Dell 5600W, K812N, 5600R OL HV-US manual Settings Description Available Settings Default Setting

Page 43

Table 7. Settings (continued)

Description

Available Settings

Default Setting

 

 

 

Set Date and Time

Set Month, Day, Year, Hours, Minutes, and Seconds

 

 

Date: mm/dd/yyyy

01/01/2009

 

Time: hh:mm:ss

12:00:00

 

NOTE: The date format is dependent on the

 

 

language selection.

 

NOTE: Time is a 24-hour clock.

Control Commands from Serial Port

[Enabled] [Disabled]

Enabled

If Enabled, control commands are accepted through the serial port, USB ports, or option card.

If Disabled, configuration and load control commands are restricted to LCD only.

Output Voltage

[Auto-sensing]

Auto-sensing

 

 

 

 

[200V] [208V]

 

 

 

 

 

[220V] [230V] [240V]

 

 

 

 

Output Frequency

[50Hz] [60Hz] [Auto-sensing]

Auto-sensing

 

 

 

Overload Alarm Level

[10%] [20%] [30%]...[100%]

100%

 

If 100%, the UPS issues an Output Overload alarm

 

 

at load > 100%.

 

 

NOTE: Output Overload Level 1 by default is set to

 

 

100% and is configurable from 10% to 100% in 10%

 

 

increments through the LCD setting menu. This

 

 

feature allows customers to be alerted before the

 

 

UPS has reached its rated capacity limits.

 

 

 

 

Automatic Start Delay

[Off] [0s] [1s] [2s]...[32767s]

LS1 0s

 

See “Configuring Load Segments” on page 49.

LS2 1s

 

 

 

Automatic on Battery Shutdown

[Off] [0s] [1s] [2s]...[32767s]

Off

 

See “Configuring Load Segments” on page 49.

 

 

 

 

Start on Battery

[Enabled] [Disabled]

Enabled

 

NOTE: Battery start is disabled from the factory and

 

 

remains disabled until the UPS has been powered

 

 

from utility and enters Standby mode. After the

 

 

UPS has been started once from utility, the Start on

 

 

Battery feature is automatically enabled. If this is set

 

 

by the user, it remains set.

 

 

 

 

Operation 43

Image 43
Contents Users Guide October 2009 164201888 Table of Contents UPS and Battery Care Transporting the UPS Additional UPS FeaturesUPS Status Menu Event Log Menu Testing BatteriesDell Online Rack UPS IntroductionIntroduction What are You Looking For? Find It Here Finding InformationImportant Safety Instructions Safety WarningsSafety Warnings Safety Warnings Inspecting the Equipment InstallationUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet 208V Rear Panel UPS Rear PanelsDell Online Rack UPS Front Panel UPS Front PanelRemoving the Battery Retaining Bracket Rackmount SetupRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the UPS Installing the EBMRepo Connections Installing Remote Emergency Power-offRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Backfeed Protection Devices Typical External Isolating Device InstallationTerminal Position UPS Initial Startup UPS Startup and Shutdown OperationStarting the UPS UPS Shutdown Starting the UPS on BatteryControl Button Functions Control Button Sequence Control Panel FunctionsDisplay Functions Changing the LanguageStartup Screen UPS Status Screen LockedUPS General Alarms Active Battery ModeBypass Mode Bad Battery Detected or Battery DisconnectedNormal Mode Status Summary Screens Description Battery Test StatusStandby Mode Event Log Battery Status Screens DescriptionMeasurements Control Screens Description Control ScreensSettings Description Available Settings Default Setting SettingsIdentification Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Retrieving the Event Log Transferring from Normal to Bypass ModeTransferring from Bypass to Normal Mode Transferring the UPS Between ModesBehavior on Overload Controlling Load Segments Through the Display Configuring Load SegmentsConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring the UPS for an EBM Configuring Battery SettingsRunning Automatic Battery Tests Configuring Automatic RestartConfiguring Automatic Battery Tests RS-232 and USB Communication Ports Additional UPS FeaturesRS-232 Communication Port Pin Assignment Dell Network Management Card on a 5600W OL UPS Dell Network Management Card OptionalDell UPS Management Software UPS and Battery Care UPS MaintenanceTransporting the UPS Remove the UPS front cover see Figure Storing the UPS and Batteries When to Replace BatteriesUpdating the UPS Firmware Testing BatteriesSpecifications Electrical Output Power LevelsRated at Nominal Inputs Regulation Normal Mode Regulation Battery ModeSafety Conformance Environmental and SafetyOperating Temperature Temperature Relative HumidityVoltage Battery ConfigurationBattery Type Battery RuntimesAccessing Alarms and Conditions TroubleshootingUPS Status Menu Event Log Menu Typical Alarms and ConditionsAction UPS Troubleshooting Troubleshooting Silencing the Alarm