Trane CCUN 205-211, CH530 Evaporator Water, Flow Lost Pump, Or Pump, Flow Overdue, Pump 1 or, Add

Page 28

Diagnostics

Evaporator Water

Chiller

Warning and

NonLatch

Evap pump

After flow had been proven the chilled water flow input

Remote

Flow Lost Pump 1

 

Special Action

 

commanded on

was open for more than 4 continuous seconds. The

 

(or Pump 2)

 

 

 

 

evaporator pump control will switch control to the

 

 

 

 

 

 

redundant pump. If redundant pump is not available,

 

 

 

 

 

 

diagnostic will clear when flow is established.

 

 

 

 

 

 

 

 

Evaporator Water

Chiller

Warning and

NonLatch

Estab. Evap. Water

Evaporator water flow was not proven within a user

Remote

Flow Overdue

 

Special Action

 

Flow on going from

adjustable time of the evaporator water pump relay being

 

Pump 1 (or

 

 

 

STOP to AUTO.

energized. Diagnostic is reset with return of evaporator

 

Pump 2)

 

 

 

 

water flow.

 

 

 

 

 

 

 

 

Fault Detected:

Chiller

Warning and

NonLatch

All

Detection of a pump fault will cause pump control to

Remote

Evaporator Water

 

Special Action

 

 

switch to the redundant pump.

 

Pump 1 (or

 

 

 

 

 

 

Pump 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser Water

Chiller

Warning and

NonLatch

Start and All Run

After flow had been proven the condenser water flow

Remote

Flow Lost Pump 1

 

Special Action

 

Modes

input was open for more than 4 continuous seconds. This

 

(or Pump 2)

 

 

 

 

diagnostic is automatically cleared once all circuits are de-

 

 

 

 

 

 

energized.

 

 

 

 

 

 

 

 

Condenser Water

Chiller

Warning and

NonLatch

Estab Cond Water

Condenser water flow was not proven within a user

Remote

Flow Overdue

 

Special Action

 

Flow

adjustable time of the condenser water pump relay being

 

Pump 1 (or

 

 

 

 

energized.

 

Pump 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault Detected:

Chiller

Warning and

NonLatch

All

Detection of a pump fault will cause pump control to

Remote

Condenser Water

 

Special Action

 

 

switch to the redundant pump.

 

Pump 1 (or

 

 

 

 

 

 

Pump 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Fault

Circuit

Warning

NonLatch

All

The fan fault input was open for more than 5 seconds.

Local

 

 

 

 

 

 

 

High Condensing

Chiller

Warning

Latch

Running

When running in parallel pump control, with one pump

Remote

Pressure Pump

 

 

 

 

on, a high condensing pressure will force add the second

 

Add

 

 

 

 

pump. It will latch on to prevent pump cycling.

 

 

 

 

 

 

 

 

28

CG-SVU02B-E4

Image 28
Contents User Guide Safety recommendations General informationForeword ReceptionMaintenance contract WarrantyTraining Contents Overview Controls InterfaceDynaView Interface Display ScreensKeypad/Display Lockout Feature KeypadMain Reports Settings Main ScreensAuto Stop Chiller Level Mode Top Level Mode Description MP Resetting MP Resetting Sub Modes DescriptionChiller Level Mode Top Level Mode Description Stopped Stopped Sub Modes DescriptionChiller Level Mode Top Level Mode Description Run Inhibit Chiller Level Mode Top Level Mode Description AutoRun Inhibit Sub Modes Description Auto Sub Modes DescriptionChiller Level Mode Top Level Mode Description Running Chiller Level Mode Top Level Mode Description Running LimitWaiting to Start Sub Modes Description Running Sub Modes DescriptionChiller Level Mode Top Level Mode Description Shutting Down Chiller Level Mode Top Level Mode Description MiscShutting Down Sub Modes Description Misc. Sub Modes DescriptionCircuit Level Operating Modes Circuit Level Mode Top Level Mode Description Running Limit Circuit Level Mode Top Level Mode Description Shutting DownCircuit Level Mode Top Level Mode Description Misc Preparing Shutdown Sub Modes DescriptionReports Screen Ashrae Chiller Log Historic DiagnosticsCircuit Ashrae Log Settings Screen Description Units Resolution, Default ChillerFeature Settings System Manual Control SettingsCircuit Manual Control Settings Display SettingsDiagnostics Screen Chiller Mode StoppedTechView Interface CD-ROMSoftware Download TechView Interface Diagnostics Active Diagnostic Name Effects Severity Modes Criteria Reset Inactive Level MP Reset Has OccurredCompressor Fault Low Pressure CutoutSuction Temperature Sensor TemperatureEvaporator Entering Water Temp Sensor Evaporator Leaving WaterError High Evaporator WaterHigh Pressure Cutout Emergency StopFault Detected Pump Fault DetectedPump 1 or Fan Fault Evaporator WaterDiagnostic Name Effects Severity Active Criteria Reset Modes Level InactiveDiagnostics Special Main Processor Boot Messages and Diagnostics DynaView Display Message Description TroubleshootingDiagnostics Default setting Event/Status Programmable Relays Alarms and StatusEvent/state Description CG-SVU02B-E4 CG-SVU02B-E4