Quick Start
Interface Connectors
External Alarm Connector
The external alarm
and two output pairs (pins 1 and 2 - major alarms; pins 3 and 4 - minor A
alarms).
L
A
R
M
6
5
4
3
2 1
The pinouts are as follows:
Pin # | Description | Explanation | |
|
|
| |
1 | Major Alarm + | The major alarm output is available for power supply or | |
2 | Major Alarm - | major alarm failure alerting. The maximum voltage across | |
the contacts is 350 V, and the maximum current is 150 mA. | |||
|
| ||
|
| This alarm is closed when power is off. | |
|
|
| |
3 | Minor Alarm + | The minor alarm output is available for power supply or | |
4 | Minor Alarm - | minor alarm failure alerting. The maximum voltage across | |
the contacts is 350 V, and the maximum current is 150 mA. | |||
|
| ||
|
| This alarm remains open when power is off. | |
|
|
| |
5 | Alarm In + | The alarm inputs provide 5 VDC across the two contacts, | |
6 | Alarm In - | and generate an alarm when a short circuit is detected | |
between the contacts. | |||
|
| ||
|
| The alarm generated is a minor severity alarm. | |
|
|
|
Compact T1 - Release 6.1 | 15 |