Eaton Electrical APR48, 10640205 quick start Battery Fault Protection

Page 20

Data Power Solutions Quick Start Guide

Battery Fault Protection

A fault protection device (such as a circuit breaker or fuse) must be fitted in series with one of the battery cables of each battery string.

The fault protection device must be:

Located as close as practical to the corresponding battery string output terminal, and

Capable of disconnecting the potential fault current of the battery string.

The battery circuit breaker(s) of the power system can not be considered as the fault protection device for the battery string(s) and associated wiring.

The interrupt rating of the battery circuit breaker(s) fitted within the power systems is 10kA. Therefore, the maximum potential short-circuit current of a 48V battery string must be

limited to less than 10kA or the total internal impedance of the battery string should be greater than 5.7mΩ.

If a smaller rated external fault protection device is used, then batteries with appropriate internal impedance need to be selected.

电池故障保护

故障保护装置(例如:断路器或保险丝)必须串接在每组电池的一条电缆上。

故障保护设备必须:

尽量接近相应的电池组输出终端,并且

能够断开电池组的潜在故障电流。

不能把电源系统电池电路断路器认为是电池组和相关引线的故障保护装置。

不能把电源系统电池断路器认为是电池组和相关引线的故障保护装置。 电源系统内电池断路器的分断能力额定值是10 kA。 因此,48V

电池组的最大潜在短路电流必须限制到小于10kA, 或者,电池组的内阻必须大于5.7毫欧。

如果使用较低额定值的外部故障保护装置,则必须选择内阻合适的电池。

20

Copyright © 2006-2009 Eaton Corporation. All Rights Reserved.

10640205 February 2009

 

Image 20
Contents Data Power Solutions Quick Start Guide Data Power Solutions Quick Start Guide Contents Worldwide Support For Further Information and Technical AssistanceAPS3 and APS6 Series 48V DC Power Systems Access Power RectifiersGeneral Description SM45 Supervisory ModuleInputs Pre-InstallationLow Voltage Disconnect if applicable Data Power Solutions Quick Start Guide Entrées Alimentation Secteur Wechselspannungs-EingängeEquipment Classification OutputsIngressi C.A Entradas CABatteries if applicable RectifiersRedresseurs GleichrichterRaddrizzatori RectificadoresEntretien Location and EnvironmentServicing EMC Compliance WartungManutenzione ReparacionesInstallation Mounting the APS DC Power System Location and EnvironmentInspecting the Equipment and Reporting Damage Important Notes for Rack Mounted SystemsRemarques importantes pour les systèmes montés dans un rack Wichtige Hinweise für Anlagen mit SchrankmontageClearance Requirements Connecting the DC Load CablesDC Load Cable Specifications Page Fit load cable clamps Strip cable endsFit cable and sleeves Terminate cablesInstalling the External Batteries if applicable Battery SizingBattery Location Arrange sleeves and tighten clamp screwsBattery Fault Protection Protection en cas de défaut de la batterie BatterieschutzBattery Cable Specifications Before You StartPrepare cable clamp Strip cable and fit sleeveArrange sleeve and clamp the battery cables Repeat for other battery cables if requiredTerminate cable Remove knockout and fit coverConnecting the Battery Temperature Sensor Cable Mounting the Battery Temperature SensorConnecting the APS DC Power System to the AC Supply AC Supply RequirementsAC Installation Inserting the Access Power RectifiersPre-Power-Up Check CommissioningApplying DC Power to the Load Applying AC PowerConfiguring the APS DC Power System for Operation Output Circuit Breaker Field Replacement and Repair Battery Input Circuit BreakersUL Listed Mark Desktop variants APS3-060 & APS3-061Specifications System InputSystem Output EnvironmentRectifiers Dimensions H, W, DWeight