Liebert GXT2-6000 RT208 user manual Alarm conditions, Troubleshooting guide Problem Cause Solution

Page 43

Troubleshooting

All audible alarms can be silenced, with the exception of Low Battery, Bypass Reminder and Missing Batteries at Startup alarms. Once silenced, the alarm will not sound again until a new alarm condi- tion is present.

Table 5

Alarm conditions

 

 

 

 

 

Condition

Alarm

 

 

Battery Mode (utility failure)

One short beep every 10 seconds; more than 2 minutes of run time remaining

 

 

 

Low Battery

 

Two short beeps every 5 seconds; less than 2 minutes of run time remaining

 

 

On Bypass Reminder

A one-second beep every 2 minutes

 

 

Output Overload (bypass)

One short beep every half second

 

 

Overtemperature (bypass)

A one-second, or two-second, beep every 4 seconds

 

 

DC Bus Overvoltage (bypass)

A one-second, or two-second, beep every 4 seconds

 

 

Control Power Supply Failure (bypass)

A one-second, or two-second, beep every 4 seconds

 

 

PFC Failure (bypass)

A one-second, or two-second, beep every 4 seconds

 

 

Inverter Failure

A one-second, or two-second, beep every 4 seconds

 

 

Inverter-to-Inverter Communications

A one-half second beep every 1 second

Failure

 

 

 

Battery Test Failure

A two-second beep every 1 minute

 

 

REPO Activated

A one-quarter second beep every half second

 

 

 

Table 6

Troubleshooting guide

 

 

 

 

Problem

Cause

Solution

 

 

 

 

UPS fails to start when the

UPS is short-circuited or

Ensure the UPS is OFF. Disconnect all loads and ensure

nothing is lodged in output receptacles.

ON button is pressed.

overloaded.

Ensure the loads are not defective or shorted internally.

 

 

 

 

 

 

 

 

 

UPS not plugged in.

UPS is operating in Battery Mode, make certain UPS is

 

 

securely plugged into the wall receptacle.

 

 

 

Battery indicator is

UPS input protection fuse

UPS is operating in Battery Mode. Save data and close

has blown/opened.

applications. Replace UPS input fuse, then restart UPS.

illuminated.

 

 

 

Utility voltage out of UPS

UPS is operating in Battery Mode. Save data and close

 

 

applications. Ensure utility supply voltage is within

 

 

input range.

 

 

acceptable limits for UPS.

 

 

 

 

 

 

 

 

 

Batteries are not fully

Keep UPS plugged in continuously at least 24 hours to

 

 

charged.

recharge batteries.

UPS has reduced battery

UPS is overloaded.

Check load level display and reduce the load on the UPS.

time.

 

 

 

 

Batteries may not be able to

Replace batteries. Contact your local dealer, Liebert

 

 

 

 

representative or the Liebert Worldwide Support Group for

 

 

hold a full charge due to age.

 

 

replacement battery kit.

 

 

 

 

 

 

Fault and Bypass indicators

UPS overloaded or load

Check load level display and remove non-essential loads.

and all Load Level indicators

Recalculate the load and reduce number of loads

equipment is faulty.

are illuminated.

connected to UPS. Check load equipment for faults.

 

 

 

 

Fault and Bypass indicators

UPS control power supply

UPS requires service. Contact your local dealer, Liebert

and diagnostic indicator C are

fault.

representative or the Liebert Worldwide Support Group.

illuminated.

 

 

 

 

 

 

 

Fault and Bypass indicators

UPS PFC (Power Factor

UPS requires service. Contact your local dealer, Liebert

and diagnostic indicator D are

Correction Circuit) fault.

representative or the Liebert Worldwide Support Group.

illuminated.

 

 

 

 

 

 

 

 

 

 

UPS internal fan has a

Ensure the UPS is not overloaded, ventilation openings

 

 

are not blocked and room ambient temperature is not

Fault and Bypass indicators

problem or UPS shutdown

excessive.

and diagnostic indicator A are

due to temperature

Wait 30 minutes to allow UPS to cool, then restart UPS.

illuminated.

 

condition. Load is on bypass

 

If UPS does not restart, contact your local dealer, Liebert

 

 

power.

 

 

representative or the Liebert Worldwide Support Group.

 

 

 

 

 

 

 

37

Image 43
Contents GXT2-6000RT208 Power AvailabilityPage Table of Contents Controls and Indicators Configuration ProgramModes of Operation MaintenanceTroubleshooting SpecificationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDC to DC Converter BatteryDynamic Bypass Main Frame and Electronics Internal Battery PackMajor Components PD-001 Removable Power Distribution BoxWHAT’S Included Top bezels Tower use Battery cover grilleGEC connector Mounting hardware Rack mount Handles Configuration Disk Ferrite BeadsAttach Bezels to Top Install the Main CabinetInstallation and Configuration Tower UPS InstallationQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyReturn flanges Retaining Latches Front Innermembers members Rack Depth M4 nuts M4 nutsExternal Battery Cabinet Installation Slide cover over connec- tors Loosen screws to move cover Connect Input/Output PowerReplacing a power distribution box Distribution Box Electrical ConnectionsElectrical requirements-PD-001 4 PD-001 Power Distribution BoxPD-HDWR and PD-HDWR-MBS Terminal Block Connections Electrical requirements-PD-HDWR and PD-HDWR-MBSInstall the Internal Battery Pack Install the Grounding Electrode ConductorGround Electrode System or Protective Earth System Initial Startup and Electrical Checks Initial Startup and Electrical Checks Configuration Program GXT2-6000RT208 Configuration Program FeaturesWhat You Will Need Configuration Program-Installation Establishing Communication Link with the UPS Exit Without Changing UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Changing UPS SettingsN Reverse Detection 120V UPS Models Only UPS TabOutput Voltage Auto RestartFrequency Selection Options TabOptions Tab Used With Earlier GXT 2U Models Battery Cabinets Number Battery TabLow Battery Time Warning Auto Battery Test TimeAbout Tab Horizontal overlay for rack mounting ON/Alarm Silence/Battery Test ButtonControls and Indicators OFF/Bypass ButtonUPS on Indicator Green Battery Level Indicators 5 GreenFault Indicator Red Bypass Indicator AmberModes of Operation Normal Mode OperationBattery Mode Operation Battery Recharge OperationCommunications Snmp Web Card Snmp Adapter Communications Interface PortCommunications 11.1.1 DB-9 Interface PortUPS Intelligent Communications Pin 4 Remote Shutdown on BatteryKey to Repo switch connections 1 VDC Sense Ground Remote Emergency Power OffRepo Connection Battery Cover Captive Screws Front Bezels Battery ReplacementMaintenance Internal Battery Replacement ProceduresConnector Connector cover Cover Electrical connectors UPS ReplacementFault indicators TroubleshootingIndicator status Diagnosis/Audible alarm Troubleshooting guide Problem Cause Solution Alarm conditionsCondition Alarm Only phase angles of 120, 180 or 240 degrees ±10 Battery/External Cabinets Load% Minutes Battery run times6000VA Run Time Auto-Learning Battery Run Times UPS specifications SpecificationsModel Number Battery specificationsPower distribution box specifications See Battery run timesExternal battery cabinet specifications Product Warranty RegistrationUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Specifications Page Asia 23F, Allied Kajima Bldg Technical Support/ServiceCompany Behind the Products Locations