Dell 5600W, K812N, 5600R OL HV-US manual Installing Remote Emergency Power-off, Repo Connections

Page 25

5Make any necessary provisions for cord retention and strain relief.

NOTE: Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.

Installing Remote Emergency Power-off

REPO is used to shut down the UPS from a distance. For example, this feature can be used for shutting down the load and the UPS by thermal relay, in the event of room overtemperature. When REPO is activated, the UPS shuts down the output and all its power converters immediately. The UPS logic power remains on to issue an alarm.

The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown procedure initiated by any power management software. Any devices that are operating on battery power are also shut down immediately.

When the REPO switch is reset, the equipment will not return to utility or battery power until the UPS is manually restarted.

The REPO contacts are normally open.

WARNING: The REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation.

CAUTION: The REPO must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The REPO switch must have a minimum rating of 24 Vdc and 20 mA and be a dedicated latching-type switch not tied into any other circuit. The REPO signal must remain active for at least 250 ms for proper operation.

CAUTION: To ensure the UPS stops supplying power to the load during any mode of operation, the input power must be disconnected from the UPS when the emergency power-off function is activated.

NOTE: For Europe, the emergency switch requirements are detailed in Harmonized document HD-384-48 S1,

“Electrical Installation of the Buildings, Part 4: Protection for Safety, Chapter 46: Isolation and Switching.”

REPO Connections

Wire Function

Terminal Wire Size Rating

Suggested Wire Size

 

 

 

REPO

4–0.32 mm2 (12–22 AWG)

0.82 mm2 (18 AWG)

NOTE: The pins must be open to keep the UPS running. If the UPS shuts down because the REPO connector pins are shorted, restart the UPS by re-opening the REPO connector pins and turning on the UPS manually. Maximum resistance in the shorted loop is 10 ohm.

NOTE: Always test the REPO function before applying your critical load to avoid accidental load loss.

Installation 25

Image 25
Contents Users Guide October 2009 164201888 Table of Contents UPS and Battery Care Transporting the UPS Additional UPS FeaturesUPS Status Menu Event Log Menu Testing BatteriesDell Online Rack UPS IntroductionIntroduction What are You Looking For? Find It Here Finding InformationImportant Safety Instructions Safety WarningsSafety Warnings Safety Warnings Inspecting the Equipment InstallationUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet 208V Rear Panel UPS Rear PanelsDell Online Rack UPS Front Panel UPS Front PanelRemoving the Battery Retaining Bracket Rackmount SetupRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the UPS Installing the EBMRepo Connections Installing Remote Emergency Power-offRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Backfeed Protection Devices Typical External Isolating Device InstallationTerminal Position UPS Initial Startup UPS Startup and Shutdown OperationStarting the UPS UPS Shutdown Starting the UPS on BatteryControl Button Functions Control Button Sequence Control Panel FunctionsDisplay Functions Changing the LanguageStartup Screen UPS Status Screen LockedBypass Mode Battery ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveNormal Mode Status Summary Screens Description Battery Test StatusStandby Mode Event Log Battery Status Screens DescriptionMeasurements Control Screens Description Control ScreensSettings Description Available Settings Default Setting SettingsIdentification Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Bypass to Normal Mode Transferring from Normal to Bypass ModeTransferring the UPS Between Modes Retrieving the Event LogBehavior on Overload Controlling Load Segments Through the Display Configuring Load SegmentsConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring the UPS for an EBM Configuring Battery SettingsRunning Automatic Battery Tests Configuring Automatic RestartConfiguring Automatic Battery Tests RS-232 and USB Communication Ports Additional UPS FeaturesRS-232 Communication Port Pin Assignment Dell Network Management Card on a 5600W OL UPS Dell Network Management Card OptionalDell UPS Management Software UPS and Battery Care UPS MaintenanceTransporting the UPS Remove the UPS front cover see Figure Storing the UPS and Batteries When to Replace BatteriesUpdating the UPS Firmware Testing BatteriesSpecifications Rated at Nominal Inputs Regulation Normal Mode Power LevelsRegulation Battery Mode Electrical OutputOperating Temperature Environmental and SafetyTemperature Relative Humidity Safety ConformanceBattery Type Battery ConfigurationBattery Runtimes VoltageAccessing Alarms and Conditions TroubleshootingUPS Status Menu Event Log Menu Typical Alarms and ConditionsAction UPS Troubleshooting Troubleshooting Silencing the Alarm