Liebert GXT2-6000 RT208 user manual PD-HDWR and PD-HDWR-MBS Terminal Block Connections

Page 21

Installation and Configuration

6.3.3PD-HDWR and PD-HDWR-MBS Terminal Block Connections

Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same conduit.

Table 1 Electrical requirements—PD-HDWR and PD-HDWR-MBS

Input Current

Recommended (Max.)

Recommended Wire

Maximum Wire

Terminal

Rating

External Overcurrent

(including ground wire)

Accepted by

Tightening

 

Protection

(75°C copper wire)

Terminal Block

Torque

24A

30A

10 AWG

8 AWG

20 in-lb

 

 

 

 

 

The standard PD-HDWR comes installed on the UPS. The PD-HDWR-MBS with manual bypass switch is optionally available. Both have the same hardwire terminal connections.

N

L2

L1

N

L2

L1

 

OUTPUT

 

INPUT

30A Max. Branch

 

 

Overcurrent Protection

 

 

 

 

8-10 AWG - USE COPPER WIRE ONLY - 20 in-lb - Strip 7mm

 

 

 

N

 

 

 

 

 

L2

 

 

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

 

 

 

208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or 240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output to Load - See Note 1

N

L2

L1

 

120

208

0

120

 

 

 

 

or 240

Input to UPS - See Note 2

NOTE

1.The installer must provide circuit breaker protection according to local codes. The utility disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain service space around the UPS or use flexible conduit.

2.The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local codes. Output circuits must not share a common conduit with any other wiring.

For best performance, distribute all L-N loads evenly between L1 and L2.

6.3.4 PD-001 Power Distribution Box

An optional PD-001 is available to provide the conve- nience of an L14-30P input plug and output receptacles. To use this box, remove the original PD-HDWR hardwire box and install the PD-001.

Table 2

Electrical requirements—PD-001

 

 

 

 

 

 

Recommended (Max.)

 

Input Current

External Overcurrent

Required Utility

Rating

 

Protection

Receptacle

24A

 

30A

NEMA L14-30R

 

 

 

 

Output

Receptacles

Manual

Bypass

Switch

15

Image 21
Contents GXT2-6000RT208 Power AvailabilityPage Table of Contents Controls and Indicators Configuration ProgramTroubleshooting MaintenanceSpecifications Modes of OperationFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionBattery DC to DC ConverterDynamic Bypass Internal Battery Pack Main Frame and ElectronicsMajor Components PD-001 Removable Power Distribution BoxGEC connector Mounting hardware Rack mount Handles Top bezels Tower use Battery cover grilleConfiguration Disk Ferrite Beads WHAT’S IncludedInstallation and Configuration Install the Main CabinetTower UPS Installation Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityReturn flanges Retaining Latches Front Innermembers members Rack Depth M4 nuts M4 nutsExternal Battery Cabinet Installation Replacing a power distribution box Connect Input/Output PowerDistribution Box Electrical Connections Slide cover over connec- tors Loosen screws to move coverPD-HDWR and PD-HDWR-MBS Terminal Block Connections 4 PD-001 Power Distribution BoxElectrical requirements-PD-HDWR and PD-HDWR-MBS Electrical requirements-PD-001Install the Grounding Electrode Conductor Install the Internal Battery PackGround Electrode System or Protective Earth System Initial Startup and Electrical Checks Initial Startup and Electrical Checks GXT2-6000RT208 Configuration Program Features Configuration ProgramWhat You Will Need Configuration Program-Installation Establishing Communication Link with the UPS Read/Confirm UPS Configuration Settings Configuration Program-OperationChanging UPS Settings Exit Without Changing UPS SettingsOutput Voltage UPS TabAuto Restart N Reverse Detection 120V UPS Models OnlyFrequency Selection Options TabOptions Tab Used With Earlier GXT 2U Models Low Battery Time Warning Battery TabAuto Battery Test Time Battery Cabinets NumberAbout Tab Controls and Indicators ON/Alarm Silence/Battery Test ButtonOFF/Bypass Button Horizontal overlay for rack mountingFault Indicator Red Battery Level Indicators 5 GreenBypass Indicator Amber UPS on Indicator GreenBattery Mode Operation Normal Mode OperationBattery Recharge Operation Modes of OperationCommunications Communications Interface Port11.1.1 DB-9 Interface Port Communications Snmp Web Card Snmp AdapterUPS Intelligent Communications Pin 4 Remote Shutdown on BatteryRemote Emergency Power Off Key to Repo switch connections 1 VDC Sense GroundRepo Connection Maintenance Battery ReplacementInternal Battery Replacement Procedures Battery Cover Captive Screws Front BezelsConnector Connector cover Cover Electrical connectors UPS ReplacementTroubleshooting Fault indicatorsIndicator status Diagnosis/Audible alarm Alarm conditions Troubleshooting guide Problem Cause SolutionCondition Alarm Only phase angles of 120, 180 or 240 degrees ±10 Battery run times Battery/External Cabinets Load% Minutes6000VA Run Time Auto-Learning Battery Run Times UPS specifications SpecificationsPower distribution box specifications Battery specificationsSee Battery run times Model NumberProduct Warranty Registration External battery cabinet specificationsUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Specifications Page Company Behind the Products Technical Support/ServiceLocations Asia 23F, Allied Kajima Bldg