TDK 750W HALF RACK technical manual Connecting single loads, local sensing default

Page 31

3.9.7Connecting single loads, local sensing (default).

Fig.3-10 shows recommended load and sensing connections for a single load. The local sense lines shown are default connections at the rear panel J2 sense connector. Local sensing is suit- able for applications where load regulation is less critical.

+V

+

 

Load

Power -V

Supply

-Rem.sense

Load lines, twisted

-Local sense

pair, shortest length

+Local sense

possible.

+Rem.sense

 

Fig.3-10: Single load connection, local sensing

3.9.8Connecting single loads, remote sensing

Fig.3-11 shows recommended remote sensing connection for single loads. Remote sensing is used when, in Constant Voltage mode, the load regulation is important at the load terminals. Use twisted or shielded wires to minimize noise pick-up. If shielded wires are used, the shield should be connected to the ground at one point, either at the power supply chassis or the load ground. The optimal point for the shield ground should be determined by experimentation.

+V

Power -VSupply

-Rem.sense -Local sense +Local sense +Rem.sense

Load lines. Twisted pair shortest length possible.

+

Load

Sense lines. Twisted pair or shielded.

Fig.3-11: Remote sensing, single load

3.9.9Connecting multiple loads, radial distribution method

Fig.3-12 shows multiple loads connected to one supply. Each load should be connected to the power supply’s output terminals using separate airs of wires. It is recommended that each pair of wires will be as short as possible and twisted or shielded to minimize noise pick-up and radiation. The sense wires should be connected to the power supply output terminals or to the load with the most critical load regulation requirement.

23

83-507-5002 Rev. B

Image 31
Contents Genesystm 750W Half Rack Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and CONNECTORS………... ……… ……… Isolated Analog Progamming Option ……………………………..…… Warranty Safety Instructions Safety Instructions SICHERHEITS-INSTALLATIONS Anweisungen Anderungen and Bauteileersatz Sicherheits-und WarnsymboleUmweltbedingungen General Description Features and optionsGeneral Information IntroductionParallel operation Multiple output power systemControl via the serial communication port Analog voltage programming and monitoringAccessories Chapter SpecificationsFront Panel Supplemental Characteristics Genesystm Genh 750W Power Supplies Outline Drawings Initial Inspections InstallationGeneral Preparation for USERack Mounting Single unit installationGENH/RM Rack Mounting outline drawings AC Input Power ConnectionLOCATION, Mounting and Cooling AC Source RequirementsGeneral TURN-ON Checkout ProcedureAC Input Connector AC Input CordUVL Check Constant Voltage CheckConstant Current Check OVP CheckConnecting the Load AWG Wire termination 6V to 60V Models Noise and Impedance Effects Inductive loads Making the load connectionsBus-bars shield mounting 80V to 600V Models 83-507-5002 Rev. B Connecting single loads, remote sensing Connecting single loads, local sensing defaultConnecting multiple loads, radial distribution method Grounding outputs Multiple load connection with distribution terminalsLocal sensing Sense wiringOutput Terminal Grounding Local and Remote SensingRemote sensing 10.4 J2 sense connector technical informationFront Panel Controls and Indicators Front and Rear Panel Controls and ConnectorsVoltage Auxiliary Function Rear panel connections and controls Number Description Rear Panel Connections and Controls1 SW1 position function Rear Panel SW1 Setup SwitchResetting the SW1 switch Rear Panel J1 Programming and Monitoring ConnectorMaking J1 connections 83-507-5002 Rev. B Local SignalEnain IfcomStandard Operation Constant Voltage ModeConstant Current Mode Local OperationAutomatic Crossover Setting the OVP levelResetting the OVP circuit Over Voltage Protection OVPOutput ON/OFF Control Output SHUT-OFF SO Control VIA Rear Panel J1 ConnectorUnder Voltage Limit UVL Foldback ProtectionCV/CC Signal ENABLE/DISABLE Control VIA Rear Panel J1 ConnectorSAFE-START and AUTO-RESTART Modes Psok SignalOver Temperature Protecton OTP Last Setting MemorySeries connection for increased output voltage Series OperationSeries connection for positive/negative output voltages Series connection for positive and negative output voltageBasic parallel operation Setting up the Master unitSetting up the Slave units Parallel OperationSetting the units as Master or Slave Setting Over Voltage protectionSetting Foldback protection Advanced parallel configurationAST OFF OUT OFF Master and Slave units default operationTo release units from Slave mode Current display accuracyFront Panel Locking DAISY-CHAIN ConnectionLocked front panel Unlocked front panelLOCAL/REMOTE Analog Indication Remote Analog ProgrammingRemote voltage programming connection DownRemote resistive programming Resisitive Programming of Output Voltage and Current LimitRemote Monitoring of Output Voltage and Current Configuration RS232 & RS485 Remote Control6 RS232/RS485 port in Local mode Rear Panel RS232/RS485 ConnectorFront panel in Remote mode MD Mode SRQ Retransmission MD Mode DescriptionMD Mode enable Serial communication mode MD Mode SRQSingle power supply Connecting Power Supplies to RS232 or RS485 BUSCommunication Interface Protocol Command SET Description Error MessagesID Control Commands Initialization Control CommandsOutput Control Commands OUT? DVC?Filter FILTER?Global Output Commands Enable SRQ retransmission MD Mode Option Required Single Byte CommandsEnable MD Mode MD Mode Option Required Disable SRQ retransmission MD Mode Option RequiredPrint Power On Time Addressed commands with response Read registersRetransmit Last Message Addressed commands without response Acknowledge SRQ Test if MD Mode is InstalledRe-enable SRQ with out reading/clearing the Seve Register 110x Status Control Commands STATUS, Error and SRQ RegistersTXD Conditional RegistersBIT Service Request Enable and Event RegistersFault Event Register Fault Enable RegisterStatus Event Register Status Enable RegisterSerial Communication Test SET-UP Power supply set-upCommunication Test PPM/C SpecificationsIsolated Analog Programming Option 1 0-5V/0-10V Option PN IS510Isolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance OUP Fuse Rating