Liebert GXT2-6000 RT208 user manual Install the Grounding Electrode Conductor

Page 22

Installation and Configuration

6.4Install the Grounding Electrode Conductor

A Grounding Electrode Conductor must be attached to the rear panel using the M5x12 Phillips screw provided. This connection is required in addition to the power input ground connection to the remov- able power distribution box.

Install an 8 AWG (10 mm2) (75°C copper wire) (minimum size, see NEC 250-5d, 250-81, 250-83, table 250-94) grounding electrode conductor to the nearest effectively grounded metal structural member, nearest effectively grounded metal water pipe or other grounding electrode in the grounding electrode system. If the grounding electrode conductor must be protected, non-metal conduit is recommended. If metal conduit must be used, bond both ends of the conduit to the grounding electrode conductor. Con- duit is not an acceptable grounding electrode conductor.

A 5mm ring lug for 8AWG wire lug is provided in the accessory box. Other suitable connectors may be used.

 

GROUNDING ELECTRODE CONDUCTOR

+

+

Ground Electrode System or Protective Earth System

NOTE

IN BATTERY MODE ONLY, the UPS operates as a separately derived source and contains a neutral to ground bonding jumper. A grounding electrode conductor (GEC) must be installed in accordance with national and local wiring codes and regulations.

6.5Install the Internal Battery Pack

To facilitate shipping and installation, the GXT2-6000RT208 ships without the internal battery installed. Once the UPS is installed in place, the internal battery pack must be installed.

1.Unpack the internal battery from its shipping container.

2.Lift the battery pack from its container, holding it in the center of the pack. Do NOT lift the battery pack by grasping the connector on the rear.

3.Align the battery pack so that the rear connector is nearest the control panel.

4.Slide in the battery pack until fully inserted.

5.Install the battery door, tightening the two captive screws, finger tight. The battery door will not install if the battery is not fully inserted.

6.For tower installation, place the horizontal overlay over the controls and indicators (see illustration at right).

7.Install the two front bezels.

Controls and Indicators

Screws for battery door

Battery

Compartment

Battery

Battery cover

Front bezels

Back of battery

Battery connector

16

Image 22
Contents Power Availability GXT2-6000RT208Page Table of Contents Configuration Program Controls and IndicatorsSpecifications MaintenanceTroubleshooting Modes of OperationFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionDC to DC Converter BatteryDynamic Bypass Main Frame and Electronics Internal Battery PackMajor Components Removable Power Distribution Box PD-001Configuration Disk Ferrite Beads Top bezels Tower use Battery cover grilleGEC connector Mounting hardware Rack mount Handles WHAT’S IncludedTower UPS Installation Install the Main CabinetInstallation and Configuration Attach Bezels to TopQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyReturn flanges Retaining Latches Front Innermembers members M4 nuts Rack Depth M4 nuts External Battery Cabinet Installation Distribution Box Electrical Connections Connect Input/Output PowerReplacing a power distribution box Slide cover over connec- tors Loosen screws to move coverElectrical requirements-PD-HDWR and PD-HDWR-MBS 4 PD-001 Power Distribution BoxPD-HDWR and PD-HDWR-MBS Terminal Block Connections Electrical requirements-PD-001Install the Internal Battery Pack Install the Grounding Electrode ConductorGround Electrode System or Protective Earth System Initial Startup and Electrical Checks Initial Startup and Electrical Checks Configuration Program GXT2-6000RT208 Configuration Program FeaturesWhat You Will Need Configuration Program-Installation Establishing Communication Link with the UPS Changing UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Exit Without Changing UPS SettingsAuto Restart UPS TabOutput Voltage N Reverse Detection 120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier GXT 2U Models Auto Battery Test Time Battery TabLow Battery Time Warning Battery Cabinets NumberAbout Tab OFF/Bypass Button ON/Alarm Silence/Battery Test ButtonControls and Indicators Horizontal overlay for rack mountingBypass Indicator Amber Battery Level Indicators 5 GreenFault Indicator Red UPS on Indicator GreenBattery Recharge Operation Normal Mode OperationBattery Mode Operation Modes of Operation11.1.1 DB-9 Interface Port Communications Interface PortCommunications Communications Snmp Web Card Snmp AdapterPin 4 Remote Shutdown on Battery UPS Intelligent CommunicationsKey to Repo switch connections 1 VDC Sense Ground Remote Emergency Power OffRepo Connection Internal Battery Replacement Procedures Battery ReplacementMaintenance Battery Cover Captive Screws Front BezelsUPS Replacement Connector Connector cover Cover Electrical connectorsFault indicators TroubleshootingIndicator status Diagnosis/Audible alarm Troubleshooting guide Problem Cause Solution Alarm conditionsCondition Alarm Only phase angles of 120, 180 or 240 degrees ±10 Battery/External Cabinets Load% Minutes Battery run times6000VA Run Time Auto-Learning Battery Run Times Specifications UPS specificationsSee Battery run times Battery specificationsPower distribution box specifications Model NumberExternal battery cabinet specifications Product Warranty RegistrationUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Specifications Page Locations Technical Support/ServiceCompany Behind the Products Asia 23F, Allied Kajima Bldg