Trane CH530, CCUN 205-211, CGAN 209-214 Chiller Level Mode Top Level Mode Description MP Resetting

Page 10

DynaView Interface

Table 1 - Main screen menu, Chiller Operating Modes - Top Level

Chiller Level Mode

Top Level Mode

Description

 

 

MP Resetting

The main processor is going through reset.

 

 

MP Resetting Sub Modes

Description

 

 

 

No Chiller Sub-Modes

 

 

 

 

Chiller Level Mode

 

 

 

Top Level Mode

Description

 

 

Stopped

The chiller is not running either circuit, and cannot run without

 

intervention.

 

 

Stopped Sub Modes

Description

 

 

Local Stop

Chiller is stopped by the DynaView Stop button command-

 

cannot be remotely overridden.

 

 

Immediate Stop

Chiller is stopped by the DynaView Immediate Stop (by

 

pressing the Stop then Immediate Stop buttons in

 

succession) - previous shutdown was manually commanded

 

to shutdown immediately.

 

 

No Circuits Available

The entire chiller is stopped by circuit diagnostics or lockouts

 

that may automatically clear.

 

 

Diagnostic Shutdown - Manual Reset

The chiller is stopped by a diagnostic that requires manual

 

intervention to reset.

 

 

10

CG-SVU02B-E4

Image 10
Contents User Guide Foreword Safety recommendationsGeneral information ReceptionMaintenance contract WarrantyTraining Contents Overview Controls InterfaceDynaView Interface Display ScreensKeypad/Display Lockout Feature KeypadMain Reports Settings Main ScreensAuto Stop Chiller Level Mode Top Level Mode Description Stopped Chiller Level Mode Top Level Mode Description MP ResettingMP Resetting Sub Modes Description Stopped Sub Modes DescriptionRun Inhibit Sub Modes Description Chiller Level Mode Top Level Mode Description Run InhibitChiller Level Mode Top Level Mode Description Auto Auto Sub Modes DescriptionWaiting to Start Sub Modes Description Chiller Level Mode Top Level Mode Description RunningChiller Level Mode Top Level Mode Description Running Limit Running Sub Modes DescriptionShutting Down Sub Modes Description Chiller Level Mode Top Level Mode Description Shutting DownChiller Level Mode Top Level Mode Description Misc Misc. Sub Modes DescriptionCircuit Level Operating Modes Circuit Level Mode Top Level Mode Description Misc Circuit Level Mode Top Level Mode Description Running LimitCircuit Level Mode Top Level Mode Description Shutting Down Preparing Shutdown Sub Modes DescriptionReports Screen Ashrae Chiller Log Historic DiagnosticsCircuit Ashrae Log Settings Screen Description Units Resolution, Default ChillerCircuit Manual Control Settings Feature SettingsSystem Manual Control Settings Display SettingsDiagnostics Screen Chiller Mode StoppedTechView Interface CD-ROMSoftware Download TechView Interface Diagnostics Compressor Fault Active Diagnostic Name Effects SeverityModes Criteria Reset Inactive Level MP Reset Has Occurred Low Pressure CutoutEvaporator Entering Water Suction Temperature SensorTemperature Temp Sensor Evaporator Leaving WaterHigh Pressure Cutout ErrorHigh Evaporator Water Emergency StopPump 1 or Fan Fault Fault DetectedPump Fault Detected Evaporator WaterDiagnostic Name Effects Severity Active Criteria Reset Modes Level InactiveDiagnostics Special Main Processor Boot Messages and Diagnostics DynaView Display Message Description TroubleshootingDiagnostics Default setting Event/Status Programmable Relays Alarms and StatusEvent/state Description CG-SVU02B-E4 CG-SVU02B-E4