Diagnostics
Evaporator Water | Chiller | Warning and | NonLatch | Evap pump | After flow had been proven the chilled water flow input | Remote |
Flow Lost Pump 1 |
| Special Action |
| commanded on | was open for more than 4 continuous seconds. The |
|
(or Pump 2) |
|
|
|
| evaporator pump control will switch control to the |
|
|
|
|
|
| redundant pump. If redundant pump is not available, |
|
|
|
|
|
| diagnostic will clear when flow is established. |
|
|
|
|
|
|
|
|
Evaporator Water | Chiller | Warning and | NonLatch | Estab. Evap. Water | Evaporator water flow was not proven within a user | Remote |
Flow Overdue |
| Special Action |
| Flow on going from | adjustable time of the evaporator water pump relay being |
|
Pump 1 (or |
|
|
| STOP to AUTO. | energized. Diagnostic is reset with return of evaporator |
|
Pump 2) |
|
|
|
| water flow. |
|
|
|
|
|
|
|
|
Fault Detected: | Chiller | Warning and | NonLatch | All | Detection of a pump fault will cause pump control to | Remote |
Evaporator Water |
| Special Action |
|
| switch to the redundant pump. |
|
Pump 1 (or |
|
|
|
|
|
|
Pump 2) |
|
|
|
|
|
|
|
|
|
|
|
|
|
Condenser Water | Chiller | Warning and | NonLatch | Start and All Run | After flow had been proven the condenser water flow | Remote |
Flow Lost Pump 1 |
| Special Action |
| Modes | input was open for more than 4 continuous seconds. This |
|
(or Pump 2) |
|
|
|
| diagnostic is automatically cleared once all circuits are de- |
|
|
|
|
|
| energized. |
|
|
|
|
|
|
|
|
Condenser Water | Chiller | Warning and | NonLatch | Estab Cond Water | Condenser water flow was not proven within a user | Remote |
Flow Overdue |
| Special Action |
| Flow | adjustable time of the condenser water pump relay being |
|
Pump 1 (or |
|
|
|
| energized. |
|
Pump 2) |
|
|
|
|
|
|
|
|
|
|
|
|
|
Fault Detected: | Chiller | Warning and | NonLatch | All | Detection of a pump fault will cause pump control to | Remote |
Condenser Water |
| Special Action |
|
| switch to the redundant pump. |
|
Pump 1 (or |
|
|
|
|
|
|
Pump 2) |
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan Fault | Circuit | Warning | NonLatch | All | The fan fault input was open for more than 5 seconds. | Local |
|
|
|
|
|
|
|
High Condensing | Chiller | Warning | Latch | Running | When running in parallel pump control, with one pump | Remote |
Pressure Pump |
|
|
|
| on, a high condensing pressure will force add the second |
|
Add |
|
|
|
| pump. It will latch on to prevent pump cycling. |
|
|
|
|
|
|
|
|