TDK 750W HALF RACK Parallel Operation, Basic parallel operation, Setting up the Master unit

Page 49

Remote programming in series operation for positive and negative output voltage

1.

Programming by external voltage:

The analog programming circuits of this power

 

 

supply are referenced to the negative output po-

 

 

tential. Therefore, the circuits used to control

 

 

each series connected unit must be separated

 

 

and floated from each other.

2.

Using the SO function and PS_OK signal:

The Shut-Off and PS_OK circuits are referenced

 

 

to the isolated interface common, IF_COM (J1-

 

 

2,3). The IF_COM terminals of the units can be

 

 

connected to obtain a single control circuit for the

 

 

power supplies connected in series.

3.

Programming by external resistor:

Programming by external resistor is possible. Re-

 

 

fer to section 6.5 for details.

4.

Programming via the Serial

The communication port is referenced to the

 

Communication port (RS232/RS485):

IF_COM which is isolated from the power supply

 

 

output potential. Therefore power supplies con-

 

 

nected in series can be chained using the Re-

 

 

mote-In and Remote-Out connectors. Refer to

 

 

chapter 7 for details.

5.15 PARALLEL OPERATION

Up to four units of the same VOLTAGE and CURRENT rating can be connected in parallel to provide up to four times the Output Current capability. One of the units operates as a Master and the remaining units are Slaves. The Slave units are analog programmed by the Master unit. In remote digital operation, only the Master unit can be programmed by the computer, while the Slave units may be connected to the computer for voltage, current and status readback only. Fol- low the following procedure to configure multiple supplies for parallel operation. Refer to Sec. 5.15.1 and to Sec. 5.15.2 for detailed explanation.

5.15.1 Basic parallel operation

In this method, setting the units as Master and Slaves is made by the rear panel J1 connections and the setup switch SW1. Each unit displays its own output current and voltage. To program the load current, the Master unit should be programmed to the total load current divided by the num- ber of units in the system. Refer to the following procedure to configure multiple supplies for basic parallel operation.

1.Setting up the Master unit

Set the Master unit Output Voltage to the desired voltage. Program the Output Current to the desired load current divided by the number of parallel units. During operation, the Master unit operates in CV mode, regulating the load voltage at the programmed Output Voltage. Connect the sensing circuit to local or remote sensing as shown in Fig.5-4 or fig.5-5.

2.Setting up the Slave units

-1. The Output Voltage of the Slave units should be programmed 2-5% higher than the Out- put Voltage of the Master unit to prevent interference with the Master unit’s control. The Out- put Current setting of each unit should be programmed to the desired load current divided by the number of parallel units.

-2. Set the rear panel setup switch SW1 position 2 to the up position.

-3. Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).

-4. Connect J1 terminal 10(IPGM) of the slave unit to J1 terminal 25(P) of the master unit.

41

83-507-5002 Rev. B

Image 49
Contents Genesystm 750W Half Rack Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and CONNECTORS………... ……… ……… Isolated Analog Progamming Option ……………………………..…… Warranty Safety Instructions Safety Instructions SICHERHEITS-INSTALLATIONS Anweisungen Anderungen and Bauteileersatz Sicherheits-und WarnsymboleUmweltbedingungen General Information Features and optionsIntroduction General DescriptionControl via the serial communication port Multiple output power systemAnalog voltage programming and monitoring Parallel operationAccessories Chapter SpecificationsFront Panel Supplemental Characteristics Genesystm Genh 750W Power Supplies Outline Drawings General InstallationPreparation for USE Initial InspectionsRack Mounting Single unit installationLOCATION, Mounting and Cooling AC Input Power ConnectionAC Source Requirements GENH/RM Rack Mounting outline drawingsAC Input Connector TURN-ON Checkout ProcedureAC Input Cord GeneralConstant Current Check Constant Voltage CheckOVP Check UVL CheckConnecting the Load AWG Wire terminationInductive loads Noise and Impedance EffectsMaking the load connections 6V to 60V ModelsBus-bars shield mounting 80V to 600V Models 83-507-5002 Rev. B Connecting single loads, remote sensing Connecting single loads, local sensing defaultConnecting multiple loads, radial distribution method Grounding outputs Multiple load connection with distribution terminalsOutput Terminal Grounding Sense wiringLocal and Remote Sensing Local sensingRemote sensing 10.4 J2 sense connector technical informationFront Panel Controls and Indicators Front and Rear Panel Controls and ConnectorsVoltage Auxiliary Function Rear panel connections and controls Number Description Rear Panel Connections and Controls1 SW1 position function Rear Panel SW1 Setup SwitchResetting the SW1 switch Rear Panel J1 Programming and Monitoring ConnectorMaking J1 connections 83-507-5002 Rev. B Enain SignalIfcom LocalConstant Current Mode Constant Voltage ModeLocal Operation Standard OperationResetting the OVP circuit Setting the OVP levelOver Voltage Protection OVP Automatic CrossoverUnder Voltage Limit UVL Output SHUT-OFF SO Control VIA Rear Panel J1 ConnectorFoldback Protection Output ON/OFF ControlCV/CC Signal ENABLE/DISABLE Control VIA Rear Panel J1 ConnectorOver Temperature Protecton OTP Psok SignalLast Setting Memory SAFE-START and AUTO-RESTART ModesSeries connection for increased output voltage Series OperationSeries connection for positive/negative output voltages Series connection for positive and negative output voltageSetting up the Slave units Setting up the Master unitParallel Operation Basic parallel operationSetting Foldback protection Setting Over Voltage protectionAdvanced parallel configuration Setting the units as Master or SlaveTo release units from Slave mode Master and Slave units default operationCurrent display accuracy AST OFF OUT OFFFront Panel Locking DAISY-CHAIN ConnectionLocked front panel Unlocked front panelLOCAL/REMOTE Analog Indication Remote Analog ProgrammingRemote voltage programming connection DownRemote resistive programming Resisitive Programming of Output Voltage and Current LimitRemote Monitoring of Output Voltage and Current Configuration RS232 & RS485 Remote Control6 RS232/RS485 port in Local mode Rear Panel RS232/RS485 ConnectorFront panel in Remote mode MD Mode enable Serial communication mode MD Mode DescriptionMD Mode SRQ MD Mode SRQ RetransmissionSingle power supply Connecting Power Supplies to RS232 or RS485 BUSCommunication Interface Protocol Command SET Description Error MessagesID Control Commands Initialization Control CommandsOutput Control Commands Filter DVC?FILTER? OUT?Global Output Commands Enable MD Mode MD Mode Option Required Single Byte CommandsDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredPrint Power On Time Addressed commands with response Read registersRetransmit Last Message Addressed commands without response Acknowledge SRQ Test if MD Mode is InstalledRe-enable SRQ with out reading/clearing the Seve Register 110x Status Control Commands STATUS, Error and SRQ RegistersTXD Conditional RegistersBIT Service Request Enable and Event RegistersFault Event Register Fault Enable RegisterStatus Event Register Status Enable RegisterSerial Communication Test SET-UP Power supply set-upCommunication Test Isolated Analog Programming Option Specifications1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance OUP Fuse Rating