DynaView Interface
Table 1 - Main screen menu, Chiller Operating Modes - Top Level
Chiller Level Mode
Top Level Mode | Description |
|
|
MP Resetting | The main processor is going through reset. |
|
|
MP Resetting Sub Modes | Description |
|
|
| No Chiller |
|
|
|
|
Chiller Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Stopped | The chiller is not running either circuit, and cannot run without |
| intervention. |
|
|
Stopped Sub Modes | Description |
|
|
Local Stop | Chiller is stopped by the DynaView Stop button command- |
| cannot be remotely overridden. |
|
|
Immediate Stop | Chiller is stopped by the DynaView Immediate Stop (by |
| pressing the Stop then Immediate Stop buttons in |
| succession) - previous shutdown was manually commanded |
| to shutdown immediately. |
|
|
No Circuits Available | The entire chiller is stopped by circuit diagnostics or lockouts |
| that may automatically clear. |
|
|
Diagnostic Shutdown - Manual Reset | The chiller is stopped by a diagnostic that requires manual |
| intervention to reset. |
|
|
10 |