Dell 5600W, K812N, 5600R OL HV-US manual Troubleshooting

Page 70

Table 16. Typical Alarms and Conditions (continued)

Alarm or Condition

Possible Cause

Action

Output Overload Level 2

The load level is >101% and

(Alarm 159)

<110% of the UPS rating.

 

Continuous Alarm

 

Remove some of the equipment from the UPS. The UPS continues to operate, but transfers to Fault mode in two minutes.

The alarm clears when the load drops below 5% of the set point.

Output Overload Level 3

The load is >110% of the UPS

Remove some of the equipment from the

(Alarm 162)

rating.

UPS. The UPS continues to operate, but

 

transfers to Fault mode in 300 ms to one

Continuous Alarm

 

 

second.

 

 

 

 

The alarm clears when the load drops below

 

 

5% of the set point.

 

 

 

Battery DC Over Voltage

Battery voltage levels have

The UPS turns off the charger until the next

(Alarm 68)

exceeded the maximum

power recycle. Contact your service

allowable limits.

representative.

Continuous Alarm

 

 

 

 

 

Charger Failure

A battery charger fault has been

The UPS turns off the charger until the next

(Alarm 34)

detected.

power recycle. Contact your service

 

representative.

Continuous Alarm

 

 

 

 

 

 

Inverter AC Over Voltage

The UPS has detected

The UPS transfers to Bypass mode if

(Alarm 0)

abnormally high output voltage

supporting the load.

levels.

 

Intermittent Alarm

 

 

 

 

 

 

Inverter AC Under Voltage

The UPS has detected

The UPS transfers to Bypass mode if

(Alarm 1)

abnormally low output voltage

supporting the load.

levels.

 

Continuous Alarm

 

 

 

 

 

 

Bypass AC Over Voltage

The measured voltage on

A notification alarm is generated and the

(Notice 3)

Bypass has exceeded the upper

notice is logged.

voltage limit specification for

 

Intermittent Alarm

Only apply this setting when Qualify Bypass is

bypass operation.

set to Always and utility is present, but above

 

 

 

 

 

the bypass overvoltage range.

 

 

Do not apply this setting if a Utility Not

 

 

Present alarm is active.

 

 

 

70 Troubleshooting

Image 70
Contents Users Guide October 2009 164201888 Table of Contents Additional UPS Features UPS and Battery Care Transporting the UPSTesting Batteries UPS Status Menu Event Log MenuIntroduction Dell Online Rack UPSIntroduction Finding Information What are You Looking For? Find It HereSafety Warnings Important Safety InstructionsSafety Warnings Safety Warnings Installation Inspecting the EquipmentUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet UPS Rear Panels 208V Rear PanelUPS Front Panel Dell Online Rack UPS Front PanelRackmount Setup Removing the Battery Retaining BracketRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the EBM Installing the UPSInstalling Remote Emergency Power-off Repo ConnectionsRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Typical External Isolating Device Installation Backfeed Protection DevicesTerminal Position UPS Initial Startup UPS Startup and Shutdown OperationStarting the UPS Starting the UPS on Battery UPS ShutdownControl Panel Functions Control Button Functions Control Button SequenceDisplay Functions Changing the LanguageStartup Screen Screen Locked UPS StatusBad Battery Detected or Battery Disconnected Battery ModeBypass Mode UPS General Alarms ActiveNormal Mode Status Summary Screens Description Battery Test StatusStandby Mode Battery Status Screens Description Event LogMeasurements Control Screens Control Screens DescriptionSettings Description Available Settings Default Setting SettingsIdentification Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring the UPS Between Modes Transferring from Normal to Bypass ModeTransferring from Bypass to Normal Mode Retrieving the Event LogBehavior on Overload Configuring Load Segments Controlling Load Segments Through the DisplayConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring Battery Settings Configuring the UPS for an EBMRunning Automatic Battery Tests Configuring Automatic RestartConfiguring Automatic Battery Tests Additional UPS Features RS-232 and USB Communication PortsRS-232 Communication Port Pin Assignment Dell Network Management Card Optional Dell Network Management Card on a 5600W OL UPSDell UPS Management Software UPS and Battery Care UPS MaintenanceTransporting the UPS Remove the UPS front cover see Figure When to Replace Batteries Storing the UPS and BatteriesTesting Batteries Updating the UPS FirmwareSpecifications Regulation Battery Mode Power LevelsRated at Nominal Inputs Regulation Normal Mode Electrical OutputTemperature Relative Humidity Environmental and SafetyOperating Temperature Safety ConformanceBattery Runtimes Battery ConfigurationBattery Type VoltageAccessing Alarms and Conditions TroubleshootingUPS Status Menu Typical Alarms and Conditions Event Log MenuAction UPS Troubleshooting Troubleshooting Silencing the Alarm
Related manuals
Manual 8 pages 24.59 Kb