Eaton Electrical 10640205, APR48 General Description, APS3 and APS6 Series 48V DC Power Systems

Page 5

Data Power Solutions Quick Start Guide

General Description

APS3 and APS6 Series (48V) DC Power Systems

APS dc power systems provide high reliability 48V dc power for wiring closet and other data and telecommunications equipment. Each power system includes ac/dc rectifier modules, a supervisory module to provide control and communications functions, circuit breakers to protect the output cabling, and output terminals to connect the cables to the dc powered equipment and optional batteries. Four APS3 and two APS6 dc power system models are available, as shown on the following three pages.

APS3-058rack-mounted version, without battery option

APS3-059rack-mounted version, with battery option

APS3-060 – desktop version, without battery option

APS3-061 – desktop version, with battery option

APS6-058rack-mounted version, without battery option

APS6-059rack-mounted version, with battery option

Input: APS dc power systems can be powered by a wide range of ac sources such as single- phase, two-phase, three-phase (L-N) and three-phase (L-L). Depending on the nominal voltage of the ac supply (120V or 240V), the power systems are equipped with either APU48 or APR48 rectifiers. Fused ac sockets (one per rectifier) are available for connecting the power system to the ac supply.

Output: Eight floating dc outlets are available for connecting equipment power cables to the APS dc power system. Each dc outlet is protected by a corresponding 6A or 25A load circuit breaker. Any combination of 6A or 25A rated load circuit breakers (up to a maximum of eight) can be fitted, depending on customer requirements.

Battery Option: External VRLA 48V batteries can be connected to APS3-059, APS3-061 and APS6-059 dc power systems to provide backup power during ac outages. The battery float voltage is temperature compensated.

Access Power Rectifiers

There are three status indicator LEDs on the Access Power Rectifier front panel (Power On, Urgent Alarm and Non-Urgent Alarm).

Two types of fan-cooled, hot-pluggable Access Power Rectifiers are available:

APU48 – 48 V, 720 W, 120 - 240 V ac

APR48 – 48 V, 1500 W, 208 - 240 V ac

SM45 Supervisory Module

The SM45 supervisory module is an advanced control and monitoring solution for Access Power Solutions (APS) dc power systems. It provides a full suite of advanced communications options, including built-in Ethernet interface, Web server and SNMP agent. Alarm notifications may be by SNMP traps. The SM45 has an onboard audible indicator and two alarm LEDs.

Copyright © 2006-2009 Eaton Corporation. All Rights Reserved.

5

10640205 February 2009

 

Image 5
Contents Data Power Solutions Quick Start Guide Data Power Solutions Quick Start Guide Contents For Further Information and Technical Assistance Worldwide SupportAccess Power Rectifiers APS3 and APS6 Series 48V DC Power SystemsGeneral Description SM45 Supervisory ModuleInputs Pre-InstallationLow Voltage Disconnect if applicable Data Power Solutions Quick Start Guide Wechselspannungs-Eingänge Entrées Alimentation SecteurOutputs Equipment ClassificationIngressi C.A Entradas CARectifiers Batteries if applicableGleichrichter RedresseursRaddrizzatori RectificadoresEntretien Location and EnvironmentServicing Wartung EMC ComplianceManutenzione ReparacionesMounting the APS DC Power System Location and Environment InstallationInspecting the Equipment and Reporting Damage Important Notes for Rack Mounted SystemsWichtige Hinweise für Anlagen mit Schrankmontage Remarques importantes pour les systèmes montés dans un rackClearance Requirements Connecting the DC Load CablesDC Load Cable Specifications Page Strip cable ends Fit load cable clampsFit cable and sleeves Terminate cablesBattery Sizing Installing the External Batteries if applicableBattery Location Arrange sleeves and tighten clamp screwsBattery Fault Protection Batterieschutz Protection en cas de défaut de la batterieBefore You Start Battery Cable SpecificationsPrepare cable clamp Strip cable and fit sleeveRepeat for other battery cables if required Arrange sleeve and clamp the battery cablesTerminate cable Remove knockout and fit coverMounting the Battery Temperature Sensor Connecting the Battery Temperature Sensor CableConnecting the APS DC Power System to the AC Supply AC Supply RequirementsInserting the Access Power Rectifiers AC InstallationPre-Power-Up Check CommissioningApplying DC Power to the Load Applying AC PowerConfiguring the APS DC Power System for Operation Battery Input Circuit Breakers Output Circuit Breaker Field Replacement and RepairUL Listed Mark Desktop variants APS3-060 & APS3-061System Input SpecificationsSystem Output EnvironmentRectifiers Dimensions H, W, DWeight