Dell 5600R OL HV-US, K812N, 5600W manual Repo Connector

Page 26

Remove Jumper if

Installed

Figure 16. REPO Connector

To install the REPO switch:

1Verify that the UPS is off and disconnected from utility power.

2Remove the REPO connector from the accessory kit.

NOTE: Verify that there is no jumper installed in the REPO connector. If a jumper is installed, remove it before connecting to the REPO port. See Figure 16.

3Connect the REPO connector to the REPO port labeled “IN” on the UPS rear panel.

CAUTION: If you are daisy-chaining the REPO function, observe the following connection requirements to avoid unintentional shutdown of the UPS:

SThe left pin of the REPO port labeled “OUT” on the first UPS must be connected to the left pin of the REPO port labeled “IN” on the second UPS.

SThe right pin of the REPO port labeled “OUT” on the first UPS must be connected to the right pin of the REPO port labeled “IN.” on the second UPS.

4Optional. If you are daisy-chaining the REPO function with another UPS, you can shut down the entire system using a single switch.

Connect the second REPO connector to the REPO port labeled “OUT.”

NOTE: A separate contact must simultaneously cause UPS input AC power to be removed.

5Connect the switch or circuit to the REPO connector on the UPS rear panel using insulated 0.75 mm2–0.5 mm2 (18–20 AWG) wire.

6Optional. If you are daisy-chaining the REPO function with another UPS, connect the REPO port labeled “OUT” to the REPO port labeled “IN” on the next UPS.

26 Installation

Image 26
Contents Users Guide October 2009 164201888 Table of Contents Additional UPS Features UPS and Battery Care Transporting the UPSTesting Batteries UPS Status Menu Event Log MenuIntroduction Dell Online Rack UPSIntroduction Finding Information What are You Looking For? Find It HereSafety Warnings Important Safety InstructionsSafety Warnings Safety Warnings Installation Inspecting the EquipmentUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet UPS Rear Panels 208V Rear PanelUPS Front Panel Dell Online Rack UPS Front PanelRackmount Setup Removing the Battery Retaining BracketRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the EBM Installing the UPSInstalling Remote Emergency Power-off Repo ConnectionsRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Typical External Isolating Device Installation Backfeed Protection DevicesTerminal Position UPS Initial Startup Starting the UPS OperationUPS Startup and Shutdown Starting the UPS on Battery UPS ShutdownControl Panel Functions Control Button Functions Control Button SequenceStartup Screen Changing the LanguageDisplay Functions Screen Locked UPS StatusBad Battery Detected or Battery Disconnected Battery ModeBypass Mode UPS General Alarms ActiveStandby Mode Status Summary Screens Description Battery Test StatusNormal Mode Battery Status Screens Description Event LogMeasurements Control Screens Control Screens DescriptionIdentification SettingsSettings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring the UPS Between Modes Transferring from Normal to Bypass ModeTransferring from Bypass to Normal Mode Retrieving the Event LogBehavior on Overload Configuring Load Segments Controlling Load Segments Through the DisplayConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring Battery Settings Configuring the UPS for an EBMConfiguring Automatic Battery Tests Configuring Automatic RestartRunning Automatic Battery Tests Additional UPS Features RS-232 and USB Communication PortsRS-232 Communication Port Pin Assignment Dell Network Management Card Optional Dell Network Management Card on a 5600W OL UPSDell UPS Management Software Transporting the UPS UPS MaintenanceUPS and Battery Care Remove the UPS front cover see Figure When to Replace Batteries Storing the UPS and BatteriesTesting Batteries Updating the UPS FirmwareSpecifications Regulation Battery Mode Power LevelsRated at Nominal Inputs Regulation Normal Mode Electrical OutputTemperature Relative Humidity Environmental and SafetyOperating Temperature Safety ConformanceBattery Runtimes Battery ConfigurationBattery Type VoltageUPS Status Menu TroubleshootingAccessing Alarms and Conditions Typical Alarms and Conditions Event Log MenuAction UPS Troubleshooting Troubleshooting Silencing the Alarm