Trane CGWN 205-211, CCUN 205-211, CGAN 209-214, CH530 manual Keypad/Display Lockout Feature

Page 7

DynaView Interface

The bottom of the screen (7) is present in all screens and contains the following functions. The contrast (8,9) may require re-adjustment at ambient temperatures significantly different from those present at last adjustment. The other functions are critical to machine operation. The AUTO and STOP keys are used to enable or disable the chiller. The key selected is in black (reverse video). The chiller will stop when the STOP key is touched and after completing the Run Unload mode.

Touching the AUTO key will enable the chiller if no diagnostic is present. (A separate action must be taken to clear active diagnostics.) The AUTO and STOP keys take precedence over the Enter and Cancel keys. (While a setting is being changed, AUTO and STOP keys are recognized even if Enter or Cancel has not been pressed.) The ALARMS button appears only when an alarm is present, and blinks (by alternating between normal and reverse video) to draw attention to a diagnostic condition. Pressing the ALARMS button takes you to the corresponding tab for additional information.

Keypad/Display Lockout Feature

Note: The DynaView display and Touch Screen Lock screen is shown above. This screen is used if the Display and touch screen and lock feature is enabled. Thirty minutes after the last keystroke, this screen is displayed and the Display and Touch Screen is locked out until the sequence "159 <ENTER>" is pressed. Until the proper password is entered, there will be no access to the DynaView screens including all reports, setpoints, and Auto/Stop/Alarms/Interlocks. The password "159" can not be changed from either DynaView or TechView.

For setting changes, use the password "314 <ENTER>".

Figure 2 - Keypad

1

CG-SVU02B-E4

7

Image 7
Contents User Guide Reception Safety recommendationsGeneral information ForewordMaintenance contract WarrantyTraining Contents Controls Interface OverviewDisplay Screens DynaView InterfaceKeypad Keypad/Display Lockout FeatureMain Screens Main Reports SettingsAuto Stop Stopped Sub Modes Description Chiller Level Mode Top Level Mode Description MP ResettingMP Resetting Sub Modes Description Chiller Level Mode Top Level Mode Description StoppedAuto Sub Modes Description Chiller Level Mode Top Level Mode Description Run InhibitChiller Level Mode Top Level Mode Description Auto Run Inhibit Sub Modes DescriptionRunning Sub Modes Description Chiller Level Mode Top Level Mode Description RunningChiller Level Mode Top Level Mode Description Running Limit Waiting to Start Sub Modes DescriptionMisc. Sub Modes Description Chiller Level Mode Top Level Mode Description Shutting DownChiller Level Mode Top Level Mode Description Misc Shutting Down Sub Modes DescriptionCircuit Level Operating Modes Preparing Shutdown Sub Modes Description Circuit Level Mode Top Level Mode Description Running LimitCircuit Level Mode Top Level Mode Description Shutting Down Circuit Level Mode Top Level Mode Description MiscReports Screen Ashrae Chiller Log Historic DiagnosticsCircuit Ashrae Log Description Units Resolution, Default Chiller Settings ScreenDisplay Settings Feature SettingsSystem Manual Control Settings Circuit Manual Control SettingsChiller Mode Stopped Diagnostics ScreenCD-ROM TechView InterfaceSoftware Download TechView Interface Diagnostics Low Pressure Cutout Active Diagnostic Name Effects SeverityModes Criteria Reset Inactive Level MP Reset Has Occurred Compressor FaultTemp Sensor Evaporator Leaving Water Suction Temperature SensorTemperature Evaporator Entering WaterEmergency Stop ErrorHigh Evaporator Water High Pressure CutoutEvaporator Water Fault DetectedPump Fault Detected Pump 1 or Fan FaultActive Criteria Reset Modes Level Inactive Diagnostic Name Effects SeverityDiagnostics Special DynaView Display Message Description Troubleshooting Main Processor Boot Messages and DiagnosticsDiagnostics Default setting Event/Status Programmable Relays Alarms and StatusEvent/state Description CG-SVU02B-E4 CG-SVU02B-E4