Trane CGAN 209-214 Active Diagnostic Name Effects Severity, Low Pressure Cutout, Compressor Fault

Page 25

Diagnostics

Table 5 - Main Processor Diagnostics

 

 

 

 

Active

 

 

Diagnostic Name

Effects

Severity

Persistence

Modes

Criteria

Reset

[Inactive

Level

 

 

 

 

 

 

 

 

 

Modes]

 

 

 

 

 

 

 

 

 

MP: Reset Has Occurred

Chiller

Warning

NonLatch

All

The main processor has successfully come out of a reset and

NA

 

 

 

 

 

built its application. A reset may have been due to a power up,

 

 

 

 

 

 

installing new software or configuration. This diagnostic is

 

 

 

 

 

 

immediately and automatically cleared and thus can only be

 

 

 

 

 

 

seen in the historic diagnostic list.

 

 

 

 

 

 

 

 

Low Pressure Cutout

Circuit

Immediate

Latch

Starting and

The suction refrigerant pressure (gauge) fell below the given

Local

 

 

 

 

Running

threshold for the refrigerant installed:

 

 

 

 

 

[Stop, See

• 0.7 bar for R22 and R407c

 

 

 

 

 

criteria]

• 0.3 bar for R134a

 

 

 

 

 

 

• 1.0 bar for R410a

 

 

 

 

 

 

 

 

High Motor Temp/Overload

Cprsr

Immediate

Latch

All

• The High Motor Temperature or the Compressor Overload

Local

 

 

 

 

 

switch remained open for more than 35 minutes.

 

 

 

 

 

 

• Five compressor fault diagnostics have occurred within the

 

 

 

 

 

 

last 210 minutes.

 

 

 

 

 

 

 

 

Compressor Fault

Cprsr

Immediate

NonLatch

All

The High Motor Temperature or the Compressor Overload

Local

 

 

 

 

 

switch input is open.

 

 

 

 

 

 

 

 

BAS Failed to Establish

Chiller

Special

NonLatch

At power-up

The BAS was setup as "installed" and the BAS did not

Remote

Communication

 

 

 

 

communicate with the MP within 15 minutes after power-up.

 

 

 

 

 

 

 

 

BAS Communication Lost

Chiller

Special

NonLatch

All

The BAS was setup as "installed" at the MP and the Comm

Remote

 

 

 

 

 

3 LLID lost communications with the BAS for 15 continuous

 

 

 

 

 

 

minutes after it had been established. The chiller follows the

 

 

 

 

 

 

value of the Tracer Default Run Command which can be

 

 

 

 

 

 

previously written by Tracer and stored nonvolatilely by the MP

 

 

 

 

 

 

(either use local or shutdown).

 

 

 

 

 

 

 

 

External Chilled/Hot Water

Chiller

Warning

NonLatch

All

a. Function Not "Enabled": no diagnostics.

Remote

Setpoint

 

 

 

 

b. "Enabled ": Out-Of-Range Low or Hi or bad LLID, set

 

 

 

 

 

 

diagnostic, default CWS/HWS to next level of priority (e.g.

 

 

 

 

 

 

Front Panel SetPoint). This Warning diagnostic will automatically

 

 

 

 

 

 

reset if the input returns to the normal range.

 

 

 

 

 

 

 

 

External Demand Limit

Chiller

Warning

NonLatch

All

a. Function Not "Enabled": no diagnostics.

Remote

Setpoint

 

 

 

 

b. "Enabled ": Out-Of-Range Low or Hi or bad LLID, set

 

 

 

 

 

 

diagnostic, default DLS to next level of priority (e.g. Front Panel

 

 

 

 

 

 

SetPoint). This Warning diagnostic will automatically reset if the

 

 

 

 

 

 

input returns to the normal range.

 

 

 

 

 

 

 

 

Circuit Pumpdown

Circuit

Warning

Latch

Operational/

Going below the low pressure setting + 0.2 bar shall terminate

Remote

Terminated

 

 

 

Service

Service Pumpdown. This indicates that the suction pressure of

 

 

 

 

 

Pumpdown

circuit 1 or 2 did not go below the low pressure setting + 0.2

 

 

 

 

 

[All Except

bar within 1 minute from the start of Service Pumpdown.

 

 

 

 

 

Operational

 

 

 

 

 

 

and Service

 

 

 

 

 

 

Pumpdown]

 

 

 

 

 

 

 

 

 

Chilled Water Flow (Entering

Chiller

Immediate

Latch

Any Ckt(s)

The entering evaporator water temperature fell below the

Remote

Water Temp)

 

 

 

Energized

leaving evaporator water temperature by more than 1.7°C for

 

 

 

 

 

[No Ckt(s)

37°C sec while at least 1 compressor was running.

 

 

 

 

 

Energized]

 

 

 

 

 

 

 

 

 

CG-SVU02B-E4

25

Image 25
Contents User Guide General information Safety recommendationsForeword ReceptionMaintenance contract WarrantyTraining Contents Controls Interface OverviewDisplay Screens DynaView InterfaceKeypad Keypad/Display Lockout FeatureMain Screens Main Reports SettingsAuto Stop MP Resetting Sub Modes Description Chiller Level Mode Top Level Mode Description MP ResettingChiller Level Mode Top Level Mode Description Stopped Stopped Sub Modes DescriptionChiller Level Mode Top Level Mode Description Auto Chiller Level Mode Top Level Mode Description Run InhibitRun Inhibit Sub Modes Description Auto Sub Modes DescriptionChiller Level Mode Top Level Mode Description Running Limit Chiller Level Mode Top Level Mode Description RunningWaiting to Start Sub Modes Description Running Sub Modes DescriptionChiller Level Mode Top Level Mode Description Misc Chiller Level Mode Top Level Mode Description Shutting DownShutting Down Sub Modes Description Misc. Sub Modes DescriptionCircuit Level Operating Modes Circuit Level Mode Top Level Mode Description Shutting Down Circuit Level Mode Top Level Mode Description Running LimitCircuit Level Mode Top Level Mode Description Misc Preparing Shutdown Sub Modes DescriptionReports Screen Ashrae Chiller Log Historic DiagnosticsCircuit Ashrae Log Description Units Resolution, Default Chiller Settings ScreenSystem Manual Control Settings Feature SettingsCircuit Manual Control Settings Display SettingsChiller Mode Stopped Diagnostics ScreenCD-ROM TechView InterfaceSoftware Download TechView Interface Diagnostics Modes Criteria Reset Inactive Level MP Reset Has Occurred Active Diagnostic Name Effects SeverityCompressor Fault Low Pressure CutoutTemperature Suction Temperature SensorEvaporator Entering Water Temp Sensor Evaporator Leaving WaterHigh Evaporator Water ErrorHigh Pressure Cutout Emergency StopPump Fault Detected Fault DetectedPump 1 or Fan Fault Evaporator WaterActive Criteria Reset Modes Level Inactive Diagnostic Name Effects SeverityDiagnostics Special DynaView Display Message Description Troubleshooting Main Processor Boot Messages and DiagnosticsDiagnostics Default setting Event/Status Programmable Relays Alarms and StatusEvent/state Description CG-SVU02B-E4 CG-SVU02B-E4