderCurrent Transformer Diode Unit RGV13100T onlyECU Electronic Control Unit 5 A.V.R Automatic Voltage Regulator RGV12100 only- 8- Idle Control Unit RGV12100 only - 9-OIL Pressure Switch AC Switch NO-FUSE BreakerRelief Valve - 10-RGV13100T AC Receptacle- 11- - 12- AC plug DescriptionGfci Receptacle Connecting to Domestic Circuit House Wiring- 13- - 14- - 15- AC Three Phase Receptacle RGV13100T only - 16-Description of Generator Operation Primary Exciting Action RGV12100Voltage Regulating Mechanism RGV12100 - 17-Advantages of Current Transformer Control RGV13100T Current Transformer Control RGV13100T- 18- Safety Precautions Do not place inflammable materials near the generatorOperate the generator on a level surface Do not operate with wet hands or in the rainIncandescent lamp, heater, etc. with a power factor Range of ApplicationsMotor driven tools and light electrical appliances - 20-Appliances without any indication as to power consumption - 21-- 22- Measuring Instruments Measuring Procedures- 23- AC Output Measuring - 24-Stator Measuring Insulation Resistance- 25- Rotor Control PanelCurrent Transformer RGV13100T - 26-Checking Functional Members Pilot Lamp and VoltmeterAC Receptacles - 27-RGV12100 - 28-Exciting Coil RGV12100 only Rotor Assembly- 29- Brush A.V.RAutomatic Voltage Regulator - 30-Current Transformer RGV13100T only - 31-RGV12100 only Idle Control Unit- 32- - 33- Disassembly and Assembly Preparation and PrecautionsDisassembly Procedures Control Panel AlternatorComponent Parts - 35-Generator assembly Control Box RGV12100 Control Box RGV13100T Fuel Tank Generator Assembling Procedures Front Cover - 40-- 41- Rear Cover - 42-- 43- Troubleshooting No AC outputAC Voltage is too high or too low Check engine speed Check if engine is overheatedEngine dose not run - 45-Wiring Diagram - 46-- 47- Lively Blvd. Wood Dale, IL 60191 Phone 630-350-8200 Fax