Dell K812N, 5600W, 5600R OL HV-US manual Event Log, Battery Status Screens Description

Page 39

Table 5. Battery Status Screens

Battery Status Screen

Description

 

 

Battery charging

Batteries are charged in constant current mode.

 

 

Battery floating

Batteries are charged in constant voltage mode.

 

 

Battery resting

Batteries are connected but are not being charged or discharged.

 

(This is part of the normal charging cycle.)

 

 

Battery discharging

Batteries are discharging.

 

 

Battery disconnected

Batteries are unavailable because they are disconnected.

 

 

Charger disabled

The charger is off. You can enable the Charger setting from the Settings menu

 

(see page 45).

 

 

Event Log

The Event Log holds up to 50 events. You can scroll through the event screens, beginning with the most recent event.

NOTE: The date format depends on the language selection.

The first row of each event screen contains the date (MM/DD/YYYY) and time (hh:mm:ss) at which the event occurred. The second row contains the type of event and code. The event description begins on the third row and may continue to the fourth row. The bottom right corner of the event screen displays two numbers: an ordering number of the event in the log, followed by the total number of events in the log.

If there are no events in the log, the event screen displays “No events in log.”

See “Retrieving the Event Log” on page 47.

Operation 39

Image 39
Contents Users Guide October 2009 164201888 Table of Contents UPS and Battery Care Transporting the UPS Additional UPS FeaturesUPS Status Menu Event Log Menu Testing BatteriesDell Online Rack UPS IntroductionIntroduction What are You Looking For? Find It Here Finding InformationImportant Safety Instructions Safety WarningsSafety Warnings Safety Warnings Inspecting the Equipment InstallationUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet 208V Rear Panel UPS Rear PanelsDell Online Rack UPS Front Panel UPS Front PanelRemoving the Battery Retaining Bracket Rackmount SetupRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the UPS Installing the EBMRepo Connections Installing Remote Emergency Power-offRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Backfeed Protection Devices Typical External Isolating Device InstallationTerminal Position UPS Initial Startup Operation UPS Startup and ShutdownStarting the UPS UPS Shutdown Starting the UPS on BatteryControl Button Functions Control Button Sequence Control Panel FunctionsChanging the Language Display FunctionsStartup Screen UPS Status Screen LockedUPS General Alarms Active Battery ModeBypass Mode Bad Battery Detected or Battery DisconnectedStatus Summary Screens Description Battery Test Status Normal ModeStandby Mode Event Log Battery Status Screens DescriptionMeasurements Control Screens Description Control ScreensSettings Settings Description Available Settings Default SettingIdentification Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Retrieving the Event Log Transferring from Normal to Bypass ModeTransferring from Bypass to Normal Mode Transferring the UPS Between ModesBehavior on Overload Controlling Load Segments Through the Display Configuring Load SegmentsConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring the UPS for an EBM Configuring Battery SettingsConfiguring Automatic Restart Running Automatic Battery TestsConfiguring Automatic Battery Tests RS-232 and USB Communication Ports Additional UPS FeaturesRS-232 Communication Port Pin Assignment Dell Network Management Card on a 5600W OL UPS Dell Network Management Card OptionalDell UPS Management Software UPS Maintenance UPS and Battery CareTransporting the UPS Remove the UPS front cover see Figure Storing the UPS and Batteries When to Replace BatteriesUpdating the UPS Firmware Testing BatteriesSpecifications Electrical Output Power LevelsRated at Nominal Inputs Regulation Normal Mode Regulation Battery ModeSafety Conformance Environmental and SafetyOperating Temperature Temperature Relative HumidityVoltage Battery ConfigurationBattery Type Battery RuntimesTroubleshooting Accessing Alarms and ConditionsUPS Status Menu Event Log Menu Typical Alarms and ConditionsAction UPS Troubleshooting Troubleshooting Silencing the Alarm