Liebert GXT2-6000 RT208 user manual External Battery Cabinet Installation

Page 19

Installation and Configuration

6.2External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS.

! CAUTION

The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.

! CAUTION

Verify that the battery cabinet circuit breaker is in the OFF position. Do no energize the battery cabinet at this time. When installation is complete, you will be instructed to turn on the circuit breaker.

When the external battery cabinet is received, it should be inspected for freight damage. Report dam- age to the carrier and your local dealer or Liebert representative.

To install an external battery cabinet:

1.For slide rail installations, first remove the top/side fin by sliding it forward and lifting it up. Optional rack-mount handles are shipped with the external battery cabinet and may be installed now. (Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert representative for these additional options and any assistance needed.)

2.Fasten the slides into position with the screws according to the instructions included with the slide rails.

3.Use the enclosed support bases for the tower option to prevent the assembly from tipping over. One additional set of support base extensions ships with each external battery cabinet.

4.Connect the supplied external battery cabinet cable to either of the connectors on the rear of the external battery cabinet, then to the rear of the UPS.

5.The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 7 - Battery run times in this manual.

6.Do NOT turn on the battery cabinet circuit breaker at this time. Please complete the remainder of the installation first.

NOTE

After installation is complete, you must use the included configuration program to program the UPS for the number of external battery cabinets connected. Instructions for using the configuration program follow in 8.0 - Configuration Program.

Support Base With Spacers for External Battery Cabinets

-

+

-

+

UPS and Four External Battery Cabinets With Support Base

13

Image 19
Contents GXT2-6000RT208 Power AvailabilityPage Table of Contents Controls and Indicators Configuration ProgramModes of Operation MaintenanceTroubleshooting SpecificationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDC to DC Converter BatteryDynamic Bypass Main Frame and Electronics Internal Battery PackMajor Components PD-001 Removable Power Distribution BoxWHAT’S Included Top bezels Tower use Battery cover grilleGEC connector Mounting hardware Rack mount Handles Configuration Disk Ferrite BeadsAttach Bezels to Top Install the Main CabinetInstallation and Configuration Tower UPS InstallationQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyReturn flanges Retaining Latches Front Innermembers members Rack Depth M4 nuts M4 nutsExternal Battery Cabinet Installation Slide cover over connec- tors Loosen screws to move cover Connect Input/Output PowerReplacing a power distribution box Distribution Box Electrical ConnectionsElectrical requirements-PD-001 4 PD-001 Power Distribution BoxPD-HDWR and PD-HDWR-MBS Terminal Block Connections Electrical requirements-PD-HDWR and PD-HDWR-MBSInstall the Internal Battery Pack Install the Grounding Electrode ConductorGround Electrode System or Protective Earth System Initial Startup and Electrical Checks Initial Startup and Electrical Checks Configuration Program GXT2-6000RT208 Configuration Program FeaturesWhat You Will Need Configuration Program-Installation Establishing Communication Link with the UPS Exit Without Changing UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Changing UPS SettingsN Reverse Detection 120V UPS Models Only UPS TabOutput Voltage Auto RestartFrequency Selection Options TabOptions Tab Used With Earlier GXT 2U Models Battery Cabinets Number Battery TabLow Battery Time Warning Auto Battery Test TimeAbout Tab Horizontal overlay for rack mounting ON/Alarm Silence/Battery Test ButtonControls and Indicators OFF/Bypass ButtonUPS on Indicator Green Battery Level Indicators 5 GreenFault Indicator Red Bypass Indicator AmberModes of Operation Normal Mode OperationBattery Mode Operation Battery Recharge OperationCommunications Snmp Web Card Snmp Adapter Communications Interface PortCommunications 11.1.1 DB-9 Interface PortUPS Intelligent Communications Pin 4 Remote Shutdown on BatteryKey to Repo switch connections 1 VDC Sense Ground Remote Emergency Power OffRepo Connection Battery Cover Captive Screws Front Bezels Battery ReplacementMaintenance Internal Battery Replacement ProceduresConnector Connector cover Cover Electrical connectors UPS ReplacementFault indicators TroubleshootingIndicator status Diagnosis/Audible alarm Troubleshooting guide Problem Cause Solution Alarm conditionsCondition Alarm Only phase angles of 120, 180 or 240 degrees ±10 Battery/External Cabinets Load% Minutes Battery run times6000VA Run Time Auto-Learning Battery Run Times UPS specifications SpecificationsModel Number Battery specificationsPower distribution box specifications See Battery run timesExternal battery cabinet specifications Product Warranty RegistrationUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Specifications Page Asia 23F, Allied Kajima Bldg Technical Support/ServiceCompany Behind the Products Locations