Liebert GXT2-6000 RT208 user manual Connect Input/Output Power, Replacing a power distribution box

Page 20

Installation and Configuration

6.3Connect Input/Output Power

The UPS ships with the basic hardwire box attached. If an optional model is to be used, remove the standard box and install the optional box using the three captive mounting screws marked in the illustration, below, right.

6.3.1Replacing a power distribution box

Whenever a power distribution box is not attached to a UPS, the cover must be slid over the electrical connectors to prevent damage or injury.

1.On the power distribution box attached to the UPS, locate the three captive mounting screws holding the box to the UPS (see illustration above, right).

2.Turn the screws until the box can be pulled away from the UPS. Exercise care to avoid removing screws from the hardwire box.

3.On the replacement power distribution box to be attached to the UPS, loosen the cover over the electrical connectors by backing out the three screws one turn each.

4.Slide the cover open to expose the electrical connectors.

5.Gently retighten the three screws loosened in Step 3.

6.Align the connectors on the box and UPS.

7.Push the box into place.

8.Holding the box firmly against the UPS, tighten the three captive mounting screws until the box is secure. Do not overtighten.

Slide cover over connec- tors

Loosen screws to move cover

THEMANUAL

DISCONNECT

BYPASS SWITCH.

BYPASS POWER TO

Mounting screws for removable box

6.3.2Distribution Box Electrical Connections

Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.

The installer must provide a 30A branch circuit breaker. The input circuit breaker on the distribution box and the output circuit breaker on the rear fixed-panel of the UPS disconnect all power between the main cabinet and the distribution box.

Models equipped with a manual bypass switch pass utility power directly to the bypass switch from the input terminal block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass switch.

Figure 3 30A branch circuit breaker connection diagram

PD-HDWR Distribution Box

PD-HDWR-MBS Distribution Box

Input

 

Input

 

 

Utility

Output

Utility

 

Byp

30A External

30A Input

30A External

30A Input

Output

Inv

Branch Circuit

Circuit

Branch Circuit

Circuit

Breaker

Breaker

Breaker

Breaker

 

30A UPS Output

30A UPS Output

Circuit Breaker

Circuit Breaker

UPS - PFC, Battery, Inverter

UPS - PFC, Battery, Inverter

14

Image 20
Contents Power Availability GXT2-6000RT208Page Table of Contents Configuration Program Controls and IndicatorsMaintenance TroubleshootingSpecifications Modes of OperationFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDynamic Bypass BatteryDC to DC Converter Major Components Internal Battery PackMain Frame and Electronics Removable Power Distribution Box PD-001Top bezels Tower use Battery cover grille GEC connector Mounting hardware Rack mount HandlesConfiguration Disk Ferrite Beads WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Attach Bezels to TopReturn flanges Retaining Latches Front Innermembers members Installing the Adjustable Rack-Mount Kit-Sold SeparatelyQuantity M4 nuts Rack Depth M4 nutsExternal Battery Cabinet Installation Connect Input/Output Power Replacing a power distribution boxDistribution Box Electrical Connections Slide cover over connec- tors Loosen screws to move cover4 PD-001 Power Distribution Box PD-HDWR and PD-HDWR-MBS Terminal Block ConnectionsElectrical requirements-PD-HDWR and PD-HDWR-MBS Electrical requirements-PD-001Ground Electrode System or Protective Earth System Install the Grounding Electrode ConductorInstall the Internal Battery Pack Initial Startup and Electrical Checks Initial Startup and Electrical Checks What You Will Need GXT2-6000RT208 Configuration Program FeaturesConfiguration Program Configuration Program-Installation Establishing Communication Link with the UPS Configuration Program-Operation Read/Confirm UPS Configuration SettingsChanging UPS Settings Exit Without Changing UPS SettingsUPS Tab Output VoltageAuto Restart N Reverse Detection 120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier GXT 2U Models Battery Tab Low Battery Time WarningAuto Battery Test Time Battery Cabinets NumberAbout Tab ON/Alarm Silence/Battery Test Button Controls and IndicatorsOFF/Bypass Button Horizontal overlay for rack mountingBattery Level Indicators 5 Green Fault Indicator RedBypass Indicator Amber UPS on Indicator GreenNormal Mode Operation Battery Mode OperationBattery Recharge Operation Modes of OperationCommunications Interface Port Communications11.1.1 DB-9 Interface Port Communications Snmp Web Card Snmp AdapterPin 4 Remote Shutdown on Battery UPS Intelligent CommunicationsRepo Connection Remote Emergency Power OffKey to Repo switch connections 1 VDC Sense Ground Battery Replacement MaintenanceInternal Battery Replacement Procedures Battery Cover Captive Screws Front BezelsUPS Replacement Connector Connector cover Cover Electrical connectorsIndicator status Diagnosis/Audible alarm TroubleshootingFault indicators Condition Alarm Alarm conditionsTroubleshooting guide Problem Cause Solution Only phase angles of 120, 180 or 240 degrees ±10 6000VA Run Time Battery run timesBattery/External Cabinets Load% Minutes Auto-Learning Battery Run Times Specifications UPS specificationsBattery specifications Power distribution box specificationsSee Battery run times Model NumberUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Product Warranty RegistrationExternal battery cabinet specifications Specifications Page Technical Support/Service Company Behind the ProductsLocations Asia 23F, Allied Kajima Bldg