Diagnostics
Comm Loss: | Circuit | Immediate | Latch | All | Continual loss of communication between the MP and the | Remote |
Suction Pressure Transducer |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Warning | Latch | All | Continual loss of communication between the MP and the | Remote |
Ext Chilled/Hot Wtr Setpoint |
| and Special |
|
| Functional ID has occurred for a |
|
|
| Action |
|
| shall discontinue use of the External Chilled/Hot Water |
|
|
|
|
|
| Setpoint source and revert to the next higher priority for |
|
|
|
|
|
| setpoint arbitration |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Warning | Latch | All | Continual loss of communication between the MP and the | Remote |
External Demand Limit |
| and Special |
|
| Functional ID has occurred for a |
|
Setpoint |
| Action |
|
| shall discontinue use of the External Demand Limit Setpoint |
|
|
|
|
|
| source and revert to the next higher priority for setpoint |
|
|
|
|
|
| arbitration |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Warning | Latch | All | Continual loss of communication between the MP and the | Remote |
Auxiliary Setpoint Command |
| and Special |
|
| Functional ID has occurred for a |
|
|
| Action |
|
| shall discontinue use of the Auxiliary Setpoint and revert to the |
|
|
|
|
|
| Chilled Water Setpoint based on setpoint arbitration |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Immediate | Latch | All | Continual loss of communication between the MP and the | Remote |
High Pressure Cutout Switch |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Immediate | Latch | All | Continual loss of communication between the MP and the | Remote |
Evaporator Water Flow Switch |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Immediate | Latch | All | Continual loss of communication between the MP and the | Remote |
Condenser Water Flow Switch |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Warning | NonLatch | All | Continual loss of communication between the MP and the | Remote |
Local BAS Interface |
| and Special |
|
| Functional ID has occurred for a |
|
|
| Action |
|
| last values sent from BAS |
|
|
|
|
|
|
|
|
Comm Loss: | Circuit | Normal | Latch | All | Continual loss of communication between the MP and the | Remote |
Solenoid Valve |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Cprsr | Immediate | Latch | All | Continual loss of communication between the MP and the | Remote |
Motor Temp/Overload |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Cprsr | Immediate | Latch | All | Continual loss of communication between the MP and the | Remote |
Compressor Run Command |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Circuit | Warning | Latch | All | Continual loss of communication between the MP and the | Remote |
Protection Module Cprsr |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
30 |