TDK 750W HALF RACK technical manual DAISY-CHAIN Connection, Front Panel Locking

Page 52

 

 

 

 

 

 

 

 

 

 

+S

 

 

 

 

 

 

 

 

 

 

-S

 

 

 

 

 

 

 

 

 

 

Twisted

 

 

 

 

 

 

 

 

 

 

pair

To J1-10

 

 

 

 

-S

+S

 

 

 

 

 

 

 

 

 

+V

As short as possible

SLAVE#2

 

 

 

 

 

 

 

 

MASTER

 

 

 

+S

POWER SUPPLY

POWER SUPPLY

 

 

-V

Twisted

 

 

 

pair

 

 

 

 

J1-25

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

IPGM

 

 

 

 

 

J1-8 J1-12 J1

-10

 

 

 

 

 

SLAVE#1

 

 

+V

 

 

 

 

 

 

 

POWER SUPPLY

 

 

-V

-S

 

 

 

 

 

 

 

 

 

 

 

 

-S -LS

+LS +S

 

 

 

 

 

 

 

 

 

 

 

 

LOAD

Fig.5-5: Parallel operation with Remote sensing

CAUTION Make sure that the connection between –V terminals is reliable to avoid disconnection during operation. Disconnection may cause damage to the power supply.

NOTE

With local sensing it is important to minimize the wire length and resistance. Also the positive and negative wire resistance should be close as possible to each other to achieve current balance be- tween power supplies

5.16 DAISY-CHAIN CONNECTION

It is possible to configure a multiple power supply system to shut down all the units when a fault condition occurs in one of the units. When the fault is removed, the system recovers according to its setting to Safe-start or Auto-restart mode.

Setup switch SW1, position 5 should be set to its DOWN position to enable the Daisy-chain op- eration. Other SW1 positions can be set according to the application requirements.

If a fault occurs in one of the units, its PS_OK signal will be set to a low level and the display will indicate the fault. The other units will shut off and their display will indicate “SO”. When the fault condition is removed, the units will recover to their last setting according to their Safe-start or Auto-restart setting.

Fig.5-6 shows connection of three units, however the same connection method applies to sys- tems with a larger number of units.

POWER SUPPLY

#1

J1-2,3 J1-16 J1-15

POWER SUPPLY

#2

J1-2,3 J1-16 J1-15

POWER SUPPLY

#3

J1-2,3 J1-16 J1-15

IF_COM

PS_OK

SO

IF_COM PS_OK SO

IF_COM

PS_OK

SO

 

 

 

Fig.5-6: Daisy-chain connection

 

 

5.17 FRONT PANEL LOCKING

The front panel controls can be locked to protect from accidental power supply parameter change. Press and hold the PREV button to toggle between “Locked front panel’ and “Unlocked front panel”. The display will cycle between “LFP” and “UFP”. Releasing the PREV button while one of the modes is displayed, selects that mode.

44

83-507-5002 Rev. B

Image 52
Contents Genesystm 750W Half Rack Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and CONNECTORS………... ……… ……… Isolated Analog Progamming Option ……………………………..…… Warranty Safety Instructions Safety Instructions SICHERHEITS-INSTALLATIONS Anweisungen Anderungen and Bauteileersatz Sicherheits-und WarnsymboleUmweltbedingungen Features and options General InformationIntroduction General DescriptionMultiple output power system Control via the serial communication portAnalog voltage programming and monitoring Parallel operationAccessories Specifications ChapterFront Panel Supplemental Characteristics Genesystm Genh 750W Power Supplies Outline Drawings Installation GeneralPreparation for USE Initial InspectionsSingle unit installation Rack MountingAC Input Power Connection LOCATION, Mounting and CoolingAC Source Requirements GENH/RM Rack Mounting outline drawingsTURN-ON Checkout Procedure AC Input ConnectorAC Input Cord GeneralConstant Voltage Check Constant Current CheckOVP Check UVL CheckConnecting the Load Wire termination AWGNoise and Impedance Effects Inductive loadsMaking the load connections 6V to 60V ModelsBus-bars shield mounting 80V to 600V Models 83-507-5002 Rev. B Connecting single loads, remote sensing Connecting single loads, local sensing defaultConnecting multiple loads, radial distribution method Multiple load connection with distribution terminals Grounding outputsSense wiring Output Terminal GroundingLocal and Remote Sensing Local sensing10.4 J2 sense connector technical information Remote sensingFront Panel Controls and Indicators Front and Rear Panel Controls and ConnectorsVoltage Auxiliary Function Rear Panel Connections and Controls Rear panel connections and controls Number DescriptionRear Panel SW1 Setup Switch 1 SW1 position functionResetting the SW1 switch Rear Panel J1 Programming and Monitoring ConnectorMaking J1 connections 83-507-5002 Rev. B Signal EnainIfcom LocalConstant Voltage Mode Constant Current ModeLocal Operation Standard OperationSetting the OVP level Resetting the OVP circuitOver Voltage Protection OVP Automatic CrossoverOutput SHUT-OFF SO Control VIA Rear Panel J1 Connector Under Voltage Limit UVLFoldback Protection Output ON/OFF ControlENABLE/DISABLE Control VIA Rear Panel J1 Connector CV/CC SignalPsok Signal Over Temperature Protecton OTPLast Setting Memory SAFE-START and AUTO-RESTART ModesSeries Operation Series connection for increased output voltageSeries connection for positive and negative output voltage Series connection for positive/negative output voltagesSetting up the Master unit Setting up the Slave unitsParallel Operation Basic parallel operationSetting Over Voltage protection Setting Foldback protectionAdvanced parallel configuration Setting the units as Master or SlaveMaster and Slave units default operation To release units from Slave modeCurrent display accuracy AST OFF OUT OFFDAISY-CHAIN Connection Front Panel LockingUnlocked front panel Locked front panelRemote Analog Programming LOCAL/REMOTE Analog IndicationDown Remote voltage programming connectionResisitive Programming of Output Voltage and Current Limit Remote resistive programmingRemote Monitoring of Output Voltage and Current RS232 & RS485 Remote Control Configuration6 RS232/RS485 port in Local mode Rear Panel RS232/RS485 ConnectorFront panel in Remote mode MD Mode Description MD Mode enable Serial communication modeMD Mode SRQ MD Mode SRQ RetransmissionConnecting Power Supplies to RS232 or RS485 BUS Single power supplyCommunication Interface Protocol Error Messages Command SET DescriptionID Control Commands Initialization Control CommandsOutput Control Commands DVC? FilterFILTER? OUT?Global Output Commands Single Byte Commands Enable MD Mode MD Mode Option RequiredDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredPrint Power On Time Addressed commands with response Read registersRetransmit Last Message Addressed commands without response Acknowledge SRQ Test if MD Mode is InstalledRe-enable SRQ with out reading/clearing the Seve Register 110x STATUS, Error and SRQ Registers Status Control CommandsConditional Registers TXDService Request Enable and Event Registers BITFault Enable Register Fault Event RegisterStatus Enable Register Status Event RegisterSerial Communication Test SET-UP Power supply set-upCommunication Test Specifications Isolated Analog Programming Option1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance OUP Fuse Rating