Diagnostics
Table 5 - Main Processor Diagnostics
|
|
|
| Active |
|
| |
Diagnostic Name | Effects | Severity | Persistence | Modes | Criteria | Reset | |
[Inactive | Level | ||||||
|
|
|
|
| |||
|
|
|
| Modes] |
|
| |
|
|
|
|
|
|
| |
MP: Reset Has Occurred | Chiller | Warning | NonLatch | All | The main processor has successfully come out of a reset and | NA | |
|
|
|
|
| built its application. A reset may have been due to a power up, |
| |
|
|
|
|
| installing new software or configuration. This diagnostic is |
| |
|
|
|
|
| immediately and automatically cleared and thus can only be |
| |
|
|
|
|
| seen in the historic diagnostic list. |
| |
|
|
|
|
|
|
| |
Low Pressure Cutout | Circuit | Immediate | Latch | Starting and | The suction refrigerant pressure (gauge) fell below the given | Local | |
|
|
|
| Running | threshold for the refrigerant installed: |
| |
|
|
|
| [Stop, See | • 0.7 bar for R22 and R407c |
| |
|
|
|
| criteria] | • 0.3 bar for R134a |
| |
|
|
|
|
| • 1.0 bar for R410a |
| |
|
|
|
|
|
|
| |
High Motor Temp/Overload | Cprsr | Immediate | Latch | All | • The High Motor Temperature or the Compressor Overload | Local | |
|
|
|
|
| switch remained open for more than 35 minutes. |
| |
|
|
|
|
| • Five compressor fault diagnostics have occurred within the |
| |
|
|
|
|
| last 210 minutes. |
| |
|
|
|
|
|
|
| |
Compressor Fault | Cprsr | Immediate | NonLatch | All | The High Motor Temperature or the Compressor Overload | Local | |
|
|
|
|
| switch input is open. |
| |
|
|
|
|
|
|
| |
BAS Failed to Establish | Chiller | Special | NonLatch | At | The BAS was setup as "installed" and the BAS did not | Remote | |
Communication |
|
|
|
| communicate with the MP within 15 minutes after |
| |
|
|
|
|
|
|
| |
BAS Communication Lost | Chiller | Special | NonLatch | All | The BAS was setup as "installed" at the MP and the Comm | Remote | |
|
|
|
|
| 3 LLID lost communications with the BAS for 15 continuous |
| |
|
|
|
|
| minutes after it had been established. The chiller follows the |
| |
|
|
|
|
| value of the Tracer Default Run Command which can be |
| |
|
|
|
|
| previously written by Tracer and stored nonvolatilely by the MP |
| |
|
|
|
|
| (either use local or shutdown). |
| |
|
|
|
|
|
|
| |
External Chilled/Hot Water | Chiller | Warning | NonLatch | All | a. Function Not "Enabled": no diagnostics. | Remote | |
Setpoint |
|
|
|
| b. "Enabled ": |
| |
|
|
|
|
| diagnostic, default CWS/HWS to next level of priority (e.g. |
| |
|
|
|
|
| Front Panel SetPoint). This Warning diagnostic will automatically |
| |
|
|
|
|
| reset if the input returns to the normal range. |
| |
|
|
|
|
|
|
| |
External Demand Limit | Chiller | Warning | NonLatch | All | a. Function Not "Enabled": no diagnostics. | Remote | |
Setpoint |
|
|
|
| b. "Enabled ": |
| |
|
|
|
|
| diagnostic, default DLS to next level of priority (e.g. Front Panel |
| |
|
|
|
|
| SetPoint). This Warning diagnostic will automatically reset if the |
| |
|
|
|
|
| input returns to the normal range. |
| |
|
|
|
|
|
|
| |
Circuit Pumpdown | Circuit | Warning | Latch | Operational/ | Going below the low pressure setting + 0.2 bar shall terminate | Remote | |
Terminated |
|
|
| Service | Service Pumpdown. This indicates that the suction pressure of |
| |
|
|
|
| Pumpdown | circuit 1 or 2 did not go below the low pressure setting + 0.2 |
| |
|
|
|
| [All Except | bar within 1 minute from the start of Service Pumpdown. |
| |
|
|
|
| Operational |
|
| |
|
|
|
| and Service |
|
| |
|
|
|
| Pumpdown] |
|
| |
|
|
|
|
|
|
| |
Chilled Water Flow (Entering | Chiller | Immediate | Latch | Any Ckt(s) | The entering evaporator water temperature fell below the | Remote | |
Water Temp) |
|
|
| Energized | leaving evaporator water temperature by more than 1.7°C for |
| |
|
|
|
| [No Ckt(s) | 37°C sec while at least 1 compressor was running. |
| |
|
|
|
| Energized] |
|
| |
|
|
|
|
|
|
|
25 |