Liebert GXT2-6000 RT208 user manual Install the Main Cabinet, Installation and Configuration

Page 16

Installation and Configuration

6.0INSTALLATION AND CONFIGURATION

This section includes instructions on how to install, configure and perform initial electrical checks of your UPS installation.

DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 7.0 - Initial Startup and Electrical Checks.

Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative.

! CAUTION

The UPS is heavy (see 14.0 - Specifications). Take proper precautions when lifting or moving it.

Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, cor- rosives and other conductive contaminants. Maintain a minimum clearance of 4" (100mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).

NOTE

UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.

6.1Install the Main Cabinet

The GXT2-6000RT208 may be installed either as a tower unit or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instruc- tions in either 6.1.1 - Tower UPS Installation or 6.1.2 - Installing the Adjustable Rack-MountKit—Sold Separately.

6.1.1Tower UPS Installation

When using the GXT2-6000RT208 in a tower configuration, use the included support base (shown below, left) to stabilize the UPS.

If any external battery cabinets are added, they will include spacers to accommodate the additional cabinets (shown below, right).

Figure 2 Support base and spacers

End Bases

2U Spacer

Spacers added to support

4U Support Basebase to accommodate additional battery cabinets

Attach Bezels to Top

When used as a tower, the GXT2-6000RT208 requires bezels attached to the top. To connect the bezels:

1.Position the UPS so that the battery compartment is on the bottom.

2.Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of the UPS.

10

Image 16
Contents Power Availability GXT2-6000RT208Page Table of Contents Configuration Program Controls and IndicatorsMaintenance TroubleshootingSpecifications Modes of OperationFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDC to DC Converter BatteryDynamic Bypass Main Frame and Electronics Internal Battery PackMajor Components Removable Power Distribution Box PD-001Top bezels Tower use Battery cover grille GEC connector Mounting hardware Rack mount HandlesConfiguration Disk Ferrite Beads WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Attach Bezels to TopQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyReturn flanges Retaining Latches Front Innermembers members M4 nuts Rack Depth M4 nutsExternal Battery Cabinet Installation Connect Input/Output Power Replacing a power distribution boxDistribution Box Electrical Connections Slide cover over connec- tors Loosen screws to move cover4 PD-001 Power Distribution Box PD-HDWR and PD-HDWR-MBS Terminal Block ConnectionsElectrical requirements-PD-HDWR and PD-HDWR-MBS Electrical requirements-PD-001Install the Internal Battery Pack Install the Grounding Electrode ConductorGround Electrode System or Protective Earth System Initial Startup and Electrical Checks Initial Startup and Electrical Checks Configuration Program GXT2-6000RT208 Configuration Program FeaturesWhat You Will Need Configuration Program-Installation Establishing Communication Link with the UPS Configuration Program-Operation Read/Confirm UPS Configuration SettingsChanging UPS Settings Exit Without Changing UPS SettingsUPS Tab Output VoltageAuto Restart N Reverse Detection 120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier GXT 2U Models Battery Tab Low Battery Time WarningAuto Battery Test Time Battery Cabinets NumberAbout Tab ON/Alarm Silence/Battery Test Button Controls and IndicatorsOFF/Bypass Button Horizontal overlay for rack mountingBattery Level Indicators 5 Green Fault Indicator RedBypass Indicator Amber UPS on Indicator GreenNormal Mode Operation Battery Mode OperationBattery Recharge Operation Modes of OperationCommunications Interface Port Communications11.1.1 DB-9 Interface Port Communications Snmp Web Card Snmp AdapterPin 4 Remote Shutdown on Battery UPS Intelligent CommunicationsKey to Repo switch connections 1 VDC Sense Ground Remote Emergency Power OffRepo Connection Battery Replacement MaintenanceInternal Battery Replacement Procedures Battery Cover Captive Screws Front BezelsUPS Replacement Connector Connector cover Cover Electrical connectorsFault indicators TroubleshootingIndicator status Diagnosis/Audible alarm Troubleshooting guide Problem Cause Solution Alarm conditionsCondition Alarm Only phase angles of 120, 180 or 240 degrees ±10 Battery/External Cabinets Load% Minutes Battery run times6000VA Run Time Auto-Learning Battery Run Times Specifications UPS specificationsBattery specifications Power distribution box specificationsSee Battery run times Model NumberExternal battery cabinet specifications Product Warranty RegistrationUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Specifications Page Technical Support/Service Company Behind the ProductsLocations Asia 23F, Allied Kajima Bldg