Liebert GXT2-6000 RT208 user manual Only phase angles of 120, 180 or 240 degrees ±10

Page 44

 

 

 

Troubleshooting

Table 6

Troubleshooting guide

 

 

 

 

Problem

Cause

Solution

 

 

 

Fault and Bypass indicators

UPS internal DC bus

UPS requires service. Contact your local dealer, Liebert

and diagnostic indicator B are

overvoltage.

representative or the Liebert Worldwide Support Group.

illuminated.

 

 

 

 

 

 

 

Fault and Bypass indicators

 

UPS requires service. Contact your local dealer, Liebert

and diagnostic indicator E are

UPS inverter fault.

Representative or the Liebert Worldwide Support Group.

illuminated.

 

 

 

 

 

 

 

 

Fault and Bypass indicators

Inverter-to-Inverter

UPS requires service. Contact your local dealer, Liebert

and diagnostic indicators A

Communications Failure

Representative or the Liebert Worldwide Support Group.

and B are illuminated.

 

 

 

 

 

Fault indicator and diagnostic

 

Replace batteries. Contact your local dealer, Liebert

indicators A and C are

UPS failed the battery test.

representative or the Liebert Worldwide Support Group.

illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

Only phase angles of 120, 180 or 240 degrees (±10

 

 

 

degrees) are permitted. These must be compatible with

 

 

 

the selections in the configuration program.

 

 

 

Or the phase angle has changed while the UPS was

Fault indicator and diagnostic

 

running. The phase angle is detected at startup and

L1 to L2 phase angle

cannot be changed to a different power source while

indicators A and D are

unacceptable.

running.

illuminated.

 

 

 

Turn the UPS Off and wait until the fans stop. Apply input

 

 

 

 

 

 

AC power. The UPS will reprogram the phase angle to

 

 

 

match the utility, if the utility is 120, 180 or 240 degrees

 

 

 

between L1 and L2. If this does not resolve the issue,

 

 

 

contact a qualified electrician to verify the site wiring.

Fault indicator and diagnostic

 

UPS has shut down due to the REPO (Remote Emergency

indicators B and C are

REPO is currently activated.

Power Off). The output cannot be started by any method.

illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

UPS is OFF due to previous REPO (REPO is no longer

Fault indicator and diagnostic

UPS output is OFF from a

activated). Once utility power is restored, press the OFF

indicators B and D are

previous REPO command.

button twice within four seconds (to clear the alarm), then

illuminated.

 

REPO is no longer activated.

press the ON button to start UPS (Auto-restart is NOT

 

 

 

possible).

 

 

 

Your UPS has received a signal or command from the

Fault indicator and diagnostic

UPS shutdown due to a

attached computer. If this was inadvertent, ensure the

indicators C and E are

command from the

communication cable used is correct for your system. For

illuminated.

 

communications port(s).

assistance, contact your local dealer, Liebert

 

 

 

representative or the Liebert Worldwide Support Group.

Fault indicator and diagnostic

 

UPS requires service. Contact your local dealer, Liebert

indicators D and E are

UPS charger fault.

Representative or the Liebert Worldwide Support Group.

illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

Check battery connections, completely power down and

AC Input indicator is On &

Battery source is not

restart UPS.

NOTE: If the battery circuit opens while the UPS is

Battery indicator is flashing.

available; continuous horn.

running, it will be detected when the next battery test is

 

 

 

 

 

 

performed.

 

 

 

 

 

 

Bypass voltage is present,

The AC input powers the PFC input and serves as the

 

 

bypass source. If the AC is present but the voltage or

 

 

but is disabled for use

 

 

frequency exceeds the acceptable range for safe

Bypass indicator is flashing.

because the voltage or

operation with a load, the bypass will be disabled and this

 

 

frequency is outside

 

 

indicator will flash, indicating that the bypass is

 

 

acceptable limits.

 

 

unavailable.

 

 

 

 

 

 

 

38

Image 44
Contents Power Availability GXT2-6000RT208Page Table of Contents Configuration Program Controls and IndicatorsMaintenance TroubleshootingSpecifications Modes of OperationFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDynamic Bypass BatteryDC to DC Converter Major Components Internal Battery PackMain Frame and Electronics Removable Power Distribution Box PD-001Top bezels Tower use Battery cover grille GEC connector Mounting hardware Rack mount HandlesConfiguration Disk Ferrite Beads WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Attach Bezels to TopReturn flanges Retaining Latches Front Innermembers members Installing the Adjustable Rack-Mount Kit-Sold SeparatelyQuantity M4 nuts Rack Depth M4 nutsExternal Battery Cabinet Installation Connect Input/Output Power Replacing a power distribution boxDistribution Box Electrical Connections Slide cover over connec- tors Loosen screws to move cover4 PD-001 Power Distribution Box PD-HDWR and PD-HDWR-MBS Terminal Block ConnectionsElectrical requirements-PD-HDWR and PD-HDWR-MBS Electrical requirements-PD-001Ground Electrode System or Protective Earth System Install the Grounding Electrode ConductorInstall the Internal Battery Pack Initial Startup and Electrical Checks Initial Startup and Electrical Checks What You Will Need GXT2-6000RT208 Configuration Program FeaturesConfiguration Program Configuration Program-Installation Establishing Communication Link with the UPS Configuration Program-Operation Read/Confirm UPS Configuration SettingsChanging UPS Settings Exit Without Changing UPS SettingsUPS Tab Output VoltageAuto Restart N Reverse Detection 120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier GXT 2U Models Battery Tab Low Battery Time WarningAuto Battery Test Time Battery Cabinets NumberAbout Tab ON/Alarm Silence/Battery Test Button Controls and IndicatorsOFF/Bypass Button Horizontal overlay for rack mountingBattery Level Indicators 5 Green Fault Indicator RedBypass Indicator Amber UPS on Indicator GreenNormal Mode Operation Battery Mode OperationBattery Recharge Operation Modes of OperationCommunications Interface Port Communications11.1.1 DB-9 Interface Port Communications Snmp Web Card Snmp AdapterPin 4 Remote Shutdown on Battery UPS Intelligent CommunicationsRepo Connection Remote Emergency Power OffKey to Repo switch connections 1 VDC Sense Ground Battery Replacement MaintenanceInternal Battery Replacement Procedures Battery Cover Captive Screws Front BezelsUPS Replacement Connector Connector cover Cover Electrical connectorsIndicator status Diagnosis/Audible alarm TroubleshootingFault indicators Condition Alarm Alarm conditionsTroubleshooting guide Problem Cause Solution Only phase angles of 120, 180 or 240 degrees ±10 6000VA Run Time Battery run timesBattery/External Cabinets Load% Minutes Auto-Learning Battery Run Times Specifications UPS specificationsBattery specifications Power distribution box specificationsSee Battery run times Model NumberUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Product Warranty RegistrationExternal battery cabinet specifications Specifications Page Technical Support/Service Company Behind the ProductsLocations Asia 23F, Allied Kajima Bldg