Dell 5600R OL HV-US, K812N, 5600W manual Troubleshooting

Page 71

Table 16. Typical Alarms and Conditions (continued)

Alarm or Condition

Possible Cause

Action

 

 

 

 

Bypass AC Under Voltage

The measured voltage on

A notification alarm is generated and the

(Notice 4)

Bypass is less than the upper

notice is logged.

 

voltage limit specification for

 

 

Intermittent Alarm

Only apply this setting when Qualify Bypass is

bypass operation.

set to Always and utility is present, but below

 

 

 

 

 

the bypass undervoltage range.

 

 

 

Do not apply this setting if a Utility Not

 

 

Present alarm is active.

 

 

 

 

Bypass Under/Over Freq

The measured voltage on

A notification alarm is generated and the

(Notice 5)

Bypass is out-of-range for either

notice is logged.

 

the upper or lower voltage limit

 

 

Intermittent Alarm

Only apply this setting when Qualify Bypass is

specification for bypass

set to Always and utility is present, but outside

 

 

operation.

 

the bypass frequency range.

 

 

 

 

 

 

Do not apply this setting if a Utility Not

 

 

Present alarm is active.

 

 

 

 

 

Rectifier Input Over Current

The UPS has detected that

The UPS transfers to Battery mode if

 

(Alarm 26)

rectifier input current limits

supporting the load.

 

have been exceeded.

 

 

Continuous Alarm

 

 

 

 

 

 

 

 

 

Inverter Output Over

The UPS has detected that the

The UPS transfers to Bypass mode if

 

Current

inverter output current limits

supporting the load.

 

(Alarm 27)

have been exceeded.

 

 

 

 

 

Continuous Alarm

 

 

 

 

 

 

 

DC Link Over Voltage

The link or rail voltage has

The UPS transfers to Battery mode if

 

(Alarm 28)

exceeded its upper threshold

supporting the load.

 

limit.

 

 

Continuous Alarm

 

 

 

 

 

 

 

 

 

DC Link Under Voltage

The link or rail voltage has

The UPS transfers to Battery mode if

 

(Alarm 29)

dropped below its lower

supporting the load.

 

threshold limit.

 

 

Intermittent Alarm

 

 

 

 

 

 

 

 

 

DC Link Imbalance

The internal ± DC bus (DC

The UPS transfers to Battery mode if

 

(Alarm 1234)

rail) voltages generated in the

supporting the load.

 

UPS are imbalanced.

 

 

Intermittent Alarm

 

 

 

 

 

 

 

 

 

Rectifier Fault

The UPS has detected a fault in

Contact your service representative.

 

(Alarm 30)

the rectifier circuit while

 

 

attempting recovery from

 

 

Continuous Alarm

 

 

Bypass mode or Converter

 

 

 

 

 

 

mode.

 

 

 

 

 

 

 

 

Troubleshooting

71

Image 71
Contents Users Guide October 2009 164201888 Table of Contents UPS and Battery Care Transporting the UPS Additional UPS FeaturesUPS Status Menu Event Log Menu Testing BatteriesDell Online Rack UPS IntroductionIntroduction What are You Looking For? Find It Here Finding InformationImportant Safety Instructions Safety WarningsSafety Warnings Safety Warnings Inspecting the Equipment InstallationUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet 208V Rear Panel UPS Rear PanelsDell Online Rack UPS Front Panel UPS Front PanelRemoving the Battery Retaining Bracket Rackmount SetupRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the UPS Installing the EBMRepo Connections Installing Remote Emergency Power-offRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Backfeed Protection Devices Typical External Isolating Device InstallationTerminal Position UPS Initial Startup Starting the UPS OperationUPS Startup and Shutdown UPS Shutdown Starting the UPS on BatteryControl Button Functions Control Button Sequence Control Panel FunctionsStartup Screen Changing the LanguageDisplay Functions UPS Status Screen LockedUPS General Alarms Active Battery ModeBypass Mode Bad Battery Detected or Battery DisconnectedStandby Mode Status Summary Screens Description Battery Test StatusNormal Mode Event Log Battery Status Screens DescriptionMeasurements Control Screens Description Control ScreensIdentification SettingsSettings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Retrieving the Event Log Transferring from Normal to Bypass ModeTransferring from Bypass to Normal Mode Transferring the UPS Between ModesBehavior on Overload Controlling Load Segments Through the Display Configuring Load SegmentsConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring the UPS for an EBM Configuring Battery SettingsConfiguring Automatic Battery Tests Configuring Automatic RestartRunning Automatic Battery Tests RS-232 and USB Communication Ports Additional UPS FeaturesRS-232 Communication Port Pin Assignment Dell Network Management Card on a 5600W OL UPS Dell Network Management Card OptionalDell UPS Management Software Transporting the UPS UPS MaintenanceUPS and Battery Care Remove the UPS front cover see Figure Storing the UPS and Batteries When to Replace BatteriesUpdating the UPS Firmware Testing BatteriesSpecifications Electrical Output Power LevelsRated at Nominal Inputs Regulation Normal Mode Regulation Battery ModeSafety Conformance Environmental and SafetyOperating Temperature Temperature Relative HumidityVoltage Battery ConfigurationBattery Type Battery RuntimesUPS Status Menu TroubleshootingAccessing Alarms and Conditions Event Log Menu Typical Alarms and ConditionsAction UPS Troubleshooting Troubleshooting Silencing the Alarm
Related manuals
Manual 8 pages 24.59 Kb