Dell 5600R OL HV-US Typical External Isolating Device Installation, Backfeed Protection Devices

Page 29

5Insert the conduit through the wiring access entry and attach the conduit fitting to the panel. Strip 0.5(1.5 cm) of insulation from the end of each incoming wire.

CAUTION: If the UPS does not have an automatic protection device against current backfeed, Dell recommends installing an external isolating device (see Figure 19). After the device is installed, you must add a warning label with the following wording or the equivalent on the external AC contactor:

RISK OF VOLTAGE BACKFEED. Isolate the UPS before operating on this circuit, then check for hazardous voltage between all terminals.

External Distribution Panel

QT

L/L1

N/L2

B

UPS

L/L1

N/L2

Legend

BCoil Remote Switch

QMagneto-Thermal Input Main Switch

TAC Contactor ( see Table 1)

N/L2 Neutral/L2

L/L1

L1 Line Input

Figure 19. Typical External Isolating Device Installation

The following table lists AC contactors that can be used as backfeed protection devices.

Table 1. Backfeed Protection Devices

Manufacturer

Type

Rating

 

 

 

Tianshui 213 Electrical Apparatus Co., Ltd.

GSC1(CJX4-d)-4011

220-240 Vac, 42 FLA

(E203071)

 

 

 

 

 

Moeller GMBH

DILM(C)32-10

600 V, 40A

 

 

 

LS Industrial Systems Co., Ltd. (E108780)

GMC(D)-32

600 Vac, 45A

 

 

 

Installation 29

Image 29
Contents Users Guide October 2009 164201888 Table of Contents UPS and Battery Care Transporting the UPS Additional UPS FeaturesUPS Status Menu Event Log Menu Testing BatteriesDell Online Rack UPS IntroductionIntroduction What are You Looking For? Find It Here Finding InformationImportant Safety Instructions Safety WarningsSafety Warnings Safety Warnings Inspecting the Equipment InstallationUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet 208V Rear Panel UPS Rear PanelsDell Online Rack UPS Front Panel UPS Front PanelRemoving the Battery Retaining Bracket Rackmount SetupRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Snap the UPS front cover into place see Figure Installing the UPS Installing the EBMRepo Connections Installing Remote Emergency Power-offRepo Connector Hardwiring the UPS Input Circuit Breaker Diagram Backfeed Protection Devices Typical External Isolating Device InstallationTerminal Position UPS Initial Startup Starting the UPS OperationUPS Startup and Shutdown UPS Shutdown Starting the UPS on BatteryControl Button Functions Control Button Sequence Control Panel FunctionsStartup Screen Changing the LanguageDisplay Functions UPS Status Screen LockedBypass Mode Battery ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveStandby Mode Status Summary Screens Description Battery Test StatusNormal Mode Event Log Battery Status Screens DescriptionMeasurements Control Screens Description Control ScreensIdentification SettingsSettings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Bypass to Normal Mode Transferring from Normal to Bypass ModeTransferring the UPS Between Modes Retrieving the Event LogBehavior on Overload Controlling Load Segments Through the Display Configuring Load SegmentsConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring the UPS for an EBM Configuring Battery SettingsConfiguring Automatic Battery Tests Configuring Automatic RestartRunning Automatic Battery Tests RS-232 and USB Communication Ports Additional UPS FeaturesRS-232 Communication Port Pin Assignment Dell Network Management Card on a 5600W OL UPS Dell Network Management Card OptionalDell UPS Management Software Transporting the UPS UPS MaintenanceUPS and Battery Care Remove the UPS front cover see Figure Storing the UPS and Batteries When to Replace BatteriesUpdating the UPS Firmware Testing BatteriesSpecifications Rated at Nominal Inputs Regulation Normal Mode Power LevelsRegulation Battery Mode Electrical OutputOperating Temperature Environmental and SafetyTemperature Relative Humidity Safety ConformanceBattery Type Battery ConfigurationBattery Runtimes VoltageUPS Status Menu TroubleshootingAccessing Alarms and Conditions Event Log Menu Typical Alarms and ConditionsAction UPS Troubleshooting Troubleshooting Silencing the Alarm