DynaView Interface
Chiller Level Mode
Top Level Mode | Description |
|
|
Waiting to Start | The chiller is going through the necessary steps to allow the |
| lead circuit to start. |
|
|
Waiting to Start Sub Modes | Description |
|
|
Waiting For Condenser Water Flow | The chiller will wait a user adjustable time in this mode for |
| condenser water flow to be established per the flow switch |
| hardwired input. |
|
|
|
|
Chiller Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Running | At least one circuit on the chiller is currently running. |
|
|
Running Sub Modes | Description |
|
|
Maximum Capacity | The chiller is operating at its maximum capacity. |
|
|
Capacity Control Softloading | The control is limiting the chiller loading due to capacity based |
| softloading setpoints. |
|
|
Unit is Building Ice | The chiller is Building Ice, and will terminate on the Ice |
| Termination Setpoint based on the Entering Evap Water |
| Temperature sensor. |
|
|
|
|
Chiller Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Running - Limit | At least one circuit on the chiller is currently running, but the |
| operation of the chiller as a whole is being actively limited by |
| the controls. The sub modes that apply to the Running top |
| modes may also be displayed along with the following limit |
| specific modes. |
|
|
Running - Limit Sub Modes | Description |
|
|
Demand Limit | The number of compressors allowed to operate is being |
| limited to less than the available number of compressors by |
| either the BAS system, the front panel demand limit setpoint |
| or the external demand limit input. |
|
|
12 |