Data Power Solutions Quick Start Guide

Batteries (if applicable)

Always install the batteries according to the relevant battery manufacturer’s instructions.

Batteries are powerful sources of energy and present a potential electrical shock and energy hazard. The energy hazard is always present, even if the batteries are not connected. Avoid short circuiting terminals of opposite polarity.

Batteries are heavy, awkward to handle and can cause personal injury. To prevent back injury, use correct lifting and bending techniques when moving batteries. If the batteries are too heavy to move, request assistance.

Remove or cover rings, wristwatch and other metal jewelry that might be exposed to battery terminals, before installing batteries.

Do not wear synthetic clothing when installing batteries.

Always use insulated tools.

Only use a clean soft damp cloth for cleaning the batteries. Do not use cleaning detergents or chemicals.

When unpacking the batteries inspect them carefully for leaks, corrosion and possible damage. Report any damage or other battery related problems immediately to your battery supplier.

Do not remove the factory-fitted transit insulation covers from the batteries until access to the battery terminals is required.

Do not place tools, loose cables or metal objects (such as interconnecting bars) on top of batteries.

Do not drop tools, loose cables or metal objects onto intercell connections or terminals of opposite polarity.

Only terminate cables and interconnecting bars after confirming that the termination will not create a short circuit.

Always tighten the battery terminal bolts according to the battery manufacturer’s specification. Failing to do so can cause erratic battery performance, possible damage to the battery, and/or personal injury.

Always ensure that any shrouding supplied with the batteries is correctly fitted to cable connectors.

Rectifiers

To reduce the risk of electric shock and maintain optimum system cooling, always cover empty rectifier slots with blanking panels (Part Number: IPN 621-05722-63A).

To avoid electrical shock, do not place hands inside the rectifier shelf.

Rectifier cases may exceed 100ºC (212ºF), especially after prolonged operation. Use suitable gloves to remove the hot rectifier.

Do not attempt to disassemble rectifiers. Return them, (in their original packaging) along with the completed Equipment Incident Report, to your local Eaton dc product representative for replacement or repair.

整流器

为了降低触电风险并保持系统最佳冷却,始终应把整流器盲板(编号:IPN 621-05722-63A) 安装到未安装整流器的空位上。

为了避免触电,不要把手伸到整流器架内。

整流器外壳温度可能会超过100ºC,特别是在长期运行之后。拆取发热整流器时, 应戴上合适的手套。

不要尝试拆卸整流器。如果需要更换或修理,应把整流器按照原样打包, 连同完整的设备故障报告一起,回给当地Eaton直流产品办事处。

10

Copyright © 2006-2009 Eaton Corporation. All Rights Reserved.

10640205 February 2009

 

Image 10
Contents Data Power Solutions Quick Start Guide Data Power Solutions Quick Start Guide Contents Worldwide Support For Further Information and Technical AssistanceGeneral Description APS3 and APS6 Series 48V DC Power SystemsAccess Power Rectifiers SM45 Supervisory ModuleLow Voltage Disconnect if applicable Pre-InstallationInputs Data Power Solutions Quick Start Guide Entrées Alimentation Secteur Wechselspannungs-EingängeIngressi C.A Equipment ClassificationOutputs Entradas CABatteries if applicable RectifiersRaddrizzatori RedresseursGleichrichter RectificadoresServicing Location and EnvironmentEntretien Manutenzione EMC ComplianceWartung ReparacionesInspecting the Equipment and Reporting Damage InstallationMounting the APS DC Power System Location and Environment Important Notes for Rack Mounted SystemsRemarques importantes pour les systèmes montés dans un rack Wichtige Hinweise für Anlagen mit SchrankmontageDC Load Cable Specifications Connecting the DC Load CablesClearance Requirements Page Fit cable and sleeves Fit load cable clampsStrip cable ends Terminate cablesBattery Location Installing the External Batteries if applicableBattery Sizing Arrange sleeves and tighten clamp screwsBattery Fault Protection Protection en cas de défaut de la batterie BatterieschutzPrepare cable clamp Battery Cable SpecificationsBefore You Start Strip cable and fit sleeveTerminate cable Arrange sleeve and clamp the battery cablesRepeat for other battery cables if required Remove knockout and fit coverConnecting the APS DC Power System to the AC Supply Connecting the Battery Temperature Sensor CableMounting the Battery Temperature Sensor AC Supply RequirementsPre-Power-Up Check AC InstallationInserting the Access Power Rectifiers CommissioningConfiguring the APS DC Power System for Operation Applying AC PowerApplying DC Power to the Load UL Listed Mark Output Circuit Breaker Field Replacement and RepairBattery Input Circuit Breakers Desktop variants APS3-060 & APS3-061System Output SpecificationsSystem Input EnvironmentWeight Dimensions H, W, DRectifiers