Liebert GXT2-6000 RT208 user manual Troubleshooting, Fault indicators

Page 42

Troubleshooting

13.0TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the UPStation GXT2-6000RT208 develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation.

1.The Fault indicator will illuminate, indicating the UPS has detected a problem.

2.An alarm will sound, alerting that the UPS requires attention.

3.One or more additional Load Level/Battery Level indicators will be illuminated to provide a diagnostic aid to the operator, as described below:

A B C

AC Input indicator

DE

Fault indicator

Battery indicators

Load Level indicators

Bypass indicator

Battery indicator UPS ON indicator

Table 4

Fault indicators

 

 

Indicator status

Diagnosis/Audible alarm

 

 

All indicators

On bypass due to output overload; beep every half-second

Indicator A

 

On bypass due to overtemperature condition on L1; 1-second beep every 4 seconds

 

On bypass due to overtemperature condition on L2; 2-second beep every 4 seconds

 

 

Indicator B

 

On bypass due to DC bus overvoltage on L1; 1-second beep every 4 seconds

 

On bypass due to DC bus overvoltage on L2; 2-second beep every 4 seconds

 

 

Indicator C

 

On bypass due to control power supply failure on L1; 1-second beep every 4 seconds

 

On bypass due to control power supply failure on L2; 2-second beep every 4 seconds

 

 

Indicator D

 

On bypass due to PFC failure on L1; 1-second beep every 4 seconds

 

On bypass due to PFC failure on L2; 2-second beep every 4 seconds

 

 

Indicator E

 

On bypass due to inverter failure on L1; 1-second beep every 4 seconds

 

On bypass due to inverter failure on L2; 2-second beep every 4 seconds

 

 

Indicators A&B

Inverter-to-Inverter communications failure; half-second beep every 1 second

Indicators A&C

UPS failed battery test; 2-second beep every 60 seconds

Indicators A&D

L1 to L2 phase angle unacceptable

Indicators B&C

REPO is currently activated, UPS output cannot be started by any method

 

 

UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power is

Indicators B&D

restored, press the OFF button twice within four seconds (to clear the alarm), then press the

 

 

ON button to start UPS (Auto-restart is NOT possible).

Indicators C&E

UPS shutdown due to command from communications (RS232 or SNMP); no beep

Indicators D&E

UPS is OFF due to charger overvoltage; 1-second beep every 4 seconds

AC Input indicator On &

AC input has been applied to start UPS but the batteries are either missing or below the

Battery indicator Flashing

minimal level to allow the UPS to start; continuous audible alarm

Bypass indicator Flashing

Bypass voltage is present, but is disabled for use because the voltage or frequency is outside

acceptable limits

 

 

Under fault conditions, the Fault indicators will be illuminated indefinitely while the battery charger is operational, or for a maximum of 5 minutes while the battery charger is not operational.

If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World- wide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.

36

Image 42
Contents Power Availability GXT2-6000RT208Page Table of Contents Configuration Program Controls and IndicatorsSpecifications MaintenanceTroubleshooting Modes of OperationFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionBattery DC to DC ConverterDynamic Bypass Internal Battery Pack Main Frame and ElectronicsMajor Components Removable Power Distribution Box PD-001Configuration Disk Ferrite Beads Top bezels Tower use Battery cover grilleGEC connector Mounting hardware Rack mount Handles WHAT’S IncludedTower UPS Installation Install the Main CabinetInstallation and Configuration Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityReturn flanges Retaining Latches Front Innermembers members M4 nuts Rack Depth M4 nutsExternal Battery Cabinet Installation Distribution Box Electrical Connections Connect Input/Output PowerReplacing a power distribution box Slide cover over connec- tors Loosen screws to move coverElectrical requirements-PD-HDWR and PD-HDWR-MBS 4 PD-001 Power Distribution BoxPD-HDWR and PD-HDWR-MBS Terminal Block Connections Electrical requirements-PD-001Install the Grounding Electrode Conductor Install the Internal Battery PackGround Electrode System or Protective Earth System Initial Startup and Electrical Checks Initial Startup and Electrical Checks GXT2-6000RT208 Configuration Program Features Configuration ProgramWhat You Will Need Configuration Program-Installation Establishing Communication Link with the UPS Changing UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Exit Without Changing UPS SettingsAuto Restart UPS TabOutput Voltage N Reverse Detection 120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier GXT 2U Models Auto Battery Test Time Battery TabLow Battery Time Warning Battery Cabinets NumberAbout Tab OFF/Bypass Button ON/Alarm Silence/Battery Test ButtonControls and Indicators Horizontal overlay for rack mountingBypass Indicator Amber Battery Level Indicators 5 GreenFault Indicator Red UPS on Indicator GreenBattery Recharge Operation Normal Mode OperationBattery Mode Operation Modes of Operation11.1.1 DB-9 Interface Port Communications Interface PortCommunications Communications Snmp Web Card Snmp AdapterPin 4 Remote Shutdown on Battery UPS Intelligent CommunicationsRemote Emergency Power Off Key to Repo switch connections 1 VDC Sense GroundRepo Connection Internal Battery Replacement Procedures Battery ReplacementMaintenance Battery Cover Captive Screws Front BezelsUPS Replacement Connector Connector cover Cover Electrical connectorsTroubleshooting Fault indicatorsIndicator status Diagnosis/Audible alarm Alarm conditions Troubleshooting guide Problem Cause SolutionCondition Alarm Only phase angles of 120, 180 or 240 degrees ±10 Battery run times Battery/External Cabinets Load% Minutes6000VA Run Time Auto-Learning Battery Run Times Specifications UPS specificationsSee Battery run times Battery specificationsPower distribution box specifications Model NumberProduct Warranty Registration External battery cabinet specificationsUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Specifications Page Locations Technical Support/ServiceCompany Behind the Products Asia 23F, Allied Kajima Bldg