Eaton Electrical APR48, 10640205 Fit load cable clamps, Strip cable ends, Fit cable and sleeves

Page 18

Data Power Solutions Quick Start Guide

Step 1- Fit load cable clamps

• Insert the square ends of the load cable clamps into the holes in the back of the system.

• Engage two turns of each retaining screw. This will ensure that the clamp does not move when the wires and sleeves are inserted.

Fit all clamps even if you do not use them all. Tighten unused clamps to prevent access to the dc outputs.

Step 2 – Strip cable ends

Strip approximately 10mm (3/8”) from the cable ends. We recommend fitting cable ferrules over the cable ends.

Step 3 – Fit cable and sleeves

To maintain safety approvals insert only the following numbers of cables per clamp, with sleeves where applicable. This will ensure that cables are retained correctly in their clamps.

Feed the cables through the clamps as follows, depending on cable size.

1mm2 (18 AWG) – 2 cable pairs* per clamp:

4mm2 (12 AWG) – 1 or 2 cable pairs per clamp.

2 x 5mm sleeves

10mm sleeve

*If only one cable pair is required then use a dummy pair with sleeves to make up the space.

Step 4 – Terminate cables

Terminate the negative load cable(s) at the (-) terminal block(s) of the dc outlet(s).

Terminate the positive load cable(s) at the (+) terminal block(s) of the dc outlet(s).

Tighten the terminal screws. Required torque: 0.4 – 0.6 Nm (3.5 – 5.3 lb-in).

Ensure that the polarity at the dc outlet(s) matches the power input polarity of your equipment. Connecting reverse polarity equipment power cables to the dc outlets of a power system might cause damage to your equipment. Such damage is not covered by our warranty.

Ensure that the correct cable sizes have been used (1mm2/18 AWG for 6 A outlets and 4mm2/12 AWG for 25 A outlets).

18

Copyright © 2006-2009 Eaton Corporation. All Rights Reserved.

10640205 February 2009

 

Image 18
Contents Data Power Solutions Quick Start Guide Data Power Solutions Quick Start Guide Contents Worldwide Support For Further Information and Technical AssistanceGeneral Description APS3 and APS6 Series 48V DC Power SystemsAccess Power Rectifiers SM45 Supervisory ModulePre-Installation Low Voltage Disconnect if applicableInputs Data Power Solutions Quick Start Guide Entrées Alimentation Secteur Wechselspannungs-EingängeIngressi C.A Equipment ClassificationOutputs Entradas CABatteries if applicable RectifiersRaddrizzatori RedresseursGleichrichter RectificadoresLocation and Environment ServicingEntretien Manutenzione EMC ComplianceWartung ReparacionesInspecting the Equipment and Reporting Damage InstallationMounting the APS DC Power System Location and Environment Important Notes for Rack Mounted SystemsRemarques importantes pour les systèmes montés dans un rack Wichtige Hinweise für Anlagen mit SchrankmontageConnecting the DC Load Cables DC Load Cable SpecificationsClearance Requirements Page Fit cable and sleeves Fit load cable clampsStrip cable ends Terminate cablesBattery Location Installing the External Batteries if applicableBattery Sizing Arrange sleeves and tighten clamp screwsBattery Fault Protection Protection en cas de défaut de la batterie BatterieschutzPrepare cable clamp Battery Cable SpecificationsBefore You Start Strip cable and fit sleeveTerminate cable Arrange sleeve and clamp the battery cablesRepeat for other battery cables if required Remove knockout and fit coverConnecting the APS DC Power System to the AC Supply Connecting the Battery Temperature Sensor CableMounting the Battery Temperature Sensor AC Supply RequirementsPre-Power-Up Check AC InstallationInserting the Access Power Rectifiers CommissioningApplying AC Power Configuring the APS DC Power System for OperationApplying DC Power to the Load UL Listed Mark Output Circuit Breaker Field Replacement and RepairBattery Input Circuit Breakers Desktop variants APS3-060 & APS3-061System Output SpecificationsSystem Input EnvironmentDimensions H, W, D WeightRectifiers