Liebert GXT2-6000 RT208 user manual Auto-Learning Battery Run Times

Page 46

Troubleshooting

13.1Auto-Learning Battery Run Times

As batteries age, the estimated run times may become less accurate. The GXT2-6000RT208 is pro- grammed to “learn” from a full battery discharge and modify the estimated run time for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.

The UPS will update the anticipated run time calculation only under certain conditions.

The UPS must have a steady load that is greater than 20%.

The UPS must be at 100% charge at the start of a battery discharge.

The battery discharge must continue uninterrupted until the batteries reach their end-of-dis- charge voltage.

If all conditions are not met, the run time calculation will not be modified.

If the configuration program is used to change the number of battery cabinets, then the values in the battery table on the right will be restored. This will override any value that is automatically learned.

40

Image 46
Contents Power Availability GXT2-6000RT208Page Table of Contents Configuration Program Controls and IndicatorsSpecifications MaintenanceTroubleshooting Modes of OperationFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionDC to DC Converter BatteryDynamic Bypass Main Frame and Electronics Internal Battery PackMajor Components Removable Power Distribution Box PD-001Configuration Disk Ferrite Beads Top bezels Tower use Battery cover grilleGEC connector Mounting hardware Rack mount Handles WHAT’S IncludedTower UPS Installation Install the Main CabinetInstallation and Configuration Attach Bezels to TopQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyReturn flanges Retaining Latches Front Innermembers members M4 nuts Rack Depth M4 nutsExternal Battery Cabinet Installation Distribution Box Electrical Connections Connect Input/Output PowerReplacing a power distribution box Slide cover over connec- tors Loosen screws to move coverElectrical requirements-PD-HDWR and PD-HDWR-MBS 4 PD-001 Power Distribution BoxPD-HDWR and PD-HDWR-MBS Terminal Block Connections Electrical requirements-PD-001Install the Internal Battery Pack Install the Grounding Electrode ConductorGround Electrode System or Protective Earth System Initial Startup and Electrical Checks Initial Startup and Electrical Checks Configuration Program GXT2-6000RT208 Configuration Program FeaturesWhat You Will Need Configuration Program-Installation Establishing Communication Link with the UPS Changing UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Exit Without Changing UPS SettingsAuto Restart UPS TabOutput Voltage N Reverse Detection 120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier GXT 2U Models Auto Battery Test Time Battery TabLow Battery Time Warning Battery Cabinets NumberAbout Tab OFF/Bypass Button ON/Alarm Silence/Battery Test ButtonControls and Indicators Horizontal overlay for rack mountingBypass Indicator Amber Battery Level Indicators 5 GreenFault Indicator Red UPS on Indicator GreenBattery Recharge Operation Normal Mode OperationBattery Mode Operation Modes of Operation11.1.1 DB-9 Interface Port Communications Interface PortCommunications Communications Snmp Web Card Snmp AdapterPin 4 Remote Shutdown on Battery UPS Intelligent CommunicationsKey to Repo switch connections 1 VDC Sense Ground Remote Emergency Power OffRepo Connection Internal Battery Replacement Procedures Battery ReplacementMaintenance Battery Cover Captive Screws Front BezelsUPS Replacement Connector Connector cover Cover Electrical connectorsFault indicators TroubleshootingIndicator status Diagnosis/Audible alarm Troubleshooting guide Problem Cause Solution Alarm conditionsCondition Alarm Only phase angles of 120, 180 or 240 degrees ±10 Battery/External Cabinets Load% Minutes Battery run times6000VA Run Time Auto-Learning Battery Run Times Specifications UPS specificationsSee Battery run times Battery specificationsPower distribution box specifications Model NumberExternal battery cabinet specifications Product Warranty RegistrationUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Specifications Page Locations Technical Support/ServiceCompany Behind the Products Asia 23F, Allied Kajima Bldg