Trane CH530, CCUN 205-211 manual Programmable Relays Alarms and Status, Event/state Description

Page 34

Diagnostics

Programmable Relays (Alarms and Status)

CH530 provides a flexible alarm or chiller status indication to a remote location through a hard wired interface to a dry contact closure.

Four relays are available for this function, and they are provided (generally with a Quad Relay Output LLID) as part of the Alarm Relay Output Option.

The events/states that can be assigned to the programmable relays are listed in the following table and through a TechView configuration.

Table 8 - Chiller events/status descriptions

Event/state

Description

Alarm - Latching

This output is true whenever there is any active diagnostic that requires a manual reset to clear, that affects the chiller, the

 

circuit, or any of the compressors on a circuit. This classification does not include informational diagnostics.

 

 

Alarm - Auto reset

This output is true whenever there is any active diagnostic that could automatically clear that affects the chiller, the circuit or

 

any of the compressors on a circuit. This classification does not include informational diagnostics. If all of the auto resetting

 

diagnostics were to clear, this output would return to a false condition.

 

 

Alarm

This output is true whenever there is any diagnostic affecting any component, whether latching or automatically clearing. This

 

classification does not include informational diagnostics.

 

 

Warning

This output is true whenever there is any informational diagnostic affecting any component, whether latching or automatically

 

clearing.

 

 

Chiller Limit Mode

This output is true whenever the chiller has been running in one of the Unloading types of limit modes (Condenser,

 

Evaporator, Current Limit or Phase Imbalance Limit) continuously for the last 20 minutes. A given limit or overlapping of

 

different limits must be in effect continuously for 20 minutes prior to the output becoming true. It will become false, if no

 

Unload limits are present for 1 minute. The filter prevents short duration or transient repetitive limits from indicating. The

 

chiller is considered to be in a limit mode for the purposes of front panel display and annunciation, on if it is fully inhibiting

 

loading by virtue of being in either the "hold" or "forced unload" regions of the limit control, excluding the "limited loading

 

region". In previous designs, the "limit load" region of the limit control was included in the criteria for the limit mode call out

 

on the front panel and annunciation outputs.

Compressor Running

The output is true whenever any compressors are started or running on the chiller and false when no compressors are either

 

starting or running on the chiller. This status may or may not reflect the true status of the compressor in Service Pumpdown

 

if such a mode exists for a particular chiller.

 

 

Maximum Capacity

The output is true whenever the chiller has reached maximum capacity continuously for the Max Capacity Relay debounce

 

time. The output is false when the chiller does not have all its available compressors running continuously for the debounce

 

time.

 

 

Table 9 - Default settings

Default setting

Event/Status

 

 

Output relay 1

Compressor running

 

 

Output relay 2

Latching alarm

 

 

Output relay 3

Chiller limit mode

 

 

Output relay 4

Warnings

 

 

34

CG-SVU02B-E4

Image 34
Contents User Guide Foreword Safety recommendationsGeneral information ReceptionMaintenance contract WarrantyTraining Contents Overview Controls InterfaceDynaView Interface Display ScreensKeypad/Display Lockout Feature KeypadMain Reports Settings Main ScreensAuto Stop Chiller Level Mode Top Level Mode Description Stopped Chiller Level Mode Top Level Mode Description MP ResettingMP Resetting Sub Modes Description Stopped Sub Modes DescriptionRun Inhibit Sub Modes Description Chiller Level Mode Top Level Mode Description Run InhibitChiller Level Mode Top Level Mode Description Auto Auto Sub Modes DescriptionWaiting to Start Sub Modes Description Chiller Level Mode Top Level Mode Description RunningChiller Level Mode Top Level Mode Description Running Limit Running Sub Modes DescriptionShutting Down Sub Modes Description Chiller Level Mode Top Level Mode Description Shutting DownChiller Level Mode Top Level Mode Description Misc Misc. Sub Modes DescriptionCircuit Level Operating Modes Circuit Level Mode Top Level Mode Description Misc Circuit Level Mode Top Level Mode Description Running LimitCircuit Level Mode Top Level Mode Description Shutting Down Preparing Shutdown Sub Modes DescriptionReports Screen Ashrae Chiller Log Historic DiagnosticsCircuit Ashrae Log Settings Screen Description Units Resolution, Default ChillerCircuit Manual Control Settings Feature SettingsSystem Manual Control Settings Display SettingsDiagnostics Screen Chiller Mode StoppedTechView Interface CD-ROMSoftware Download TechView Interface Diagnostics Compressor Fault Active Diagnostic Name Effects SeverityModes Criteria Reset Inactive Level MP Reset Has Occurred Low Pressure CutoutEvaporator Entering Water Suction Temperature SensorTemperature Temp Sensor Evaporator Leaving WaterHigh Pressure Cutout ErrorHigh Evaporator Water Emergency StopPump 1 or Fan Fault Fault DetectedPump Fault Detected Evaporator WaterDiagnostic Name Effects Severity Active Criteria Reset Modes Level InactiveDiagnostics Special Main Processor Boot Messages and Diagnostics DynaView Display Message Description TroubleshootingDiagnostics Default setting Event/Status Programmable Relays Alarms and StatusEvent/state Description CG-SVU02B-E4 CG-SVU02B-E4