DynaView Interface
Table 2 - Circuit Level Operating Modes:
Circuit Level Mode
Top Level Mode | Description |
|
|
Stopped | The circuit is not running, and cannot run without |
| intervention. |
|
|
Stopped Sub Modes | Description |
|
|
Diagnostic Shutdown - Manual Reset | The circuit has been shutdown on a latching diagnostic. |
|
|
Front Panel Circuit Lockout | The circuit is manually locked out by the circuit lockout setting |
| - the nonvolatile lockout setting is accessible through either |
| the DynaView or TechView. |
|
|
|
|
Circuit Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Run Inhibit | The given circuit is currently being inhibited from starting (and |
| running), but may be allowed to start if the inhibiting or |
| diagnostic condition is cleared. |
|
|
Run Inhibit Sub Modes | Description |
|
|
Diagnostic Shutdown - Auto Reset | The circuit has been shutdown on a diagnostic that may clear |
| automatically. |
|
|
Condenser Pressure Limit | The circuit is being inhibited from starting due to high |
| condenser pressure. |
|
|
|
|
Circuit Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Auto | The circuit is not currently running but can be expected to |
| start at any moment given that the proper conditions are |
| satisfied. |
|
|
Auto Sub Modes | Description |
|
|
| No Circuit |
|
|
|
|
Circuit Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Waiting to Start | The chiller is going through the necessary steps to allow the |
| lead circuit to start. |
|
|
Waiting to Start Sub Modes | Description |
|
|
| No Circuit |
|
|
|
|
Circuit Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Running | The compressor on the given circuit is currently running. |
|
|
Running Sub Modes | Description |
|
|
| No Circuit |
|
|
14 |