Liebert GXT2-6000 RT208 UPS Replacement, Connector Connector cover Cover Electrical connectors

Page 41

Maintenance

12.2UPS Replacement

When using a power distribution box with bypass, the UPS can be removed while powering the load through the Bypass Switch.

NOTE

During the procedure, the connected load will not be protected from power disturbances, such as spikes, sags and failure.

To remove the UPS without shutting off power to the connected load:

1.Turn the Bypass Switch on the power distribution box to the Utility position.

2.Open the Output circuit breaker (on the UPS rear panel).

3.Open the Input circuit breaker (on the power distribution box).

4.Loosen the three captive mounting screws about 20 turns until the power distribution box can be pulled away from the UPS.

5.Loosen the electrical connector cover by backing out the two screws holding it one turn each. Also loosen the end screw one turn.

6.Slide the cover to reach the end screw and cover the electrical connectors; retighten the three screws gently to hold the cover in place.

7.Replace the UPS.

8.Loosen the three screws holding the electrical connector cover again—one turn each.

9.Slide the cover away from the electrical connectors; gently retighten the three screws.

10.Align the connectors on the power distribution box and the UPS.

11.Push the power distribution box into place.

12.Holding the power distribution box firmly against the UPS, tighten the three captive mounting screws until the box is secure. Do NOT overtighten the screws.

13.Close the Input circuit breaker (on the power distribution box).

14.Close the Output circuit breaker (on the UPS rear panel).

15.Turn the Bypass Switch on the power distribution box back to the UPS position.

THEMANUAL

DISCONNECT

BYPASS SWITCH.

BYPASS POWER TO

Mounting screws

for removable power

distribution box

Electrical

Screws securing electrical

connector

connector cover

cover

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical connectors

35

Image 41
Contents GXT2-6000RT208 Power AvailabilityPage Table of Contents Controls and Indicators Configuration ProgramTroubleshooting MaintenanceSpecifications Modes of OperationFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionDynamic Bypass BatteryDC to DC Converter Major Components Internal Battery PackMain Frame and Electronics PD-001 Removable Power Distribution BoxGEC connector Mounting hardware Rack mount Handles Top bezels Tower use Battery cover grilleConfiguration Disk Ferrite Beads WHAT’S IncludedInstallation and Configuration Install the Main CabinetTower UPS Installation Attach Bezels to TopReturn flanges Retaining Latches Front Innermembers members Installing the Adjustable Rack-Mount Kit-Sold SeparatelyQuantity Rack Depth M4 nuts M4 nutsExternal Battery Cabinet Installation Replacing a power distribution box Connect Input/Output PowerDistribution Box Electrical Connections Slide cover over connec- tors Loosen screws to move coverPD-HDWR and PD-HDWR-MBS Terminal Block Connections 4 PD-001 Power Distribution BoxElectrical requirements-PD-HDWR and PD-HDWR-MBS Electrical requirements-PD-001Ground Electrode System or Protective Earth System Install the Grounding Electrode ConductorInstall the Internal Battery Pack Initial Startup and Electrical Checks Initial Startup and Electrical Checks What You Will Need GXT2-6000RT208 Configuration Program FeaturesConfiguration Program Configuration Program-Installation Establishing Communication Link with the UPS Read/Confirm UPS Configuration Settings Configuration Program-OperationChanging UPS Settings Exit Without Changing UPS SettingsOutput Voltage UPS TabAuto Restart N Reverse Detection 120V UPS Models OnlyFrequency Selection Options TabOptions Tab Used With Earlier GXT 2U Models Low Battery Time Warning Battery TabAuto Battery Test Time Battery Cabinets NumberAbout Tab Controls and Indicators ON/Alarm Silence/Battery Test ButtonOFF/Bypass Button Horizontal overlay for rack mountingFault Indicator Red Battery Level Indicators 5 GreenBypass Indicator Amber UPS on Indicator GreenBattery Mode Operation Normal Mode OperationBattery Recharge Operation Modes of OperationCommunications Communications Interface Port11.1.1 DB-9 Interface Port Communications Snmp Web Card Snmp AdapterUPS Intelligent Communications Pin 4 Remote Shutdown on BatteryRepo Connection Remote Emergency Power OffKey to Repo switch connections 1 VDC Sense Ground Maintenance Battery ReplacementInternal Battery Replacement Procedures Battery Cover Captive Screws Front BezelsConnector Connector cover Cover Electrical connectors UPS ReplacementIndicator status Diagnosis/Audible alarm TroubleshootingFault indicators Condition Alarm Alarm conditionsTroubleshooting guide Problem Cause Solution Only phase angles of 120, 180 or 240 degrees ±10 6000VA Run Time Battery run timesBattery/External Cabinets Load% Minutes Auto-Learning Battery Run Times UPS specifications SpecificationsPower distribution box specifications Battery specificationsSee Battery run times Model NumberUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Product Warranty RegistrationExternal battery cabinet specifications Specifications Page Company Behind the Products Technical Support/ServiceLocations Asia 23F, Allied Kajima Bldg