Liebert GXT2-6000 RT208 user manual Options Tab, Frequency Selection

Page 30

Configuration Program

8.5.4Frequency Selection

The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the model. All models are capable of being used as 50Hz or 60Hz systems. The UPS will automatically sense the utility frequency when first plugged in and set the nominal frequency to match. Therefore, for all normal use the Auto Sense button should be selected.

Some special applications require that the UPS be used as a frequency converter. Frequency con- verter 50Hz or frequency converter 60Hz may be selected.

Note that frequency converter operation disables the Bypass. If, for any reason, the UPS inverter is unable to power the load, the alternate bypass to utility power will not be available and power will be removed from any load.

8.6Options Tab

Computer users may choose to use versatile com- puter shutdown software that communicates with the UPS via a serial communications cable. The Options tab should not be used to modify the UPS functions for such applications.

For some industrial applications and special computer applications, the UPS may be moni- tored and controlled using external voltages and relay contact signals. The Options tab expands the UPS versatility for such applications.

Refer to your UPS manual for a description of the 9-pin communication connector on the rear of the UPS. Pin 6 of the 9-pin communication connector is used for “Any Mode Shutdown” of the UPS out- put. This control input may be used in special applications to disable the UPS output power - both Inverter and Bypass.

The Options tab allows the behavior of the Any Mode Shutdown feature to be modified.

When the program opens or the REFRESH but- ton is pressed, the UPS setting is read by the configuration program and displayed.

Factory Default Setting Illustrated - This Options tab illustration shows the available function definitions using pin 6 and the factory default settings.

! WARNING

Auto-Enable Output

Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS output can turn on automatically and without warning if the Pin 6 connection is changed.

! WARNING

Pin 6 Logic

DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to install a normally-closed connection between Pins 5 & 6. This connection must be maintained to use the UPS or to use the configuration program again, including the ability to change the UPS setting back to the default setting using the configuration program via a serial communication link.

24

Image 30
Contents Power Availability GXT2-6000RT208Page Table of Contents Configuration Program Controls and IndicatorsSpecifications MaintenanceTroubleshooting Modes of OperationFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionBattery DC to DC ConverterDynamic Bypass Internal Battery Pack Main Frame and ElectronicsMajor Components Removable Power Distribution Box PD-001Configuration Disk Ferrite Beads Top bezels Tower use Battery cover grilleGEC connector Mounting hardware Rack mount Handles WHAT’S IncludedTower UPS Installation Install the Main CabinetInstallation and Configuration Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityReturn flanges Retaining Latches Front Innermembers members M4 nuts Rack Depth M4 nutsExternal Battery Cabinet Installation Distribution Box Electrical Connections Connect Input/Output PowerReplacing a power distribution box Slide cover over connec- tors Loosen screws to move coverElectrical requirements-PD-HDWR and PD-HDWR-MBS 4 PD-001 Power Distribution BoxPD-HDWR and PD-HDWR-MBS Terminal Block Connections Electrical requirements-PD-001Install the Grounding Electrode Conductor Install the Internal Battery PackGround Electrode System or Protective Earth System Initial Startup and Electrical Checks Initial Startup and Electrical Checks GXT2-6000RT208 Configuration Program Features Configuration ProgramWhat You Will Need Configuration Program-Installation Establishing Communication Link with the UPS Changing UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Exit Without Changing UPS SettingsAuto Restart UPS TabOutput Voltage N Reverse Detection 120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier GXT 2U Models Auto Battery Test Time Battery TabLow Battery Time Warning Battery Cabinets NumberAbout Tab OFF/Bypass Button ON/Alarm Silence/Battery Test ButtonControls and Indicators Horizontal overlay for rack mountingBypass Indicator Amber Battery Level Indicators 5 GreenFault Indicator Red UPS on Indicator GreenBattery Recharge Operation Normal Mode OperationBattery Mode Operation Modes of Operation11.1.1 DB-9 Interface Port Communications Interface PortCommunications Communications Snmp Web Card Snmp AdapterPin 4 Remote Shutdown on Battery UPS Intelligent CommunicationsRemote Emergency Power Off Key to Repo switch connections 1 VDC Sense GroundRepo Connection Internal Battery Replacement Procedures Battery ReplacementMaintenance Battery Cover Captive Screws Front BezelsUPS Replacement Connector Connector cover Cover Electrical connectorsTroubleshooting Fault indicatorsIndicator status Diagnosis/Audible alarm Alarm conditions Troubleshooting guide Problem Cause SolutionCondition Alarm Only phase angles of 120, 180 or 240 degrees ±10 Battery run times Battery/External Cabinets Load% Minutes6000VA Run Time Auto-Learning Battery Run Times Specifications UPS specificationsSee Battery run times Battery specificationsPower distribution box specifications Model NumberProduct Warranty Registration External battery cabinet specificationsUsed w/ UPS Model GXT2-6000RT208 Dimensions in mm Specifications Page Locations Technical Support/ServiceCompany Behind the Products Asia 23F, Allied Kajima Bldg