Trane CGAN 209-214 Diagnostic Name Effects Severity, Active Criteria Reset Modes Level Inactive

Page 29

Diagnostics

Table 6 - Communication Diagnostics

Notes:

1.The following communication loss diagnostics will not occur unless that input or output is required to be present by the particular configuration and installed options for the chiller.

2.Communication diagnostics (with the exception of "Excessive Loss of Comm" are named by the Functional Name of the input or output that is no longer being heard from by the Main Processor.

Many LLIDs, such as the Quad Relay LLID, have more than one functional output associated with it. A comm loss with such a multiple function board will generate multiple diagnostics. Refer to the Chiller's wiring diagrams to relate the occurrence of multiple communication diagnostics back to the physical llid boards that they have been assigned to (bound).

Diagnostic Name

Effects

Severity

Persistence

Active

Criteria

Reset

 

 

 

 

Modes

 

Level

 

 

 

 

[Inactive

 

 

 

 

 

 

Modes]

 

 

 

 

 

 

 

 

 

Excessive Loss of Comm

Chiller

Immediate

Latch

All

Loss of comm with 20% or more of the llids configured for the

Remote

 

 

 

 

 

system has been detected. This diagnostic will suppress the

 

 

 

 

 

 

callout of all subsequent comm loss diagnostics. Check power

 

 

 

 

 

 

supply(s) and power disconnects - troubleshoot LLIDS buss

 

 

 

 

 

 

using TechView

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

External Auto/Stop

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

Emergency Stop

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the

Remote

Ext Ice Building Ctrl Input

 

 

 

 

Functional ID has occurred for a 35-40 second period. Chiller

 

 

 

 

 

 

shall revert to normal (non-ice building) mode regardless of last

 

 

 

 

 

 

state.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the

Remote

Outdoor Air Temperature

 

 

 

 

Functional ID has occurred for a 35-40 second period. If

 

 

 

 

 

 

configured as an air-cooled this diagnostic shall turn on all fans

 

 

 

 

 

 

and use a minimum LPC ignore time of 30 seconds.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

Evap Leaving Water Temp

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

Evap Entering Water Temp

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the

Remote

Condenser Leaving Water

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

Temp

 

 

 

 

 

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the

Remote

Condenser Entering Water

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

Temp

 

 

 

 

 

 

 

 

 

 

 

 

 

Comm Loss:

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

Discharge Pressure

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

Transducer

 

 

 

 

 

 

 

 

 

 

 

 

 

CG-SVU02B-E4

29

Image 29
Contents User Guide General information Safety recommendationsForeword ReceptionTraining WarrantyMaintenance contract Contents Controls Interface OverviewDisplay Screens DynaView InterfaceKeypad Keypad/Display Lockout FeatureMain Screens Main Reports SettingsAuto Stop MP Resetting Sub Modes Description Chiller Level Mode Top Level Mode Description MP ResettingChiller Level Mode Top Level Mode Description Stopped Stopped Sub Modes DescriptionChiller Level Mode Top Level Mode Description Auto Chiller Level Mode Top Level Mode Description Run InhibitRun Inhibit Sub Modes Description Auto Sub Modes DescriptionChiller Level Mode Top Level Mode Description Running Limit Chiller Level Mode Top Level Mode Description RunningWaiting to Start Sub Modes Description Running Sub Modes DescriptionChiller Level Mode Top Level Mode Description Misc Chiller Level Mode Top Level Mode Description Shutting DownShutting Down Sub Modes Description Misc. Sub Modes DescriptionCircuit Level Operating Modes Circuit Level Mode Top Level Mode Description Shutting Down Circuit Level Mode Top Level Mode Description Running LimitCircuit Level Mode Top Level Mode Description Misc Preparing Shutdown Sub Modes DescriptionReports Screen Circuit Ashrae Log Historic DiagnosticsAshrae Chiller Log Description Units Resolution, Default Chiller Settings ScreenSystem Manual Control Settings Feature SettingsCircuit Manual Control Settings Display SettingsChiller Mode Stopped Diagnostics ScreenCD-ROM TechView InterfaceSoftware Download TechView Interface Diagnostics Modes Criteria Reset Inactive Level MP Reset Has Occurred Active Diagnostic Name Effects SeverityCompressor Fault Low Pressure CutoutTemperature Suction Temperature SensorEvaporator Entering Water Temp Sensor Evaporator Leaving WaterHigh Evaporator Water ErrorHigh Pressure Cutout Emergency StopPump Fault Detected Fault DetectedPump 1 or Fan Fault Evaporator WaterActive Criteria Reset Modes Level Inactive Diagnostic Name Effects SeverityDiagnostics Special DynaView Display Message Description Troubleshooting Main Processor Boot Messages and DiagnosticsDiagnostics Event/state Description Programmable Relays Alarms and StatusDefault setting Event/Status CG-SVU02B-E4 CG-SVU02B-E4