Liebert GXT2-6000 RT208 user manual Establishing Communication Link with the UPS

Page 27

Configuration Program

8.3Establishing Communication Link with the UPS

Use only the serial communication cable supplied with the configuration program. If an accessory communication card has been installed in the UPS’s communication card slot, the option card must be removed while using the configuration program.

Use the serial communication cable to connect your computer’s COM1 port to the DB-9 communica- tion port on the rear of the UPS. COM2 may also be used. If the COM port of the host computer has only a DB-25 pin connector, a DB-25 to DB-9 adapter must be added.

The program may be used while the UPS is on to read and confirm the current settings. The UPS must be off and powered by the AC utility when using the configuration program to change any UPS setting. Any attempt to change a setting while the UPS is on will result in an error message.

Select Lbt_gxt2.exe from the program group to start the configuration program. The program will search COM1 & COM2 for a properly connected GXT 2U™ UPS. When the UPS is found, the opening program window will display the UPS model.

If the configuration program ever fails in its attempt to read data from a UPS, the error message below will be displayed. The program must communicate with the UPS when it first opens, when a new tab is opened and when the REFRESH, APPLY or OK buttons are pressed.

If this message is displayed, check the following items:

1.Verify that the serial communication cable is connected properly.

2.Verify that the COM port being used is designated COM1 or COM2.

3.Verify that the UPS is either in Inverter mode, Bypass mode, Battery mode or Off with AC power available at the input (AC Input indicator on). In all cases, the rear fan will be running.

4.Verify that the COM port is not in use by other UPS communication software (or non-UPS software). If MultiLink UPS software is installed on the computer, the MultiLink service must be stopped to free the COM port. MultiLink typically restarts automatically whenever the computer restarts.

5.The UPS serial port is in use by an internal, optional communication card in the UPS card slot. Remove the option card.

6.The program is connected to a UPS that was not designed for this program.

21

Image 27
Contents GXT2-6000RT208 Power AvailabilityPage Table of Contents Controls and Indicators Configuration ProgramModes of Operation MaintenanceTroubleshooting SpecificationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterBattery DC to DC ConverterDynamic Bypass Internal Battery Pack Main Frame and ElectronicsMajor Components PD-001 Removable Power Distribution BoxWHAT’S Included Top bezels Tower use Battery cover grilleGEC connector Mounting hardware Rack mount Handles Configuration Disk Ferrite BeadsAttach Bezels to Top Install the Main CabinetInstallation and Configuration Tower UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityReturn flanges Retaining Latches Front Innermembers members Rack Depth M4 nuts M4 nutsExternal Battery Cabinet Installation Slide cover over connec- tors Loosen screws to move cover Connect Input/Output PowerReplacing a power distribution box Distribution Box Electrical ConnectionsElectrical requirements-PD-001 4 PD-001 Power Distribution BoxPD-HDWR and PD-HDWR-MBS Terminal Block Connections Electrical requirements-PD-HDWR and PD-HDWR-MBSInstall the Grounding Electrode Conductor Install the Internal Battery PackGround Electrode System or Protective Earth System Initial Startup and Electrical Checks Initial Startup and Electrical Checks GXT2-6000RT208 Configuration Program Features Configuration ProgramWhat You Will Need Configuration Program-Installation Establishing Communication Link with the UPS Exit Without Changing UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Changing UPS SettingsN Reverse Detection 120V UPS Models Only UPS TabOutput Voltage Auto RestartFrequency Selection Options TabOptions Tab Used With Earlier GXT 2U Models Battery Cabinets Number Battery TabLow Battery Time Warning Auto Battery Test TimeAbout Tab Horizontal overlay for rack mounting ON/Alarm Silence/Battery Test ButtonControls and Indicators OFF/Bypass ButtonUPS on Indicator Green Battery Level Indicators 5 GreenFault Indicator Red Bypass Indicator AmberModes of Operation Normal Mode OperationBattery Mode Operation Battery Recharge OperationCommunications Snmp Web Card Snmp Adapter Communications Interface PortCommunications 11.1.1 DB-9 Interface PortUPS Intelligent Communications Pin 4 Remote Shutdown on BatteryRemote Emergency Power Off Key to Repo switch connections 1 VDC Sense GroundRepo Connection Battery Cover Captive Screws Front Bezels Battery ReplacementMaintenance Internal Battery Replacement ProceduresConnector Connector cover Cover Electrical connectors UPS ReplacementTroubleshooting Fault indicatorsIndicator status Diagnosis/Audible alarm Alarm conditions Troubleshooting guide Problem Cause SolutionCondition Alarm Only phase angles of 120, 180 or 240 degrees ±10 Battery run times Battery/External Cabinets Load% Minutes6000VA Run Time Auto-Learning Battery Run Times UPS specifications SpecificationsModel Number Battery specificationsPower distribution box specifications See Battery run timesProduct Warranty Registration External battery cabinet specificationsUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Specifications Page Asia 23F, Allied Kajima Bldg Technical Support/ServiceCompany Behind the Products Locations