Trane CCUN 205-211, CH530 Waiting to Start Sub Modes Description, Running Sub Modes Description

Page 12

DynaView Interface

Chiller Level Mode

Top Level Mode

Description

 

 

Waiting to Start

The chiller is going through the necessary steps to allow the

 

lead circuit to start.

 

 

Waiting to Start Sub Modes

Description

 

 

Waiting For Condenser Water Flow

The chiller will wait a user adjustable time in this mode for

 

condenser water flow to be established per the flow switch

 

hardwired input.

 

 

 

 

Chiller Level Mode

 

 

 

Top Level Mode

Description

 

 

Running

At least one circuit on the chiller is currently running.

 

 

Running Sub Modes

Description

 

 

Maximum Capacity

The chiller is operating at its maximum capacity.

 

 

Capacity Control Softloading

The control is limiting the chiller loading due to capacity based

 

softloading setpoints.

 

 

Unit is Building Ice

The chiller is Building Ice, and will terminate on the Ice

 

Termination Setpoint based on the Entering Evap Water

 

Temperature sensor.

 

 

 

 

Chiller Level Mode

 

 

 

Top Level Mode

Description

 

 

Running - Limit

At least one circuit on the chiller is currently running, but the

 

operation of the chiller as a whole is being actively limited by

 

the controls. The sub modes that apply to the Running top

 

modes may also be displayed along with the following limit

 

specific modes.

 

 

Running - Limit Sub Modes

Description

 

 

Demand Limit

The number of compressors allowed to operate is being

 

limited to less than the available number of compressors by

 

either the BAS system, the front panel demand limit setpoint

 

or the external demand limit input.

 

 

12

CG-SVU02B-E4

Image 12
Contents User Guide Safety recommendations General informationForeword ReceptionWarranty Maintenance contractTraining Contents Overview Controls InterfaceDynaView Interface Display ScreensKeypad/Display Lockout Feature KeypadMain Reports Settings Main ScreensAuto Stop Chiller Level Mode Top Level Mode Description MP Resetting MP Resetting Sub Modes DescriptionChiller Level Mode Top Level Mode Description Stopped Stopped Sub Modes DescriptionChiller Level Mode Top Level Mode Description Run Inhibit Chiller Level Mode Top Level Mode Description AutoRun Inhibit Sub Modes Description Auto Sub Modes DescriptionChiller Level Mode Top Level Mode Description Running Chiller Level Mode Top Level Mode Description Running LimitWaiting to Start Sub Modes Description Running Sub Modes DescriptionChiller Level Mode Top Level Mode Description Shutting Down Chiller Level Mode Top Level Mode Description MiscShutting Down Sub Modes Description Misc. Sub Modes DescriptionCircuit Level Operating Modes Circuit Level Mode Top Level Mode Description Running Limit Circuit Level Mode Top Level Mode Description Shutting DownCircuit Level Mode Top Level Mode Description Misc Preparing Shutdown Sub Modes DescriptionReports Screen Historic Diagnostics Ashrae Chiller LogCircuit Ashrae Log Settings Screen Description Units Resolution, Default ChillerFeature Settings System Manual Control SettingsCircuit Manual Control Settings Display SettingsDiagnostics Screen Chiller Mode StoppedTechView Interface CD-ROMSoftware Download TechView Interface Diagnostics Active Diagnostic Name Effects Severity Modes Criteria Reset Inactive Level MP Reset Has OccurredCompressor Fault Low Pressure CutoutSuction Temperature Sensor TemperatureEvaporator Entering Water Temp Sensor Evaporator Leaving WaterError High Evaporator WaterHigh Pressure Cutout Emergency StopFault Detected Pump Fault DetectedPump 1 or Fan Fault Evaporator WaterDiagnostic Name Effects Severity Active Criteria Reset Modes Level InactiveDiagnostics Special Main Processor Boot Messages and Diagnostics DynaView Display Message Description TroubleshootingDiagnostics Programmable Relays Alarms and Status Default setting Event/StatusEvent/state Description CG-SVU02B-E4 CG-SVU02B-E4