Troubleshooting
13.0TROUBLESHOOTING
The information below indicates various symptoms a user may encounter in the event the UPStation
1.The Fault indicator will illuminate, indicating the UPS has detected a problem.
2.An alarm will sound, alerting that the UPS requires attention.
3.One or more additional Load Level/Battery Level indicators will be illuminated to provide a diagnostic aid to the operator, as described below:
A B C
AC Input indicator
DE
Fault indicator
Battery indicators
Load Level indicators
Bypass indicator
Battery indicator UPS ON indicator
Table 4 | Fault indicators | ||
|
| ||
Indicator status | Diagnosis/Audible alarm | ||
|
| ||
All indicators | On bypass due to output overload; beep every | ||
Indicator A |
| On bypass due to overtemperature condition on L1; | |
| On bypass due to overtemperature condition on L2; | ||
|
| ||
Indicator B |
| On bypass due to DC bus overvoltage on L1; | |
| On bypass due to DC bus overvoltage on L2; | ||
|
| ||
Indicator C |
| On bypass due to control power supply failure on L1; | |
| On bypass due to control power supply failure on L2; | ||
|
| ||
Indicator D |
| On bypass due to PFC failure on L1; | |
| On bypass due to PFC failure on L2; | ||
|
| ||
Indicator E |
| On bypass due to inverter failure on L1; | |
| On bypass due to inverter failure on L2; | ||
|
| ||
Indicators A&B | |||
Indicators A&C | UPS failed battery test; | ||
Indicators A&D | L1 to L2 phase angle unacceptable | ||
Indicators B&C | REPO is currently activated, UPS output cannot be started by any method | ||
|
| UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power is | |
Indicators B&D | restored, press the OFF button twice within four seconds (to clear the alarm), then press the | ||
|
| ON button to start UPS | |
Indicators C&E | UPS shutdown due to command from communications (RS232 or SNMP); no beep | ||
Indicators D&E | UPS is OFF due to charger overvoltage; | ||
AC Input indicator On & | AC input has been applied to start UPS but the batteries are either missing or below the | ||
Battery indicator Flashing | minimal level to allow the UPS to start; continuous audible alarm | ||
Bypass indicator Flashing | Bypass voltage is present, but is disabled for use because the voltage or frequency is outside | ||
acceptable limits | |||
|
|
Under fault conditions, the Fault indicators will be illuminated indefinitely while the battery charger is operational, or for a maximum of 5 minutes while the battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World- wide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.