Trane CCUN 205-211, CGAN 209-214, CH530, CGWN 205-211 manual Diagnostics Screen, Chiller Mode Stopped

Page 20

DynaView Interface

Diagnostics Screen

The diagnostic screen is accessible by depressing the Alarms enunciator A scrollable list of the last (up to 20) active diagnostics will be presented.

Performing a Reset All Active Diagnostics will reset all active diagnostics regardless of type, machine or refrigerant circuit. Compressor diagnostics, which hold off only one compressor, will be treated as circuit diagnostics, consistent with the circuit to which they belong.

The scrollable list will be sorted by time of occurrence. If a diagnostic of severity = warning is present, the "Alarms" key will be present but not flashing. If a diagnostic of severity = shutdown (normal or immediate) is present, the "Alarm" key will display that is flashing. If no diagnostics exist, the "Alarm" key will not be present.

The "Operating Mode At Last Diagnostic" text above the most recent diagnostic will display a sub- screen listing the operating mode and submodes at the time of the last diagnostic.

Figure 8 - Diagnostics screen

 

 

Main

Reports

Settings

 

 

Reset Diags

Chiller Mode:

 

Stopped

[01]8:32 AM Nov 16, 2001 Comm Loss: Emergency Stop

[02]8:29 AM Nov 16, 2001 MP: Reset Has Occurred

Auto Stop Alarms

20

CG-SVU02B-E4

Image 20
Contents User Guide Safety recommendations General informationForeword ReceptionTraining WarrantyMaintenance contract Contents Overview Controls InterfaceDynaView Interface Display ScreensKeypad/Display Lockout Feature KeypadMain Reports Settings Main ScreensAuto Stop Chiller Level Mode Top Level Mode Description MP Resetting MP Resetting Sub Modes DescriptionChiller Level Mode Top Level Mode Description Stopped Stopped Sub Modes DescriptionChiller Level Mode Top Level Mode Description Run Inhibit Chiller Level Mode Top Level Mode Description AutoRun Inhibit Sub Modes Description Auto Sub Modes DescriptionChiller Level Mode Top Level Mode Description Running Chiller Level Mode Top Level Mode Description Running LimitWaiting to Start Sub Modes Description Running Sub Modes DescriptionChiller Level Mode Top Level Mode Description Shutting Down Chiller Level Mode Top Level Mode Description MiscShutting Down Sub Modes Description Misc. Sub Modes DescriptionCircuit Level Operating Modes Circuit Level Mode Top Level Mode Description Running Limit Circuit Level Mode Top Level Mode Description Shutting DownCircuit Level Mode Top Level Mode Description Misc Preparing Shutdown Sub Modes DescriptionReports Screen Circuit Ashrae Log Historic DiagnosticsAshrae Chiller Log Settings Screen Description Units Resolution, Default ChillerFeature Settings System Manual Control SettingsCircuit Manual Control Settings Display SettingsDiagnostics Screen Chiller Mode StoppedTechView Interface CD-ROMSoftware Download TechView Interface Diagnostics Active Diagnostic Name Effects Severity Modes Criteria Reset Inactive Level MP Reset Has OccurredCompressor Fault Low Pressure CutoutSuction Temperature Sensor TemperatureEvaporator Entering Water Temp Sensor Evaporator Leaving WaterError High Evaporator WaterHigh Pressure Cutout Emergency StopFault Detected Pump Fault DetectedPump 1 or Fan Fault Evaporator WaterDiagnostic Name Effects Severity Active Criteria Reset Modes Level InactiveDiagnostics Special Main Processor Boot Messages and Diagnostics DynaView Display Message Description TroubleshootingDiagnostics Event/state Description Programmable Relays Alarms and StatusDefault setting Event/Status CG-SVU02B-E4 CG-SVU02B-E4