Table 16. Typical Alarms and Conditions (continued)
Alarm or Condition | Possible Cause | Action |
| |
|
|
| ||
Bypass AC Under Voltage | The measured voltage on | A notification alarm is generated and the | ||
(Notice 4) | Bypass is less than the upper | notice is logged. |
| |
voltage limit specification for |
|
| ||
Intermittent Alarm | Only apply this setting when Qualify Bypass is | |||
bypass operation. | ||||
set to Always and utility is present, but below | ||||
| ||||
|
| |||
|
| the bypass undervoltage range. |
| |
|
| Do not apply this setting if a Utility Not | ||
|
| Present alarm is active. |
| |
|
|
| ||
Bypass Under/Over Freq | The measured voltage on | A notification alarm is generated and the | ||
(Notice 5) | Bypass is | notice is logged. |
| |
the upper or lower voltage limit |
|
| ||
Intermittent Alarm | Only apply this setting when Qualify Bypass is | |||
specification for bypass | ||||
set to Always and utility is present, but outside | ||||
| ||||
| operation. | |||
| the bypass frequency range. |
| ||
|
|
| ||
|
| Do not apply this setting if a Utility Not | ||
|
| Present alarm is active. |
| |
|
|
|
| |
Rectifier Input Over Current | The UPS has detected that | The UPS transfers to Battery mode if |
| |
(Alarm 26) | rectifier input current limits | supporting the load. |
| |
have been exceeded. |
|
| ||
Continuous Alarm |
|
| ||
|
|
| ||
|
|
|
| |
Inverter Output Over | The UPS has detected that the | The UPS transfers to Bypass mode if |
| |
Current | inverter output current limits | supporting the load. |
| |
(Alarm 27) | have been exceeded. |
|
| |
|
|
| ||
Continuous Alarm |
|
|
| |
|
|
|
| |
DC Link Over Voltage | The link or rail voltage has | The UPS transfers to Battery mode if |
| |
(Alarm 28) | exceeded its upper threshold | supporting the load. |
| |
limit. |
|
| ||
Continuous Alarm |
|
| ||
|
|
| ||
|
|
|
| |
DC Link Under Voltage | The link or rail voltage has | The UPS transfers to Battery mode if |
| |
(Alarm 29) | dropped below its lower | supporting the load. |
| |
threshold limit. |
|
| ||
Intermittent Alarm |
|
| ||
|
|
| ||
|
|
|
| |
DC Link Imbalance | The internal ± DC bus (DC | The UPS transfers to Battery mode if |
| |
(Alarm 1234) | rail) voltages generated in the | supporting the load. |
| |
UPS are imbalanced. |
|
| ||
Intermittent Alarm |
|
| ||
|
|
| ||
|
|
|
| |
Rectifier Fault | The UPS has detected a fault in | Contact your service representative. |
| |
(Alarm 30) | the rectifier circuit while |
|
| |
attempting recovery from |
|
| ||
Continuous Alarm |
|
| ||
Bypass mode or Converter |
|
| ||
|
|
| ||
| mode. |
|
| |
|
|
|
| |
|
| Troubleshooting | 71 |