Diagnostics
Table 6 - Communication Diagnostics
Notes:
1.The following communication loss diagnostics will not occur unless that input or output is required to be present by the particular configuration and installed options for the chiller.
2.Communication diagnostics (with the exception of "Excessive Loss of Comm" are named by the Functional Name of the input or output that is no longer being heard from by the Main Processor.
Many LLIDs, such as the Quad Relay LLID, have more than one functional output associated with it. A comm loss with such a multiple function board will generate multiple diagnostics. Refer to the Chiller's wiring diagrams to relate the occurrence of multiple communication diagnostics back to the physical llid boards that they have been assigned to (bound).
Diagnostic Name | Effects | Severity | Persistence | Active | Criteria | Reset |
|
|
|
| Modes |
| Level |
|
|
|
| [Inactive |
|
|
|
|
|
| Modes] |
|
|
|
|
|
|
|
|
|
Excessive Loss of Comm | Chiller | Immediate | Latch | All | Loss of comm with 20% or more of the llids configured for the | Remote |
|
|
|
|
| system has been detected. This diagnostic will suppress the |
|
|
|
|
|
| callout of all subsequent comm loss diagnostics. Check power |
|
|
|
|
|
| supply(s) and power disconnects - troubleshoot LLIDS buss |
|
|
|
|
|
| using TechView |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Normal | Latch | All | Continual loss of communication between the MP and the | Remote |
External Auto/Stop |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Normal | Latch | All | Continual loss of communication between the MP and the | Remote |
Emergency Stop |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Warning | Latch | All | Continual loss of communication between the MP and the | Remote |
Ext Ice Building Ctrl Input |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
| shall revert to normal |
|
|
|
|
|
| state. |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Warning | Latch | All | Continual loss of communication between the MP and the | Remote |
Outdoor Air Temperature |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
| configured as an |
|
|
|
|
|
| and use a minimum LPC ignore time of 30 seconds. |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Normal | Latch | All | Continual loss of communication between the MP and the | Remote |
Evap Leaving Water Temp |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Normal | Latch | All | Continual loss of communication between the MP and the | Remote |
Evap Entering Water Temp |
|
|
|
| Functional ID has occurred for a |
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Warning | Latch | All | Continual loss of communication between the MP and the | Remote |
Condenser Leaving Water |
|
|
|
| Functional ID has occurred for a |
|
Temp |
|
|
|
|
|
|
|
|
|
|
|
|
|
Comm Loss: | Chiller | Warning | Latch | All | Continual loss of communication between the MP and the | Remote |
Condenser Entering Water |
|
|
|
| Functional ID has occurred for a |
|
Temp |
|
|
|
|
|
|
|
|
|
|
|
|
|
Comm Loss: | Circuit | Normal | Latch | All | Continual loss of communication between the MP and the | Remote |
Discharge Pressure |
|
|
|
| Functional ID has occurred for a |
|
Transducer |
|
|
|
|
|
|
|
|
|
|
|
|
|
29 |