Dell 5600W, K812N, 5600R OL HV-US manual Testing Batteries, Updating the UPS Firmware

Page 61

Testing Batteries

For a battery test to run:

SThe batteries must be fully charged.

SThe UPS must be in Normal mode with no active alarms.

SThe load must be higher than 10%.

To test batteries:

1Connect the UPS to utility power for at least 48 hours to charge the batteries.

2Press the button for one second to go to the main menu selection and scroll down to the Control menu using the button.

3Press the button to enter the Control menu.

4Use the button to scroll to the Battery Test option.

5Press the button to start the battery test.

During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25% of the original expected runtime. The status screen displays “Battery test running” and the percentage of the test completed. The results display on the UPS status screen when complete.

Updating the UPS Firmware

To keep the UPS firmware updated with the latest improvements and benefits, visit www.dell.com for updates. You can download the latest firmware version and the instructions for installing it.

UPS Maintenance

61

Image 61
Contents Users Guide October 2009 164201888 Table of Contents UPS and Battery Care Transporting the UPS Additional UPS FeaturesUPS Status Menu Event Log Menu Testing BatteriesDell Online Rack UPS IntroductionIntroduction What are You Looking For? Find It Here Finding InformationImportant Safety Instructions Safety WarningsSafety Warnings Safety Warnings Inspecting the Equipment InstallationUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet 208V Rear Panel UPS Rear PanelsDell Online Rack UPS Front Panel UPS Front PanelRemoving the Battery Retaining Bracket Rackmount SetupRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the UPS Installing the EBMRepo Connections Installing Remote Emergency Power-offRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Backfeed Protection Devices Typical External Isolating Device InstallationTerminal Position UPS Initial Startup UPS Startup and Shutdown OperationStarting the UPS UPS Shutdown Starting the UPS on BatteryControl Button Functions Control Button Sequence Control Panel FunctionsDisplay Functions Changing the LanguageStartup Screen UPS Status Screen LockedBypass Mode Battery ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveNormal Mode Status Summary Screens Description Battery Test StatusStandby Mode Event Log Battery Status Screens DescriptionMeasurements Control Screens Description Control ScreensSettings Description Available Settings Default Setting SettingsIdentification Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Bypass to Normal Mode Transferring from Normal to Bypass ModeTransferring the UPS Between Modes Retrieving the Event LogBehavior on Overload Controlling Load Segments Through the Display Configuring Load SegmentsConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring the UPS for an EBM Configuring Battery SettingsRunning Automatic Battery Tests Configuring Automatic RestartConfiguring Automatic Battery Tests RS-232 and USB Communication Ports Additional UPS FeaturesRS-232 Communication Port Pin Assignment Dell Network Management Card on a 5600W OL UPS Dell Network Management Card OptionalDell UPS Management Software UPS and Battery Care UPS MaintenanceTransporting the UPS Remove the UPS front cover see Figure Storing the UPS and Batteries When to Replace BatteriesUpdating the UPS Firmware Testing BatteriesSpecifications Rated at Nominal Inputs Regulation Normal Mode Power LevelsRegulation Battery Mode Electrical OutputOperating Temperature Environmental and SafetyTemperature Relative Humidity Safety ConformanceBattery Type Battery ConfigurationBattery Runtimes VoltageAccessing Alarms and Conditions TroubleshootingUPS Status Menu Event Log Menu Typical Alarms and ConditionsAction UPS Troubleshooting Troubleshooting Silencing the Alarm